475 amps, per NEC 310-16. Note that this is a maximum; there are many reasons to derate the current carrying capacity of the wire.

User Avatar

Wiki User

12y ago

What else can I help you with?

Continue Learning about Engineering

What is the amperage rating of 500 MCM copper conductor?

It depends on a lot of factors. Generally speaking, if the insulation is THHN then the rating is 350 amps. If the insulation is THWN then the rating is 310 amps. The ampere rating for wire depends on the temperature of the environment it will be used in, the insulation rating and the number of circuits installed in a conduit. There are also other factors to consider... like voltage drop in long runs.


What size feeder wire for three phase 320 amp meter serving two 200 amp panels?

2/0 if copper is used; 4/0 if aluminum is used. The neutral and ground are usually smaller. 2/0 is only rated for 185 amps. 3/0 copper is rated for 210 amps, 250 MCM is rated at 215 amps if aluminum is used.


How much current does 300 sq mm cable carry?

A 228 sq mm conductor equates to 450 MCM. A conductor of 450 MCM is not a standard AWG wire size. A standard 400 MCM will carry 380 amps. A standard 500 MCM will carry 430 amps. Difference between 400 and 500 MCM amperage's is 50 amps. Transposing between the two amperage's of 50 amps will be 380 + 25 = 405 or 430 - 25 = 405 amps. This is a very rough calculated answer for the question.


What size cable is needed to supply 415v 250 amp three phase fuseboard?

A 250 MCM copper conductor with a insulation factor of 75 or 90 degrees C is rated at 255 and 265 amps respectively. This conductor can only be load to 80% capacity which allows a working current of 204 and 212 amps respectively. To obtain the full capacity of 250 amps a 350 MCM conductor will be needed. The amp rating for a 350 MCM conductor with an insulation factor of 90 degrees C is 325 amps. 325 x .8 = 260 amps.


What size SER cable to use for 375amp load?

A 400 MCM copper conductor with an insulation temperature factor of 90 degrees C is rated at 380 amps.A 500 MCM copper conductor with an insulation temperature factor of 75 degrees C is rated at 380 amps.These conductors can have either 600 or 1000 volt insulation rating depending on what the system voltage in use is.

Related Questions

What size of copper do you need for a 1250 amps rating?

There are different combination to obtain a current capacity of 1250 amps. A parallel run of #1250 MCM wires. A triple run of #600 MCM wire. The most flexible run would be with a quad run of #350 MCM wire.


How many amps does a wire rated at 600 have?

This answer is if you are referring to the sizing of electrical conductors in North America using the AWG for sizing. An American Wire Gauge sizing of 600 refers to the cross sectional area of the conductor.This amperage value is for a single copper conductor.A 600 MCM copper conductor with an insulation rating of 75 or 90 degrees C is rated for 690 and 780 amps respectively.This amperage value is for not more than three copper conductors in a conduit or raceway.A 600 MCM copper conductor with an insulation rating of 75 or 90 degrees C is rated for 420 and 475 amps respectively.This amperage value is for a single aluminium conductor.A 600 MCM aluminium conductor with an insulation rating of 75 or 90 degrees C is rated for 545 and 615 amps respectively.This amperage value is for not more than three aluminium conductors in a conduit or raceway.A 600 MCM copper conductor with an insulation rating of 75 or 90 degrees C is rated for 340 and 385 amps respectively.


What size copper wire for a run of 500 feet in parallel for a resident with a load of 600 amps single phase 240 volt?

This is a voltage drop question. A 500 MCM copper or 750 MCM aluminium conductor will limit the voltage drop to 3% or less when supplying 300 amps for 500 feet on a 240 volt system. Paralleling these conductors will allow the rating to be increased to 600 amps.


How many amps is 600 mcm good for?

The ampacity of 600 kcmil (mcm) copper wire varies depending on the application and installation conditions, such as whether it is in conduit or in free air. Generally, 600 kcmil copper wire can carry approximately 700 to 800 amps at a temperature rating of 75°C. For specific applications, it is always advisable to consult the National Electrical Code (NEC) or local regulations to ensure compliance and safety.


What size wire is required for 325 amp service?

A 350 MCM copper conductor with an insulation rating of 90 degree C is rated at 350 amps.


What size romex for 60 amps of service?

A 300 MCM copper conductor with an insulation rating of 90 degrees C is rated at 320 amps. Parallel the feeders to obtain a total of 640 amps. This will be acceptable as service feeders for a 600 amp service.A 400 MCM aluminium conductor with an insulation rating of 90 degrees C is rated at 305 amps. Parallel the feeders to obtain a total of 610 amps. This will be acceptable as service feeders for a 600 amp service.


What wire size should you use for 600 amps?

The wire size for 600 amps on a single wire 1250 MCM. A 1250 MCM copper conductor is rated for 645 amps with an insulation rating of 90 degrees C. This size of wire is too large to handle easily when it comes to the terminations. A service requiring 600 amps is usually paralleled or tripled which reduces the wire size which makes the wire much easier to handle. For a parallel service two 350 MCM cables are used and for a triple parallel run three 2/0 conductors are used. These conductors all have an insulation rating of 90 degrees C.


What size wire do you need for 900 amp?

That would need a busbar, an aluminium one with a cross section of 1 cm by 9 cm (or larger). <<>> A 600 MCM copper conductor with an insulation factor of 90 degrees C is rated at 475 amps. A 300 MCM copper conductor with an insulation factor of 90 degrees C is rated at 320 amps. A 3/0 copper conductor with an insulation factor of 90 degrees C is rated at 225 amps. These size wires can be installed in parallel 600 MCM, tripled for 300 MCM or grouped in four 3/0 wires groups to achieve the amperage required. Special parallel, three barrel and four barrel lugs have to be used to make the connection to the required load.


What is the ampere rating of 250 mcm inverter duty wire?

A 250 MCM copper conductor with an insulation factor of 75 or 90 degrees C is rated at 255 and 290 amps respectively


What size of parallel wire for 900 amp service?

Conductors by code are only allowed to be loaded up to 80 percent. In this case an over size wire set will be higher that what the wire is rated for in the code book. A 600 MCM copper conductor with an insulation factor of 90 degrees C is rated at 455 amps. Paralleled together will give an ampacity of 910 amps. After the derate the maximum amperage allowed is 728 amps. So to get the full 900 amp the wire size has to be increased to a 1000 MCM copper conductor with an insulation factor of 90 degrees C which is rated at 585 amps. Paralleled this give you an ampacity of 1170 amps. After the derate the maximum amperage allowed is 1170 x 80% = 936 amps


What is the amperage rating of 500 MCM copper conductor?

It depends on a lot of factors. Generally speaking, if the insulation is THHN then the rating is 350 amps. If the insulation is THWN then the rating is 310 amps. The ampere rating for wire depends on the temperature of the environment it will be used in, the insulation rating and the number of circuits installed in a conduit. There are also other factors to consider... like voltage drop in long runs.


What size ground wire for 600 amp service?

Ground is sized based on the size of the feeder wire and not the amps of the service! However, for a 600 amp service 1500MCM copper wire is one option (NEC 310.16) ;therefor, ground wire is 3/O copper (NEC 250.66) or another option is a two sets of 350 MCM copper wire then a #2 copper (since the biggest feeder wire is 350MCM).