answersLogoWhite

0

T430.247 of the NEC shows that a 1 hp motor operating at full load on 115v will draw 16 amps, called Full Load Current (FLC). Conductors supplying this motor are required to be 125% of FLC which is 20 amps.

Motor circuits are complicated things and do not follow the rules of other circuits. This motor, while drawing a maximum of 16 amps at full load and supplied with #12 AWG copper conductors can be protected by a breaker of 40 amps.

User Avatar

Wiki User

12y ago

What else can I help you with?

Continue Learning about Electrical Engineering

What is the full load amps for 2.4 hp motor at 460 volts?

what is the full load amps for 2.4 hp motor at 460 volts ?


What size motor start capacitor is required for a 0.6 hp electric motor?

As an electrician I can give you a vague answer with the information given. You need more specifics to do the calculations for the load amps and the supply voltage.The particular motor I looked at is a .6hp fan motor -4.0 Amps @ 230V(2650 x Full load amps ) divided by supply Voltage = MFDExample 2650 x 4amps = 10600 divided by 230volts = 46 MFDBut this is a general statement. The proper cap should be determined by researching the particular model you have.


What would full load amps be on a 480volt 3 phase 90 kw electric heater be pulling 36 amps per leg?

46 amps


What is the full load 1250 HP 4160 V motor?

129 amps


What is locked rotor current?

"Locked Rotor Current" also called LRA which stands for Locked Rotor Amps, is commonly found on electric motor nameplates. Locked Rotor essentially means the motor is not turning. The current or amps in this case have to do with the amount of electrical energy required to start the motor. At the instant the motor is switched on, it is not turning, and draws the maximum current. As the motor starts to turn, the current goes down. This required energy is much greater than the Full Load Amps or Running Amps, which is the current drawn when the motor is running at normal speed under full load. The current required to start the motor will depend on the type of motor as well as the specified design voltage required for the motor, typically the higher the voltage, the lower the required amperage or current. The term also applies to equipment such as Air Conditioners which have an enclosed motor inside the compressor, as well as the condenser fan(s) etc. Depending on the type of motor, LR current can be anywhere from 3 to 8 times the normal running current, also called RLA, or running load amps.

Related Questions

What is the difference between full load amps and running load amps?

Full load amps is the maximum rated amps that the motor should draw according to its nameplate rating. Running load amps is the actual amperage the motor is drawing at that point in time when the test is taken. Some motor loads vary depending on if the load is cyclic. The reading on this type of motor would be from no load amps to full load amps.


What is the difference between Full load Amps and Service Factor Amps on an electric motor?

Full load amps is the amperage at which the motor was designed to work at to achieve its rated horsepower. Service factor amps is the amount of a periodic overload at which a motor can operate without overload or damage. Continuous operation within the service factor amps will shorten the insulation and motor bearing life of the motor as the motor will be operating at a higher temperature than it was designed to.


What circuit breaker rating do you need for a 3 phase electric motor?

The circuit breaker is sized to the full load amps of the motor times 250%.


What is the full load amps for 2.4 hp motor at 460 volts?

what is the full load amps for 2.4 hp motor at 460 volts ?


Why is my single phase induction motor drawing to many amps?

I have a single phase induction motor. It draws 8 amps on start up and climbs to 14-15 amps when I put a load on it. When I don't have a load it runs at 1 and climbs to 2-3 amps. It is normal operation for this motor to run at the lower number of amps with a load. But I don't know what is wrong.


What is FLA in electrical terms?

FLA = full load amps <<>> It is a term that is associated with motors. It is the amperage of the motor when it operates at its full rated horsepower under load.


What is Full Load Amps?

FLA is the nameplate amperage rating of the motor when it is running at its designed horsepower and on the motors designed voltage. 746 watts = 1 HP. The FLA of a 1 HP motor at 240 volts would be W = amps x volts, Amps = Watts/Voltage. 746/240 = 3.1 amps full load. Overload the motor and the amps go higher, motor running at no load amps are lower than FLA


When servicing a 2 hp motor your amp reading is 3.10 amps what voltage is the motor operating under?

It depends on whether the motor is run on load or whether it's running light.


What will be the starting current of a 335hp Sqcage motor on no load?

Across the line starting of a motor can be as high as 300% of the full load amps.


What does Florida stand for on a motor name plate?

Full-Load Amps


Is it good to run the motor at fill load amps consistently?

yes


What size of circuit breaker do you use for 25amperes induction motor?

Read the specification plate on the motor to determine the amount of current that the motor uses, as well as the voltage and phase. Most likely, it will be a 3 phase motor, so you can't simply connect it to your house wiring, but without sufficient information, it is impossible to tell you all of the specifics. <<>> The code book rates the amperage of a three phase 40 HP motor by different voltages. at 200 volts - 120 amps, 230 volts - 104 amps, 460 volts - 52 amps and 575 volts - 52 amps. A breaker for a motor has to be sized to 250% of the motors full load amps. Also the wire size for a motor has to be 125% of the motor full load amps.