For a 5% volt drop of 6 volts the total resistance should be less than 6/8 ohms, 0.75 ohms, which for a total wire run of 500 ft is equivalent to 1.5 ohms per 1000 ft. Wire tables show that a #10 cable should be used. A #12 cable would give a volt drop of 5.3% which would probably be acceptable for occasional use and easier to store.
Extension cords are not used at 5500 volts.
#16 <<>> To load an extension cord to 1725 watts depending on the length of the cord, the bare minimum should be #14. A better size cord and my recommendation would be a #12 wire size extension cord.
you can get an electric shock from an extention cord because if you are Vaccuming your car and you pull the extention cord out of the plug you will get a 2-5 second shock
No, the 220 v and 110 v systems are designed to use a different pin layout for the plugs and sockets, to avoid possibly dangerous cross-connections. The two voltages can not be mixed and equipment for one system cannot be used on the other without a transformer.
Servive jr. Jacket thermal all weather
Extension cords are not used at 5500 volts.
#16 <<>> To load an extension cord to 1725 watts depending on the length of the cord, the bare minimum should be #14. A better size cord and my recommendation would be a #12 wire size extension cord.
you can get an electric shock from an extention cord because if you are Vaccuming your car and you pull the extention cord out of the plug you will get a 2-5 second shock
an electric owl that will kill every 1
no, you should use same amp and volt.
No, the 220 v and 110 v systems are designed to use a different pin layout for the plugs and sockets, to avoid possibly dangerous cross-connections. The two voltages can not be mixed and equipment for one system cannot be used on the other without a transformer.
You can plug an extension cord into another extension cord. A extension cord is to help make doing something easier.
The black and decker corded trimmer does feature an emergencey shut off feature.
form_title= Extension Cord form_header= Install extension cords in your office. What size extension cord do you need?*= _ [50] What color extension cord do you need?*= _ [50] Do you need a 3 prong extension cord?*= () Yes () No
Servive jr. Jacket thermal all weather
Servive jr. Jacket thermal all weather
Yes, but with a heavier gauge wire <<>> If the cord on an electric heater needs to be lengthened as a perminant feature then the whole cord should be replaced with a new cord of the same type and wire size. What this prevents is aquiring bad splice connections at the point the connection is made. Bad splice connections will create hot spots in the cable. If the lengthening of the cord is just a temporary fix, just use an extension cord. The extension cord should be the same wire size as the heater cord. Keep the extension cord under 20 feet in length.