Best Answer

There are two sections of the fuse; a straight wire section that provides quick acting response to short circuit conditions, and a coiled spring section with a soldered lump with thermal mass that provides time delay for normal overload. When inspecting a blown fuse, you can tell if it was a short or an overload by looking at where the blowout occurred.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How a fuse can provide time delayed protection for normal overload and high speed protection for short circuit?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Electrical Engineering

How is thermal overload protection done in stator windings of motor?

one way is to use RTD sensor put inside the motor windings. The RTD sensor is connected to an electronic thermal overload relay. This type of relay can provide running temperature of the motor, on the electronic thermal over load relay display panel. RTD sensor is a wire wound resistor that changes resistance depending on the temperature


What does a voltage source provide a circuit with?

powerAnswerVoltage.


What does not provide a voltage difference in a circuit?

Wires do not provide a voltage differenceAnswerAs 'voltage' is synonymous with 'potential difference', you appear to be asking "What does not provide a potential difference difference in a circuit?", which does not make any sense!


What is MCC in electrical engineering?

MOTOR CONTROL CENTER. A motor control center consists of one or more vertical metal cabinet sections with power bus and provision for plug-in mounting of individual motor controllers. Very large controllers may be bolted in place but smaller controllers can be unplugged from the cabinet for testing or maintenance. Each motor controller contains a contactor or a solid-state motor controller, overload relays to protect the motor, fuses or a circuit breaker to provide short-circuit protection, and a disconnecting switch to isolate the motor circuit. Three-phase power enters each controller through separable connectors. The motor is wired to terminals in the controller. Motor control centers provide wire ways for field control and power cables. Each motor controller in an MCC can be specified with a range of options such as separate control transformers, pilot lamps, control switches, extra control terminal blocks, various types of bi-metal and solid-state overload protection relays, or various classes of power fuses or types of circuit breakers. A motor control center can either be supplied ready for the customer to connect all field wiring, or can be an engineered assembly with internal control and interlocking wiring to a central control terminal panel board or programmable controller.


Can you suggest more efficient led driver circuit?

We probably can. You would need to provide the original circuit first, though. :D

Related questions

Does surge strips provide a built-in 15amp circuit breaker?

If the circuit breaker is in the off position there is no need of overload protection. Overload protection monitors the load amperage, If there is no amperage through the circuit there is nothing to monitor.


What fuses and circuit breakers provide protection in the event of?

Short circuit fault.


What do car fuses do?

A device designed to provide protection for a given circuit or device by physically opening the circuit. Fuses are rated by their amperage and are designed to blow or open when the current being drawn through it exceeds its design rating. They are designed to protect the electrical circuits in your car from a short circuit or overload.


The chief purpose of a service panel in a house is to?

To provide automatic circuit protection.


What can fuses not provide protection against?

Fuses do not provide protection against ground faults. Protection against a ground fault can be provided by breakers. If a fuse blows, it has to be replaced. If a breaker is tripped to off due to a surge in electrical current, the breaker can be reset.


What is acdb?

ACDB stands for alternating current distribution board. A distribution board or panel is part of an electricity supply system. The panel splits the power up into circuits. At the same time, it uses fuses or circuit breakers to provide protection from electrical overload.


What are the objectives in short circuit study?

To provide the data necessary to design protection systems.


What is a reusable circuit protector a circuit breaker - a fuse - a 10 gauge copper wire or a three prong outlet?

A circuit breaker is the only reusable circuit protector in that list. A fuse is also circuit protection, but it is not reusable. A length of wire can work like a fuse in some applications, such as feeding transformers on poles, but the wire would have to be small enough of a gauge to be able to burn out when overloaded. However, the wire would need replaced after an overload. A three prong outlet is for protecting humans, not circuits. The ground wire is for providing a low impedance fault current path back to the breaker to trip the faulted circuit's breaker (or fuse). The opening of the circuit will prevent a possible fire. However, a three prong outlet doesn't actually provide the protection of tripping the circuit.


What is ACDB panel?

ACDB stands for alternating current distribution board. A distribution board or panel is part of an electricity supply system. The panel splits the power up into circuits. At the same time, it uses fuses or circuit breakers to provide protection from electrical overload.


What is the name of the device that protects a circuit from current overload?

It is called fuse or circuit breaker.In electronics and electrical engineering, a fuse is a type of low resistance resistor that acts as a sacrificial device to provide over-current protection, of either the load or source circuit. Its essential component is a metal wire or strip that melts when too much current flows through it, interrupting the circuit that it connects. Fuses are an alternative to circuit breakers.A circuit breaker is an automatically operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit. Its basic function is to detect a fault condition and interrupt current flow.Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation.


How do you troubleshoot a thermal overload relay?

Ideally an overload relay should be set above maximum load by some small amount, but below the capability of the electrical circuits being protected. For example, breakers in your home are designed for overload protection; typical home wiring is 14 awg - 12 awg. If you have a 14 awg wire (good for 15A), you may install a 10A breaker, but if needed could install a 15A breaker depending on codes. A 20A breaker would not provide overload protection since it is too big. It would provide fault protection.


You have an equipment rated for 230V 14 FLA and you have it connected to a 20A circuit breaker. you just noticed that is now connected to a 30A circuit breaker. how would this affect your equipment?

If the motor starts without tripping the breaker and when the motor picks up the load and the breaker doesn't trip, just leave it. Code states that motors should be protected by 2.5 times the FLA to allow for start up inrush current which can go as high as 300%. In this case 14 x 2.5 = 35 amps. There not being a breaker of that size go to the next highest, that being a 40 amp breaker. The motor should have additional overload protection on the circuit set to the FLA of the motor and not depend on the breaker to provide overload protection.