answersLogoWhite

0

In order to draw the phase diagram for transformer operating at load with lagging PF and leading PF, you will need to know the equation for the transformer being load free. This constant will help you with the load bearing equation of Np/Ns=Vp/Vs=Is/Ip.

User Avatar

Wiki User

11y ago

What else can I help you with?

Continue Learning about Electrical Engineering

What happens when lagging Power Factor changes to leading PF?

when lagging Power Factor changes to leading PF, then the voltage across the circuit in which capacitor bank is connected, is increased.


Power factor lead or lag?

By definition, the terms 'leading' and 'lagging' refer to what the load current is doing with respect to the supply voltage. So, for a 'lagging power factor', it is the current that is lagging.


What is meant by lagging and leading circuit?

The terms, 'lagging' and 'leading', describe the relationship between a circuit's load current and supply voltage. They describe whether the load current waveform is leading or lagging the supply voltage -always the current, never the voltage. Inductive loads always cause the current to lag the supply voltage, whereas capacitive loads always cause the current to lead the supply voltage.


Current calculation when parallel operating generators?

Yes and no. One generator may be operating in the leading VAR region, and the other may be operating in the lagging VAR region. This would result in reactive current effectively circulating between the two generators.If you are talking about active (real) power, this should not happen, and will cause protective equipment to trip. Generators should generate real power, not consume it.


What is the vector diagram of ynd11 transformer?

In the vector group representation for this transformer, the letter 'y' represents a wye- or star-connection, and the letter 'd' represents a delta- or mesh-connection (I have no idea what 'n' stands for -anyone?). An upper-case letter indicates the higher voltage, while a lower-case letter represents the lower voltage. The sequence of the letters indicates the primary and the secondary windings. So the transformer in question is a wye-delta connection (presumably the 'y' should have been capitalised, meaning that this is a step-down transformer: i.e. Yd11).The number appearing after the letter group (in this case '11') is a multiplier of 30o and indicates the transformer connection's angular displacement (or phase displacement). In this case, the angular displacement is 11 x 30o = 330o.As angular displacement is defined as 'the angle by which the secondary line voltages lag the primary line voltages', this means the secondary line voltages of this particular transformer lags its corresponding primary line voltages by 330o.So, to draw the phasor (not 'vector') diagram for this particular transformer, you would start by drawing the phase voltages (VAN, VBN, and VCN) of the primary wye connection (using VAN as the phasor of reference), from which you would then construct the corresponding line voltages (VAB, VBC, and VCA). To finish the diagram, you will then draw the secondary delta phasor diagram, starting with Vab lagging VAB by 330o (or, if you prefer, leading by 30o), then drawing Vbc and Vca displaced by 120o.

Related Questions

Leading and lagging power factor?

The terms, 'leading' and 'lagging' refer to what the load current is doing, relative to the supply voltage (Phase difference) -never the other way around. If the current is leading the voltage, then the power factor is 'leading'; if the current is lagging the voltage, then the power factor is 'lagging'.


Where does ssb protein bind on lagging strand or on leading strand?

ssb protein bind to the lagging strand as leading strand is invovled in dna replication and lagging strand is invovled in okazaki fragment formation


When synchronus generator is supplying active and reactive power it is operating at leading or lagging power factor?

A synchronous generator is operating at lagging power factor (positive P & Q) when it is supplying P & Q to the system. P & Q are positive which means that they are flowing away from the bus where the generator is connected (overexcited case). On the other hand, it is operating at leading power factor when it is supplying P and absorbing Q. The sign of Q is negative which means that it is flowing towards the generator bus (underexcited case).


There is a y shaped replication fork on each side of each replication bubble what are the sides of the replication fork called?

One is known as the Leading strand, and the other is known as the Lagging strand.


What happens when lagging Power Factor changes to leading PF?

when lagging Power Factor changes to leading PF, then the voltage across the circuit in which capacitor bank is connected, is increased.


Would you compare generator current to line voltage to determine if your leading or lagging?

It's always the current that determines 'leading' or 'lagging' -i.e. the angle by which the current leads or lags the voltage.


What is the Reactive power in a capacitive modeand inducitive mode?

Generators can be required to generate real and reactive power. When operating in a leading mode, the generator is generating real and leading reactive power (inductive power). This means the generator is "sucking in VARS", which will pull down the terminal voltage similar to an inductor. It can also be operated in a lagging mode, which means it is generating real and lagging reactive power (capacitive power). The generator, then, is "pushing out VARS" like a capacitor, which will cause the terminal voltage to increase. Generators can only create so many leading and lagging VARs; in general lagging VARs are limited by the automatic voltage regulator output capabilities; leading vars are limitted by how much heat the stator can dissipate.


What is the affect of ambient temperature on the transfomer efficiency?

Ambient temperature affects transformer efficiency by influencing the cooling of the transformer. Higher ambient temperatures can reduce the transformer's ability to dissipate heat, leading to decreased efficiency. It is important to consider ambient temperature when designing and operating transformers to ensure optimal performance.


How do you mesure leading and lagging factor?

Leading and lagging factors can be measured by comparing their impact on a specific outcome or goal over time. Leading factors are variables that change before the outcome, while lagging factors change after the outcome. By analyzing the correlation between these factors and the outcome, you can determine their level of influence and measure their effect on the desired outcome.


Which strand (leading or lagging) will have the okazaki fragments?

The lagging strand will have the Okazaki fragments. These short fragments are created as the DNA replication machinery synthesizes the new DNA strand discontinuously in the 5'-3' direction away from the replication fork.


Why Power factor becomes less lagging when capacitor is switched on?

Because capacitor withdraw leading current from source and net resultant become less lagging.


Power factor lead or lag?

By definition, the terms 'leading' and 'lagging' refer to what the load current is doing with respect to the supply voltage. So, for a 'lagging power factor', it is the current that is lagging.