answersLogoWhite

0

A ground fault happens when (usually mains) electricity is conducted outside it's intended path and tries to get to ground by the shortest path. If you touch something 'hot' electrically while you are grounded, or are also touching something that is grounded, you will become that shortest path to ground and will be shocked and possible killed.

A ground fault can occur in normal mains wiring. For example, if a conductor is not properly insulated and it touches another conductor or the conduit it runs through it can can 'short circuit' to ground causing a ground fault.

A ground fault can also occur in a defective or miswired electrical receptacle or appliance.

To find the fault you have to be familiar with wiring for the structure in question, and have to trace the wiring through it's circuit, possibly to the mains connection to the structure.

For example, if you know that certain problem plug receptacles in a particular house are on their own circuit, you can open them and may be able to visually check for shorts and that the wires are connected properly.

User Avatar

Wiki User

12y ago

What else can I help you with?

Continue Learning about Electrical Engineering

What do ground fault relays do?

Ground fault relays sense ground faults in the circuit and trigger a circuit breaker to trip off


What are the types of faults in ehv transmission lines?

The three types are Line to ground faults line to line fault double line to ground fault three phase line to ground fault


The device used to de-energize circuits automatically when a very small ground-fault current flow is the?

Ground fault interupter.


What does the letters GFCI stand for?

Ground-fault circuit interrupter.


What are the types of grounding?

1. Ungrounded. Electrical power systems that are operated with no intentional connection to earth ground are described as ungrounded. Although these systems were standard in the '40s and '50s, they're still in use today. The main advantage of this type of grounding system is that it offers a low value of current flow and reliability during a fault. Unfortunately, this type of system also offers some big disadvantages. One major disadvantage to an ungrounded system is in the difficulty in locating a line-to-ground fault. Finding the fault is a time consuming process. For that reason, it's often done on the weekends so a company doesn't have to shut down its normal production processes. In addition, the fault must be located and repaired quickly because if a second fault occurs, the fault acts like a phase-to-phase fault extending the repair process. Advantages * Offers a low value of current flow for line-to-line ground fault (5A or less). * Presents no flash hazard to personnel for accidental line-to-ground fault. * Assures continued operation of processes on the first occurrence of a line-to-ground fault. * Low probability of line-to-ground arcing fault escalating to phase-to-phase or 3-phase fault. Disadvantages * Difficult to locate line-to-ground fault. * Doesn't control transient overvoltages. * Cost of system maintenance is higher due to labor involved in locating ground faults. * A second ground fault on another phase will result in a phase-to-phase short circuit. 2. Solidly grounded. This type of grounding system is most commonly used in industrial and commercial power systems, where grounding conductors are connected to earth ground with no intentional added impedance in the circuit. A main secondary circuit breaker is a vital component required in this system, although it has no bearing in other grounding systems. This component is large in size because it has to carry the full load current of the transformer. Back-up generators are frequently used in this type of grounding system in case a fault shuts down a production process. When this happens, the generators become solidly grounded. However, it's important to note that the generators aren't designed for the larger short circuit current associated with solidly grounded systems. A solidly grounded system has high values of current ranging between 10kA and 20kA. This current flows through grounding wires, building steel, conduit, and water pipes, which can cause major damage to equipment and shut down production processes. When a line-to-ground fault occurs, arcing can create flashes-generally in the terminating box. In this enclosed area, water is turned to steam, causing the terminating box. To locate the fault, all you need to do is follow the smoke. Advantages * Good control of transient overvoltage from neutral to ground. * Allows user to easily locate faults. * Can supply line-neutral loads. Disadvantages * Poses severe arc flash hazards. * Requires the purchase and installation of an expensive main breaker. * Unplanned interruption of production process. * Potential for severe equipment damage during a fault. * High values of fault current. * Likely escalation of single-phase fault to 3-phase fault. * Creates problems on the primary system. 3. High-resistance grounding. High-resistance grounding (HRG) systems are commonly used in plants and mills where continued operation of processes is paramount in the event of a fault. High-resistance grounding is normally accomplished by connecting the high side of a single-phase distribution transformer between the system neutral and ground, and connecting a resistor across the low-voltage secondary to provide the desired lower value of high side ground current. With an HRG system, service is maintained even during a ground fault condition. If a fault does occur, alarm indications and lights help the user quickly locate and correct the problem or allow for an orderly shutdown of the process. An HRG system limits ground fault current to between 1A and 10A. Advantages * Limits the ground fault current to a low level. * Reduces electric shock hazards. * Controls transient overvoltages. * Reduces the mechanical stresses in circuits and equipment. * Maintains continuity of service. * Reduces the line voltage drop caused by the occurrence and clearing of a ground fault. Disadvantages * High frequencies can appear as nuisance alarms. * Ground fault may be left on system for an extended period of time. Grounding of an electrical system is a decision many of us face on a daily basis. As we've seen, several methods exist to accomplish this task, each offering its own advantages and disadvantages. As an electrical designer or installation professional its up to you to make the final decision as to when best to install the most appropriate system. Azad M Patel Electrical Engineer

Related Questions

How do earthquakes happen-?

Earthquakes happen when under the ground rocks break at a fault. The rocks then break it release of energy which causes semi waves.


When rock layers break the resulting surface they break and slide on is a?

A Fault


What is the break in layers of rock?

Fault


How do you wire a ground fault switch?

To replace the wire ground fault switch, you need to switch off electric power from the source. After switching it off you can use the screwdriver to open screw and remove the faulty switch and replace it with a good one. <<>> There is no such a device as a ground fault switch. There is a ground fault breaker and a ground fault receptacle.


What is the difference between a ground fault and an arc fault?

A ground fault occurs when an electrical current flows to the ground due to a fault in the wiring or equipment. An arc fault, on the other hand, is a high-energy discharge of electricity between conductors, which can cause fires.


What do ground fault relays do?

Ground fault relays sense ground faults in the circuit and trigger a circuit breaker to trip off


What is a break in earth's crust?

A fault


What are the types of faults in ehv transmission lines?

The three types are Line to ground faults line to line fault double line to ground fault three phase line to ground fault


What part of speech is locate?

Locate is a verb. For example: Engineers worked to locate the fault responsible for the earthquake. Locatable, a derivative of locate, is an adjective. Location is a noun.


What is the difference between an arc fault and a ground fault?

An arc fault occurs when there is an unintended electrical discharge between two conductors, while a ground fault happens when an electrical current flows to the ground instead of following its intended path.


A break in the crust along which rock moves?

This is called a fault.== ==


What is a break in the crust called?

A break in the earth's crust is called a fault line.