Yes
kV is kilovolts, kW is kilowatts, kVA is kilovolt amps and kVAR is kilovolt-amps reactive. A common formula is kVA-squared = kW-squared + kVAR-squared.
To answer this question the voltage of the generator must be given.
Ground clearance132 kv - 6100 mm220 kv - 7015mm400 kv - 8840mm765 kv - 15000mm
KV DRDO is located in C.V.Raman Nagar, Bangalore
To calculate the current in amps for a 2 kV system with a primary voltage of 380 V and a secondary voltage of 220 V, you need to know the transformer's power rating (in watts) or the load connected. The formula to determine the current is ( I = \frac{P}{V} ), where ( P ) is the power in watts and ( V ) is the voltage in volts. For a 2 kV (2000 W) system, at 220 V, the current would be approximately ( I = \frac{2000 W}{220 V} \approx 9.09 ) amps. If you are looking for the primary current, you would use the primary voltage of 380 V instead.
Could be zero, could be 1000 amps. Amps are not the same thing as volts.
Multiply by Amps.
The number of amps in 1 MVA (megavolt-ampere) will depend on the voltage of the system. To calculate amperes, you can use the formula: Amperes = MVA / (sqrt(3) x kV), where kV is the voltage of the system in kilovolts.
Basically the formula is I = P / V where I = amps, P = power (kV) and V = volts for a single phase 11 kV genset the formula is 11000/400 = 27.5 amps max load. For a 3 PHASE GEN then 11000x0.8/400/3 = 7.3 amps per phase.
20,000 volts = 20 kv
220 KV lines used in Kerala have a capacity of 880 Amps
This depends on the voltage ... amps = watts / volts 660 W / 110 V = 6 amps 660 W / 220 V = 3 amps 660 W / 330 KV = 2 mA
Full load amps for a three phase, 375KVA generator is 375 / (voltage in kV) / sqrt(3).
kV is kilovolts, kW is kilowatts, kVA is kilovolt amps and kVAR is kilovolt-amps reactive. A common formula is kVA-squared = kW-squared + kVAR-squared.
To determine the current in amps produced by a 10 kV generator, you need to know the power output in watts. The formula to calculate amps is: Amps = Watts / Volts. For example, if the generator produces 10 kW (10,000 watts), the current would be 10,000 watts / 10,000 volts = 1 amp. Therefore, without knowing the specific power output, the amperage cannot be determined.
The Basic Insulation Level (BIL) for 3.3 kV systems typically ranges from 12 kV to 15 kV, while for 6.6 kV systems, it usually falls between 20 kV and 25 kV. BIL is a standardized measure of the insulation's ability to withstand transient overvoltages, such as lightning strikes and switching surges. These levels ensure that the equipment can endure electrical stresses without failure, thus enhancing reliability and safety in electrical systems.
There are zero watts in 3.5 kilovolts. Watts are the product of Amps x Volts. Without an amperage stated the wattage can not be given.