The cable that is used to connect from the generator is based on the size in kW's of the generator and the generator's breaker size rated in amps. It usually is a flexible cab-tire 4 wire cable if the generator is a portable type. If it is a stationary generator is has to be wired with a flexible conduit so as not to transmit vibration from the generator to the conduit system.
If it is a portable generator the breaker should be self contained within the generators panel. If the generator is a stationary standby unit a voltage has to be stated to calculate the conductor size and hence the breaker size to protect the conductor. Amps = Watts/Volts.
10 meters of wire
To calculate the wire size you would have to find the amperage. I = W/E, 70000/240 = 291.67 amps. The wire size according to code has to be up sized to 125%. 291.67 x 125% = 364.6. 500MCM copper wire with an insulation factor of 75 and 90 degrees C is rated at 380 and 395 amps respectively. If parallel conductors were used the wire size for 75 degree wire would be 3/0 rated at 200 amps. Parallel conductors for 90 degree wire would be 2/0 rated at 185 amps.
Yes, a well pump can be wired to a generator but to find out how well it will operate the pump's voltage and full load amperage must be stated.
You would need at the minimum a 56 KW generator. In reality you would need a 60KW.
Crank the generator excitation up to 480 or down to 460. For calculations I used 480 volts. A 60kW generator at 480 volts will put out, kW x 1000/1.73 x E x (pf(.9)) = 80 amps. It looks like the machine that is to be run off the generator is a dual voltage machine. Not knowing the HP of the machine wire it to the 460 volt connection. The inrush current might be a problem if the HP is high.
Depends on the wire size you are using. If the generator breaker is a 30 amp then install a 30 amp breaker.
I just came across literature that rated 13-16,000 btuh for each Kw of power.
The cable that is used to connect from the generator is based on the size in kW's of the generator and the generator's breaker size rated in amps. It usually is a flexible cab-tire 4 wire cable if the generator is a portable type. If it is a stationary generator is has to be wired with a flexible conduit so as not to transmit vibration from the generator to the conduit system.
If it is a portable generator the breaker should be self contained within the generators panel. If the generator is a stationary standby unit a voltage has to be stated to calculate the conductor size and hence the breaker size to protect the conductor. Amps = Watts/Volts.
There is no way to answer without knowing the wattage rating of the 9 volt generator. A generator's wattage rating depends on the size of the wire in it, the wattage of the rectifiers if it is a DC generator, and the horse power of the engine or motor that is available to turn the generator.
To answer this question a voltage must be given to find the current output. Also whether the generator is three phase or single phase.
Magnets and wire.
In conduit? direct burial? distance?
An electrical generator works by moving a coil of wire relative to a magnetic field.
10 meters of wire