Want this question answered?
Read the tag on the condenser, it will be noted as LRA. Be sure to check the LRA for the fan as well and add them together for the total. If it is not listed on the tag it will certainly be listed seperately on both the compressor and the fan motor. LRA = Locked Rotor Amps.
as per my knowledge 1 ton = 36 LRA
The simple answer is yes. The long answer requires info from you. There are two power requirements, running and starting. AC Compressors require an enormous boost of power to get them started, sometimes 5-7 times the running power. To find your running watts, we need to know the SEER rating, usually listed on the air handler. Newer units must be at least 11 SEER. 1 ton = 12,000 btus, so you have 30,000 btus. Divide this by the seer, and that's your running wattage. Even if your seer is only 10, that's only 3000 watts. Seems like not much. Now look at the outside unit to find the LRA. This is the locked rotor amp draw, which is a good indicator of the required amperage to start the unit. For example, my unit runs on 16 amps, and has an 88 amp start requirement. Now you can see how huge the start amps are. So a tiny 2.8 ton ac unit will need an 18,000 watt generator to get going! What you will need to do is install a "hard start" device on the outside unit. Its basically a large capacitor used to get the compressor going without the need for huge amps. Some claim they can cut the start amps in half. They cost $20-50, have 2 wires and are easy to install, can be installed and left in all the time, prolongs the life of the compressor and also prevents your lights from dimming when the ac kicks on. Make sure to get a properly sized one, as too big will cause big problems. The only way to know for sure is to install the hard start kit and then have someone actually measure the amp draw. Good luck.
There are several amperage ratings on AC compressors/motors. Locked Motor Amperage (LRA) is the amperage that the motor is fused for. The load of the motor is expressed in amperage or wattage, which is probably the case here. Low amperage readings on an AC unit being charged by amperage load would indicate low freon. High amperage readings indicate overcharge when charging by the amperage load. AC units are not accurately charged by amperage readings and the efficiency of motors is not expressed in amperage readings.
You add up all of the current draws, 1 + 8.5 + 1 + 10 = 20.5 amps. If you say that all of this load is on a 15 amp circuit then you must get a lot of tripping of the breaker. If the equipment was on a two pole 15 amp breaker then there would be no problem as the motor current would only be half and the rest of the equipment would operate on the three wire feeding this equipment's neutral. To over come the starting current of the motor, a factor of 250 % should be used. 10 x 250% = 25 amps. This type of load should be on a breaker of its own. A generator that will start and run this load should be 35.5 amps x 120 volts = 4260 watts. If like you say its is all on a 15 amp breaker then W = A x V = 15 x 120 = 1800 bare minimum.
Compresser lra fulafme
How many lra 1ton 3 phase compressor
The LRA could be around 15 to 20amps but this can vary , to get the precise LRA for your specific compressor you can check the technical specification provided the manufacturer
LRA stands for Lock Rotor Ampere on compressor and means that it is a high inrush current during starting period of the compressor. Ercona...
Apply an ammeter to the common wire of the compressor and turn power on. The highest peak amps are the LRA.
There is 36.7 IRA that is in a one ton of air compressor.
LRA245 convert to ton 220 3phase
LRA stands for the Lord's resistance army
Read the tag on the condenser, it will be noted as LRA. Be sure to check the LRA for the fan as well and add them together for the total. If it is not listed on the tag it will certainly be listed seperately on both the compressor and the fan motor. LRA = Locked Rotor Amps.
how many LRA in 37,000btu
lra adit
Redevelopment Agency (LRA) Audit Reports