answersLogoWhite

0


Want this question answered?

Be notified when an answer is posted

Add your answer:

Earn +20 pts
Q: What size wire for 3 phase 15 hp 480 volt motor?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering
Related questions

On a 220 volt electric motor which is the neutral wire L1 L2 or L3?

If the motor wire numbers are L1, L2 and L3, it is not a single phase motor. It is a three phase motor. Also for future reference, a 220 volt single phase motor does not use a neutral.


What is the minimum volt rating of wire used in a 3 phase 4160 volt phase to phase system?

5000 volt


What wire size is needed for 415 volt 20hp compressor motor?

A motor can be reckoned at 1.6 kVA per horse-power, so on a 415 v 3-phase suppy the current for 20 HP would be 45 amps. For continuous use the wire size should be 25 mm2


Can you use 240 volt 3 phase to run a machine that is 240 volt single phase?

Yes, if the motor is rated 240 volts 3 phase.There is such a thing as 240 volt 3 phase power.However if you are asking if you can use 240 volts single phase on a three phase motor, then the answer is no.


Can you wire up a 240 volt single phase water heater to 277 volt single phase?

no


What size time delay fuse do you use on a 40 hp 230 volt 3 phase motor?

The electrical code book states that a 40 HP 230 volt three phase motor draws 104 amps. For that motor the wire must be rated for 131 amps, Non time delay fuses at 300 amps, time delay fuses at 175 amps or a 250 amp circuit breaker. When calculating wire sizes and motor protection the motor's full load amperage should be taken from the motor's nameplate.


What size breaker for a 208 volt single phase motor that pulls 1.4 amps?

208 volts is not a common single phase voltage but you could just size your breaker to the capabilities of the conductor. 208 is normally a phase to phase voltage <<>> Many 230 volt motors can be connected to lower voltage supplies. These motors can be connected to supplies of 208 and 200 volts. The code requirement is that the 230 volt full load amperage of the motor be increased by 10% and 15% respectively for wire sizing and breaker selection. To answer the question you will need a two pole 15 amp breaker.


What size wire do you need for a 208 volt 3 phase load that draws 10.5 amps?

The size of conductor needed will be a #14. It should be copper and have an insulation factor of 90 degrees C. The fact that it is a three phase load does not enter into the calculation of the wire size.


Fuse size for 7.5 HP 3 Phase 440 Volt Motor?

The electrical code states that a 7.5 HP 460 volt three phase motor draws 11 amps. For fuse sizes, non time delay - 30 amps, time delay type D - 20 amps and if using a breaker it will be 30 amps. Minimum wire size is #12 and the maximum setting of overload devices will be 13.75 amps


What size wire do you need for 20 amp 220 volt electric motor?

12 AWG in most circumstances.


What size of cable wire used for 500 kva transformer 240 volt 3 phase?

A 10 mm cable is most commonly used for a 500 KVA transformer, 240 volt, 3 phrase. The size of the wire that is used in a transformer is based on the voltage.


What kind and length of electrical wire do you need for a 2 hp single phase 220 volt motor 50 feet away?

The motor would take 10-12 amps which would need wire of 1.5 mm2 or larger. For a permanent installation use the next size, 2.5 mm2 cross section.