Best Answer

2.5 mm twin and earth should do the trick.

A 100 kw @ 400 V, 50 Hz,3 Phase at a power factor approximately 0.8 will draw a current ( 100x1000/root 3x400x0.8 )=180.42 A. Breaker rating to be 200A TP MCCB and cable size to be minimum 4 Core 120 mm2 .

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Cable size for 100kw 3phase with 175meter length?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What size cable and breaker would be required for a 3phase 6.2kw 50hz fan 11Amps with a 20metre cable run?

4sqmm


What is the cable size for 1.5KW 3 phase induction motor?

Sir, what is the cable size for 1.5kw 3phase induction motor 400v?


What size of wire use for 3kw motor 380volts 3phase?

How to calculate a cable size of 3kw motor


Apair of cable each 880m long has tto supply 100kw at 440volts to sub station calculate the cross sectional area of the cable so that the energy dissipated in them shall not exceed 5kwtake reistivity?

8.2mm


How you calculate voltage drops in a cable knowing resistance or impedance and line current in a 3phase system?

Ohm's Law - V = IR.


What size cable should be used for a 3phase 10kw Air Heater?

To answer this question the voltage of the unit must be given.


You can select the cable length in the option box.?

You can select the cable length in the option box.


What is a cable length?

A cable length is a unit of measurement equal to one tenth of a nautical mile.


Is the cable length printed on the cable?

Yes, Cable length is always printed on the cable wire. As I have recently checked cables of peterstechnology.com cable length was printed with ISI certification mark & it's company logo. So anyone can easily recognize the medical cable. Thank you


What is the string and cable length on a jennings ck3.1r?

Bear says bow string length is 86.125in & buss cable length 31in


Coaxial cable is 500 meter it has a velocity factor 0.6 how long of the cable length does it take energy to travel the full length of the cable?

14


What will be cable rating for 5kva 3phase system?

It depends on the voltage: 208 v 14 amps, 415 v 7 amps, 480 v 6 amps.