The main insulation factors of the wiring used in every day use are 60, 75 and 90 degrees C. A #6 wire can be any of the above. The higher the insulation factor, the higher the ampacity of the wire becomes.

For a #6 wire the amperage is 60 C - 55 amps, 75 C - 65 amps and 90 degrees C - 65 amps.

User Avatar

Wiki User

12y ago

What else can I help you with?

Related Questions

What is the amp ratings of a 6 gauge wire?

A # 6 copper wire with an insulation factor of 75 or 90 degrees C is rated at 65 amps. Code states that conductors can only be continuously loaded to 80%. 65 x .8 = 52 amps.


What gauge wire is needed for 60 amp circuit?

A #6 copper wire with an insulation factor of 75 and 90 degrees C is rated at 65 amps.


How many amp is aluminum wire size 6 good for?

A #6 aluminium conductor with an insulation factor of 90 degrees C is rated for 55 amps.


What gauge wire do you need for a 12 amp?

For safety, approximately 6 or 8 mm. A #14 AWG copper wire with an insulation factor of 90 degree C will have a capacity of 15 amps.


What is the amp and voltage rating for number 6 gauge wire?

Number 6 gauge wire typically has an ampacity rating of around 55-75 amps and a voltage rating of 600 volts. These ratings may vary depending on the specific type of wire and the regulations in your area. It is important to consult the National Electrical Code (NEC) or a qualified electrician for accurate information.


How many watts can handle 18 AWG wire carry?

A#18 copper conductor with an insulation factor of 90 degrees C is rated at 6 amps.


Maximum amps 6 gage copper wire?

A #6 copper conductor with an insulation factor of 75 or 90 degrees C both have an amp rating of 65 amps. If the #6 conductor is connected to a breaker having a 90 degree C rating then the conductor can carry an amperage of 75 amps


What gauge wire for 240 v 60amp to heat pump?

A #6 copper conductor with an insulation factor of 75 and 90 degrees C is rated at 65 and 75 amps respectively.


What wire should you use for 50 amp?

For a 50 amp circuit, it is recommended to use a 6-gauge wire for copper or a 4-gauge wire for aluminum to ensure proper capacity for the current. Make sure to follow local electrical codes and regulations when selecting and installing the wire.


Can you use 8 gauge wire with a 50 amp breaker?

Yes. <<>> No. A #8 conductor with an insulation factor of 75 or 90 degrees C is only rated at 45 amps. You would need a #6 conductor with an insulation factor of 75 or 90 degrees C as it is rated at 65 amps.