Sure. No transformer is built to last forever. Aging and operations will weaken the insulation with time.
potential transformer is to maser and protection purpose the ivt is used for synchronicing purpose
A power transformer is used to provide power (to your home, for example), an instrument transformer is used to measure voltage or current (for metering, for example).
Control transformer used only for control supply 110,220, 24,12V AC. But Potential transformer used voltage measurement purpose.
Actually it depends on the air gap between the core and the windings of the transformer. This is the reason why stepped core is used in medium and large transformers as it decreases the air gap between the windings and the core of the transformer.
in isolation transformer earthing is not provide on secondary side but in ordinary transformer neutral of secondary side is earthedAnswerAn isolation transformer is a 1:1 ratio transformer; its function is to electrically isolate the secondary side from the primary side without changing the voltage. An example of an isolation transformer is the one used in a shaver socket.A distribution transformer is a step-down transformer, used within the electricity network's distribution system. An example of distribution transformer is a pole-mounted transformer, supplying low voltage to residences.(Of course, all mutual transformers provide electrical isolation between primary and secondary.)
an annex is where people live and enclosure is where things are kept e.g monkeys are kept in a monkey enclosure.
there is nothing like a balanced and unbalanced transformer.
Tha majority of Enclosure Acts were passed between 1750 and 1860.
Yes the enclosure acts applied to Scotland and the entire United Kingdom. The enclosure acts occurred between 1604 and 1914.
An isolation transformer is usually a ferromagnetic transformer. The question needs to be framed more usefully.
blocking refers to when an input terminal cannot be connected to an output terminal because there is no path available between them i.e. all possible intermediate switches are occupied
They are marked on the transformer. H1 and H2 primary, X1 and X2 secondary. Dual voltage primary H1, H3 H2, H4, Dual voltage secondary X1, X3, X2, X4.Additional Answer for Unmarked TransformerFor a completely unmarked transformer, a continuity test will confirm which terminals belong to which windings, and a resistance test will identify the high-voltage (higher resistance) and low-voltage (lower resistance) windings. In North America, HV winding terminals are identified by the letter 'H' and LV windings by the letter 'X'. For a two-winding, four terminal, transformer, to test for polarity, the transformer should be orientated so that the HV windings are on the far side of the transformer, and the LV windings are on the nearest side. By convention, the left-hand HV terminal is then marked H1, and the right-hand terminal is marked H2. The LV terminal adjacent to H2 is then connected to terminal H2, so that both the HV and LV windings are in series. A voltmeter is then connected between the LV terminal adjacent to H1, and the H1 terminal itself. A low-voltage supply is then connected across the HV windings (i.e. between H1 and H2). If the voltmeter registers a voltage higher than that applied to the HV windings, then the transformer is of additive polarity, and the LV terminal adjacent to H2 should be marked X1 and the LV terminal adjacent to H1 should be marked X2. If, on the other hand, the voltmeter reading is less than the applied voltage, then the transformer is of subtractive polarity, and the LV terminal adjacent to H2 should be marked X2, and the terminal adjacent to H1 should be marked X1.By convention, when terminal H1 'goes positive' during the AC sine-wave, then terminal X1 should also 'go positive'.A similar process applies to multi-winding multi-terminal transformers. Again, the windings of such transformers must have their terminals identified first -a simple continuity test will reveal these. The rule is that an odd number (e.g. H1, etc.) represents the 'start' of a winding, and an even number (e.g. H2) represents the 'end' of a winding. Again, a simple resistance test will identify the high-voltage (higher resistance) and low-voltage (lower resistance) windings.For UK transformer, HV windings are identified as A-B, etc., and LV windings as a-b, etc.
Both are same. This is an instrument transformer used for metering & protections.
The 3 kVA transformer will weigh double the 1.5 kVA transformer.
The difference between current transformer and potential transformer is that the secondary of a current transformer can not be open circuited while under service whereas that of the potential transformer an be open circuited without any damage to the transformer.
An audio frequency transformer is a transformer designed to operate in the range of frequencies audible to the average human. This range is generally accepted to be from 20 Hz to 20,000 Hz. The usual purpose of an audio transformer is to match impedances between circuit sections. For example: between a microphone and the input of an amplifier, (input transformer), or between the output of an amplifier and the loud speaker. (output transformer).
Variable transformer may also refer as auto transformer. We can vary the output voltage of the transformer. But in the ordinary transformers output voltage is already designed.