Want this question answered?
A 350 MCM copper wire with an insulation factor of 90 degrees C is rated at 325 amps. If the question is referring to maintaining a load of 300 amps then you have to up size the wire size because the conductor is only allowed to be loaded to 80%. A 500MCM copper wire with an insulation factor of 90 degrees C is rated at 395 amps x 80% = 316 amps.
No a #12 wire is only rated for 20 amps. The 40 amp breaker will not protect the #12 wire. A 40 amp breaker should have a #8 wire connected to it which is rated at 45 amps. The only time that a breaker is allowed to be bigger that the wire size rating according to the electrical code is when a motor is connected to the breaker. This is to stop the 300 percent inrush of the motor full load amps from nuisance tripping a smaller sized breaker.
# 4 gauge THHN or THHW is rated for 95 amps and would normally be the correct wire size. However, at 300 ft. from the source, you definetely will have a substantial voltage drop. Therefore, you need to up the conductor size to # 3 gauge.
Without the amperage the device uses this question can not be answered. The size of wire depends upon the amount of amperage a device draws. The voltage is independent of the size of the wire, it is an insulation factor. Most commonly used wire is rated at 300 volts.
You are talking of two different things here. The voltage rating of a wire is based on the insulation factor. Common wire voltages are 300, 600 and 1000 volts. Current rating of a wire is based on the diameter of the wire and measured in AWG. The electrical code states how much current can be legally applied to the wire. Answering your question, the 2 wire cable is probably 300 volt rated and your #14 size wire is rated at 15 amps. Code also states that conductors can only be loaded to 80% continuous load, so 15 x .8 = 12 amps.
There is no such thing as a watt amp. To determine wire size you need to know the current. Watts = Current x Voltage, so if you know the applied voltage to the load that consumes 300 watts you can get the answer. If we assume 120 volts as standard home voltage then current is 25 amps. If you had 240 volts it would be 12.5 amps. In general 14 AWG is 15 Amps 12 AWG is 20 Amps 10 AWG is 30 Amps
A 350 MCM copper wire with an insulation factor of 90 degrees C is rated at 325 amps. If the question is referring to maintaining a load of 300 amps then you have to up size the wire size because the conductor is only allowed to be loaded to 80%. A 500MCM copper wire with an insulation factor of 90 degrees C is rated at 395 amps x 80% = 316 amps.
At least 50mm but with all the de-rating factors it might be 70mm that's if its 2 cable single phase non armoured clipped direct. Check out the tables dopey!!!! FYI 50 mm = 2 inches, 70 mm = 2.75 inches these are not wire sizes, sound more like cable outside diameters. Correct answer The wire size is dependant on the insulation factor on the wire. A few common insulations and corresponding wire sizes for 150 amps are - Size 0 R90 good for 155 amps, also with insulations of RW 75, TWH, TW75, good for 150 amps. Size 000 TW good for 165 amps.
No a #12 wire is only rated for 20 amps. The 40 amp breaker will not protect the #12 wire. A 40 amp breaker should have a #8 wire connected to it which is rated at 45 amps. The only time that a breaker is allowed to be bigger that the wire size rating according to the electrical code is when a motor is connected to the breaker. This is to stop the 300 percent inrush of the motor full load amps from nuisance tripping a smaller sized breaker.
300 Amps if used for service entrance conductors. Table 310.15
#8. It is better to error on the next large size. # 8 THHN 90 degree wire is rated at 45 amps. If there is a possibility that the breaker is connected to a 50 amp load the wire will be undersized. A #6 wire is rated at 65 amps. For continuous use, a load factor of 80% has to be applied. 65 x .8 = 52 amps. The only time the conductor can be smaller than the breaker size is on a motor feeder. Then the breaker is sized at 250% of the nameplate full load amps (FLA) rating of the motor. This is to allow the motor's starting current, which is about 300% FLA, to not trip the breaker on start up.
# 4 gauge THHN or THHW is rated for 95 amps and would normally be the correct wire size. However, at 300 ft. from the source, you definetely will have a substantial voltage drop. Therefore, you need to up the conductor size to # 3 gauge.
Without the amperage the device uses this question can not be answered. The size of wire depends upon the amount of amperage a device draws. The voltage is independent of the size of the wire, it is an insulation factor. Most commonly used wire is rated at 300 volts.
If you use 250 or 300 MCM wire you will need a 2 1/2" weather head. If you use 300 MCM wire then you will need a 3" weather head.
You are talking of two different things here. The voltage rating of a wire is based on the insulation factor. Common wire voltages are 300, 600 and 1000 volts. Current rating of a wire is based on the diameter of the wire and measured in AWG. The electrical code states how much current can be legally applied to the wire. Answering your question, the 2 wire cable is probably 300 volt rated and your #14 size wire is rated at 15 amps. Code also states that conductors can only be loaded to 80% continuous load, so 15 x .8 = 12 amps.
A #3 copper wire with an insulation rating of 75 or 90 degrees C is rated at 100 and 110 amps consecutively. As for the voltage, wire is usually rated in 300, 600 and 1000 volts. Any three of these insulations factors will handle 12 VDC.
The gauge of wire is referenced to the capacity of a wire to carry amperage and has nothing to do with the voltage. The voltage of a wire is determined by the type of insulation that surrounds the wire. The size of the wire is determined by the amperage of the load and the distance from the supply.