In a direct-expansion (DX) system, symptoms of a flooded evaporator would include reduced cooling efficiency, as the refrigerant cannot absorb heat effectively. You might notice increased suction line pressure, ice formation on the evaporator coils, and potentially liquid refrigerant returning to the compressor, which can lead to compressor damage. Additionally, the system may exhibit short cycling or fluctuating temperatures in the conditioned space.
Evaporator is said to be flooded type if liquid refrigerant covers the entire heat transfer surface. This type of evaporator uses a float type of expansion valve. An evaporator is called dry type when a portion of the evaporator is used for superheating the refrigerant vapour after its evaporation.
Refrigerant enters a direct expansion evaporator as a saturated liquid vapor mix and leaves as a superheated vapor.
flooded type cooler is a cooler that is being flooded while direct expansion type is a type that is being directly expanded.
The expected temperature drop through a direct expansion evaporator coil is typically around 15 to 20 degrees Fahrenheit. This drop in temperature occurs as the refrigerant evaporates and absorbs heat from the air passing over the coil. It is important for efficient cooling and dehumidification in an HVAC system.
A direct expansion unit refers to a type of HVAC system where the refrigerant in the system flows directly between the evaporator and the condenser coil, without the need for a separate chiller or cooling tower. This system is commonly used in residential and commercial air conditioning units for cooling spaces efficiently.
direct expansion system
In a direct-expansion (DX) unitary system, the evaporator is in direct contact with the air stream, so the cooling coil of the airside loop is also the evaporator of the refrigeration loop. The term "direct" refers to the position of the evaporator with respect to the airside loop. The term "expansion" refers to the method used to introduce the refrigerant into the cooling coil. The liquid refrigerant passes through an expansion device (usually a valve) just before entering the cooling coil (the evaporator). This expansion device reduces the pressure and temperature of the refrigerant to the point where it is colder than the air passing through the coil. The components of the DX unitary system refrigeration loop (evaporator, compressor, condenser, expansion device and even some unit controls) may be packaged together, which provides for factory assembly and testing of all components, including the electrical wiring, the refrigerant piping, and the controls. This is called a Packaged DX system. Alternatively, the components of the refrigeration loop may be split apart, allowing for increased flexibility in the system design. This is called a Split DX system. Separating the elements has the advantage of providing the system design engineer with complete flexibility to match components in order to achieve the desired performance. One of the most common reasons for selecting a DX system, especially a packaged DX system, is that, in a smaller building, it frequently has a lower installed cost than a chilled-water system because it requires less field labor and has fewer materials to install. Packaged DX systems that use air-cooled condensers can be located on the roof of a building, in a small equipment room, or even within the perimeter wall of the building. Additionally, if the tenants are paying the utility bills, multiple packaged DX units may make it easier to track energy use, as only the specific unit serving that tenant would be used to meet the individual cooling or heating requirements.
It will, in basically all cases be a mixture of liquid and vapor, which means the refrigerant is saturated but with a few bubbles entering the evaporator. In a properly operating system though entering the metering device should be solid liquid and some sub-cooling (sub-cooled means cooler then saturation and therefore= no vapor) but then through the metering device (TXV, cap tube, orifice) some of the liquid will boil off, which is called flash gas, in order to cool the refrigerant down as saturated temperature goes down (the pressure to boiling point relation, as pressure is reduced boiling point is lowed). The amount of flash gas is directly related to the specific heat of the refigernt (BTUs/lb), the number of degrees you are cooling the refrigerant (eg. 95 to 45), and the latent heat of vaporization (BTUs/lb for change of state. liquid to vapor)
Temperature is not a pressure or force acting on a TXV (Thermostatic Expansion Valve) diaphragm. The TXV diaphragm is primarily influenced by refrigerant pressure and spring force to regulate the flow of refrigerant into the evaporator coil. Temperature affects the superheat setting of a TXV but is not a direct force acting on the diaphragm.