answersLogoWhite

0


Best Answer

The short answer is no.

The long answer is no, not if you are using standard 100-120 volt or 220-240volts found in most (all?) countries

The following is a simplified best case scenario, which incorrectly assumes a power factor of 1.

Power = Volts * Amps

Watts = Volts * AMPS (Actually VA = Volts * Amps, but VA=Watts in best case

scenario)

but 10kw > 240 * 32.

David

User Avatar

Wiki User

13y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Will a single phase 32 amp distro run 10kw?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Can I plug a 63 amp 3 phase lead coming from a 30 kva generator into a 125 amp 3 phase inlet on a distribution board. The distro has 6 x 16 amp single phase outputs and 6 x 32 amp single phase outputs?

Depending on the distro... you need to limit the output per phase. You can use 2 16amp and 1 32 amp per phase.Yes, IF the generator has overcurrent protection and each circuit on your distro is individually protected as well (most are). You will not be able to load the distro to it's full capacity of 125 amps (obviously), you will be limited by the genny's rated output.As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.If you do this work yourself, always turn off the powerat the breaker box/fuse panel BEFORE you attempt to do any work ANDalways use an electrician's test meter having metal-tipped probes(not a simple proximity voltage indicator)to insure the circuit is, in fact, de-energized.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.


What is the standard entrance phase and amp to a house?

In the U.S. single phase at 200 amps is average.


How many 50 amp single phase breakers can you install on 1 phase of a three phase 200 amp panel?

simply four but also aplying diversity they may be increased depending on situation


What is a 100 amp 208 single phase?

That is 20.8 kVa but a 208 v single phase supply is very rare. 208 v is usually three-phase, with 120v between neutral and the live wires.


How many ampers does a five horsepower draw at 220 volt single phase?

16.81 amp.


How much single phase meter can bear load?

Answer for UK, Europe and countries running a 50 Hz supply service.Common single phase meters for a 240 v system can take a 60 amp or sometimes a 100 amp load for domestic use.


Can you run a 40 amp 10KW oven from a 32 amp 12 KW transformer?

No; drawing more than the rated amperage from a transformer will cause it to overheat.


What wire size for 100 amp single phase 3 wire commercial service?

2 copper


How to convert 166 amp three phase to single value?

You can't. Currents in three-phase systems are measured in each of the individual line conductors.


Does a 3 phase step up transformer placed before a rotary phase converter reduce the single phase amp draw?

No, your amp draw will not be reduced. It will actually be slightly higher because the transformer will not be 100% efficient. Contact TEMCo Phase Converters at (800) 613-2290 if you have any more questions.


Can you run 500mcm to feed 480 volt 400 amp service?

500 mcm (or 500kcmil) conductors are used for 400 amp 480v single phase or 3 phase systems. The wire AND THE TERMINALS must be rated for 90o Celsius.


What size wire do you need for 100 amp feeder single phase running 350' away?

To answer this question a voltage must be given.