answersLogoWhite

0

The kVA rating will be listed on the transformer's nameplate, which is usually on the front of the transformer. The 480v to 120v is irrelevant, because many Transformers with different kVA ratings convert 480 volts to 120 volts. The kVA ratings can be different and thus affect the rated current through the transformer.

User Avatar

Wiki User

16y ago

What else can I help you with?

Related Questions

What happens when input voltage is fed to the secondary winding of a transformer?

The transformer operates in reverse. In other words, a step-down transformer becomes step-up, and vice-versa. Example: a transformer with a 480 volt primary and 120 volt secondary: Ratio = 4:1 (480/120=4) Fed in reverse - Ratio = 1:4 Apply 120 volts, output is 480. Note that if you accidentally reverse the transformer, still feeding it with 480 volts, the output would be 1920 volts (480 X 4 = 1920) - probably not a good thing!


What would the input current be for a 275 kva transformer with 2 phase of a 480 vac in and 120 vac at 20 amp output?

qsq


How many amp in 480 vac 3- phase primary transformer if the secondary it's 120 vac?

This 480-v three-phase transformer probably has a 208-v three-phase secondary which has 120 v from each line to neutral. In that case the primary current is 0.433 times as much as the secondary current, so 100 amps in the secondary means 43.3 amps in the primary.


What is the resistance of a 120 volt lamp draws 0.25 amperes of current?

v/i=r so 120/0.25=480 480 ohms is the resistance


How do you wire a 277 to 120 volt transformer?

The voltage 277 volts is a three phase line to neutral voltage of a 480 volt system. What is needed for the protection of the transformer is a two pole breaker from the 480 volt CDP (Central Distribution Panel). The breaker will be sized to the KVA of the transformer. The wire will be sized to the breaker plus 25%. The electrical code requires that on motor and transformer feeders, they be sized to 125% of the total current capacity of the equipment.


Whats the transfomer rating for a 2KVA voltage regulator with an input voltage of 100V-260V and a constant output voltage of 220V?

480 V INPUT / 120 OUTPUT 480 V INPUT / 120 OUTPUT 2KV/AMPERE MEANS 2KVA 2000/220=9.0909 AMPS SO 229X9.0.909=2000 WATS OR 2KW


What is 480 percent of 25?

25% of 480= 25% * 480= 0.25 * 480= 120


What is the output current of a 480 Volt primary 208 volt secondary - 3 phase transformer?

You need to mention the Load connected to find the current.


What is 0.25 of 480?

0.25 of 480 is 120. 480 multiplied by 0.25 (1/4) is 120 or 480 divided by 4.


What is the LCM of 32 and 120?

The LCM is 480.


What is 25 of 120?

120/25 x 100 = 480 Therefore, 120 is 480 percent of 25.


Do the induced voltage increase in a transformer when the magnetic field strength increase?

Yes, the more voltage you put in the more you get out. If the transformer is a 2 - 1 ratio and you put 240 in you get 120 out and when you put 480 in you get 240 out. Magnetic field strength and voltage have a direct relationship. +++ The field strength is actually a function of current, although as you say, increasing the voltage will increase the current hence the magnetic field.