Turns Ratio = (Primary turns / Secondary turns) To calculate the turns ratio you have to actually know the number of turns or wraps on the primary and secondary coils. Nobody knows that usually the manufacture of the transformer doesn't even know. So what you can use as and equivalent is to calculate the voltage ratio. So what you typically need to look for is the Input voltage and divid it by the output volatge. Usually that would be as follows; (Primary Voltage/Secondary Voltage) = Voltage Ratio
First find the ratio of the transformer. 6600/220 volts. Second find the secondary current, I = W/E, 99000/220. Third divide the secondary current by the transformer ratio. The answer will be the primary current. To check your answer (W (or VA) = V x A) multiply the primary current times the primary voltage and the secondary current times the secondary voltage and they should both equal the transformer's kVA.
By design are you going to wind the transformer yourself? In your design you need a 5:1 ratio. On the output side of the transformer any two legs of a three phase transformer is considered single phase voltage. Good luck on your project.
The phase relationship between the primary voltage and the secondary voltage of a transformer is 180 degrees (typically) on single phase transformers. If working with three phase transformers, a zero phase shift is often used in Y/Y grounded transformers. If the transformer is wired Delta / Wye, the phase shift will be 30 degrees. I've seen transformers with a phase shift of 150 as well (quite abnormal, but it exists!) due to the starring and a delta / wye configuration. If you are looking at a transformer phasor diagram, this will show the phase shift between primary or secondary (three phase transformers). For single phase, there should be a drawing showing polarity markings - what goes in the polarity marking on the primary comes out on the secondary polarity marking.
It's approximately the inverse of the voltage- or turns-ratio:
For an ideal transformer, the voltage ratio is the same as its turns ratio.
Secondary voltage / primary voltage
Turns Ratio = (Primary turns / Secondary turns) To calculate the turns ratio you have to actually know the number of turns or wraps on the primary and secondary coils. Nobody knows that usually the manufacture of the transformer doesn't even know. So what you can use as and equivalent is to calculate the voltage ratio. So what you typically need to look for is the Input voltage and divid it by the output volatge. Usually that would be as follows; (Primary Voltage/Secondary Voltage) = Voltage Ratio
line transformation ratio would be the turns ratio (ie voltage ratio), while the phase transformation ratio is most probably the phase shift introduced by a 3 phase transformer.
No, the turns ratio formula calculates the ratio of the primary to secondary winding turns on a transformer using the number of turns on each winding. Phase voltages and currents are not directly used in this calculation.
First find the ratio of the transformer. 6600/220 volts. Second find the secondary current, I = W/E, 99000/220. Third divide the secondary current by the transformer ratio. The answer will be the primary current. To check your answer (W (or VA) = V x A) multiply the primary current times the primary voltage and the secondary current times the secondary voltage and they should both equal the transformer's kVA.
By design are you going to wind the transformer yourself? In your design you need a 5:1 ratio. On the output side of the transformer any two legs of a three phase transformer is considered single phase voltage. Good luck on your project.
It depends on the turns ratio of the transformer.
Count the turns ratio of the windings. The voltage ratio is equal to the turns ratio. The current ratio is equal to the inverse of the turns ratio. For instance, a power transformer with a 10:1 turn ratio (primary to secondary) running on 120V will produce 12V. If it consumes 1 ampere from the input, it will provide 10 amperes to the output.
The phase relationship between the primary voltage and the secondary voltage of a transformer is 180 degrees (typically) on single phase transformers. If working with three phase transformers, a zero phase shift is often used in Y/Y grounded transformers. If the transformer is wired Delta / Wye, the phase shift will be 30 degrees. I've seen transformers with a phase shift of 150 as well (quite abnormal, but it exists!) due to the starring and a delta / wye configuration. If you are looking at a transformer phasor diagram, this will show the phase shift between primary or secondary (three phase transformers). For single phase, there should be a drawing showing polarity markings - what goes in the polarity marking on the primary comes out on the secondary polarity marking.
Yes
The voltage ratio of a potential, or voltage, transformer (PT or VT) depends upon the primary voltage to which it is connected. Accordingly, its voltage ratio varies considerably, as there is huge variety of system voltages throughout the world.Typically a VT's secondary voltage is standardised at 110 V which will match the full-scale deflection of a voltmeter connected to it (although it can also supply protective relays), while its primary voltage is then matched to the voltage of the system to which it is connected: in the UK, for example:11-kV:110 V33-kV:110 Vetc.