Full load starting current is typically in the region of 5or 6 times the full load motor current;.

User Avatar

Wiki User

12y ago

What else can I help you with?

Related Questions

Why no load current is 5 percent of full load current in motor?

As the no load current is the current due to core losses of the motor which is very small .in no load terminals are open circuited no current flows through it, a small current flows which is due to core


What is the Full load motor current with a 75 KW drive?

3phese 460 volt 75 kw a/c drivi full load current


What is the ratio from no load current to full load current of an induction motor?

The ratio is between 30% to 40 %


What is Fla on motor nameplate?

FLA: Full Load Ampere. Its the current drawn by the motor when the motor is running at full load FLA = kW / (1.732*V*pf*efficiency*100)


What will be the starting current of a 335hp Sqcage motor on no load?

Across the line starting of a motor can be as high as 300% of the full load amps.


Are motor conductors sized to the locked rotor current?

According to 2011 nfpa 70 nec Motor conductors are sized with the flc- full load current or the nameplate rating fla- full load amperes


Why is motor current draw lower at full speed?

Because full speed is unloaded. As you load the motor, speed decreases, and slip increases, with an accompanying increase in current.


How is the full load current different to the starting current- is the full load current higher or lower than the starting current?

While starting a motor from standstill to its rated speed, the motor has to overcome the inertia and generate enough torque to over come it. In the process the motor takes higher current during the starting. Once started and set in motion the current reduces ti its normal value. Full load current is lower than the starting current normally.


How the dc current shunt motor change from no load to full load efficiency?

decrease in starting and running torque and speed is almost constant from no load to full load. it's because the field voltage is consant and current is varied.


What is the difference between full load amps and running load amps?

Full load amps is the maximum rated amps that the motor should draw according to its nameplate rating. Running load amps is the actual amperage the motor is drawing at that point in time when the test is taken. Some motor loads vary depending on if the load is cyclic. The reading on this type of motor would be from no load amps to full load amps.


What is Full load current for 40 HP star delta motor?

What is the continuous current of 10HP star delta motor


How do you calculate breaker capacity of 10 hp three phase induction motor?

The first thing you have to do is find the full load amps of the motor. The wire size feeding the motor has to be 125% of the full load current. The breaker is usually 250% of the full load current. If the voltage and amperage had been added to the question the exact breaker size could have been calculated.