kva means 1000 x voltage x current
So in order to determine the current we need to know the voltage.
AnswerA kilovolt ampere (kV.A, not kva) is a measure of a circuit's apparent power, whereas the ampere(not amp) is a measure of current. These are two completely separate quantities, so your question is quite meaningless. You might have well have asked, "How metres are there in a kilogram of sugar?"
The formula is for single phase I x E/1000, for three phase I x E x 1.73/1000. Need to know the voltage to answer this question.
Amp. X 1.4 = KVA
Convert 160 kva to full load amp
I=Kva*1000/v*1.732 =500*1000/415*1.732 =500,000/718.78 =695.62 Amps. So max.load of 500kva DG is 695.62 Amps
All transformers, single phase or three phase have a "no-load current" rating. That is simply the nameplate rating of the Xformer in VA, (volt-amps) or KVA (1000Volt-amps) for larger Xformers. Simply divide the nameplate rating in VA or KVA by the supply voltage and you'll get the Xformers potential maximum output in ampheres.
The equation for amperage when the kilowatts are known is Amps = kVA x 1000/1.73 x Volts.The electrical code states that a feeder for a transformer has to be rated at 125% for the primary and secondary load amperages.The amperage on the primary needed to supply a 70 KVA three phase transformer to its full capacity at 600 will be 68 amps. 68 x 125% = 85 amps. A #4 copper conductor with an insulation factor of 90 degrees C is rated at 95 amps.The amperage on the secondary needed to supply a 70 KVA three phase transformer to its full capacity at 480 will be 84 amps. 84 x 125% = 105 amps. A # 3 copper conductor with an insulation factor of 90 degrees C is rated at 115 amps.
KVA = Root 3 VII = KVA *1000 / 1.73 * 415I = 500000 / 717I = 697 ApproxAnswerIt depends on the rated voltage of the generator.
500 KVA how many amps? almost 650 Amps according to formula.
Full load amps for a three phase, 375KVA generator is 375 / (voltage in kV) / sqrt(3).
You need to convert KVA to KW. In order to do this correctly you need to know your power factor.,
To answer this question a current value needs to be given. 125000 is the product of amps times volts. I = W/E = 521 amps. So to bring 240 volts up to 125 KVA you need the circuit load to draw 521 amps.
three phase full load 1000/(1.732*220)*24 = 62.98amps
Amperes when kva is shown. The formula is, Amps = kva x 1000/1.73 x volts.
To convert amps to kVA, you use the following formula: Amps = (kVA x 1000 / voltage) / 1.73
Multiply by Amps.
I=Kva*1000/v*1.732 =500*1000/415*1.732 =500,000/718.78 =695.62 Amps. So max.load of 500kva DG is 695.62 Amps
All transformers, single phase or three phase have a "no-load current" rating. That is simply the nameplate rating of the Xformer in VA, (volt-amps) or KVA (1000Volt-amps) for larger Xformers. Simply divide the nameplate rating in VA or KVA by the supply voltage and you'll get the Xformers potential maximum output in ampheres.
A rough guide is to divide kVA by the supply voltage then multiply by 1000 to get current in Amps. E.g. 20kVA divided by 120V is 0.167; times 1000 is 167 Amps. But kVA is not the same as kW, so more information is needed before equipment is used.
35 kV.A.
It depends on the rated voltage. Take 1600 KVA and divide by KV, and you will get A.