answersLogoWhite

0

What else can I help you with?

Related Questions

The calculation used to determine amperage of a conductor based on the total number of conductors in a conduit is called A derating B voltage drop C conduit fill D conductor fill?

derating


How many current carrying conductors are allowed in a raceway before derating?

You can put three ccc's in a conduit (any size conduit) before you derate. Keep in mind that for single phase loads (lighting, receptacles) the neutral is also counted as a current carrying conductor. This derating factor does not apply to nipples 24 inches long or less. See NEC Table 310.15(B)(2)(a) for full details on derating regarding ccc's.


When do you derate wires in conduit I know the code says more than 3 current carrying conductors but is there a length of conduit run when you should start to derate?

There are two things here to keep in mind. If you are trying to add more conductors to an existing conduit run use the cross sectional area of the conduit to see if more wires can be fitted. The second thing that's relates to length is the voltage drop at the load. To size the conduit work backwards from the load amperage to size the wires. If a long distance is involved a voltage drop calculation will be needed. Then select the conduit size to accommodate the wires recommended for that load amperage. The length of conduit run is not brought into the equation on de rating wire size it is always about keeping the voltage up at the load end of the run by increasing the wire size and selecting the proper conduit size for that wire.


Can you use existing PVC conduit run from basement to 8th floor for 120v circuits for chillers?

The simple answer to your question is yes. But there are limits to how many wires can be in any conduit, and the current carrying capacity of the conductors can be affected by distance, ambient temperature, and how many conductors are contained in the same conduit. Other things to consider are, Can you physically fit the wires in there? Would it be easier to run a new conduit? Do you have the manpower necessary to get the work done?


Does the Nec allow grounding electrode conductor to be run in conduit that has other conductors in the conduit and what code section?

No, the bare copper grounding conductor can not be in a conduit with other conductors. It can be in conduit by itself to provide mechanical protection for the wire.


What information can be found in the NEC PVC conduit fill table?

The NEC PVC conduit fill table provides information on the maximum number of conductors that can be safely installed in a PVC conduit based on the size of the conduit and the size of the conductors.


What is the definition of electrical capacity?

The amount of conductors per conduit size example code says 3 number 4 conductors in a 1'' conduit


What size conduit for four 4 cables?

Conduit sizing is based on the number of conductors that are drawn into it. Without the number of 1000 MCM conductors, an answer an not be given.


What information does the electrical pipe fill chart provide for determining the maximum number of conductors that can be safely installed in a conduit?

The electrical pipe fill chart provides information on the maximum number of conductors that can be safely installed in a conduit based on the size of the conduit and the size of the conductors.


Can branch circuits from a panel be pulled in the same conduit if not exeeding the conduit fill requirements?

Yes. The thing that has to be closely watched is the load on the conductors. The conductors will have to be de-rated as the code only gives amperage rating for three conductors in a raceway. So watch the connected amperage to each load and fill the conduit accordingly. This supersedes the conduit fill requirements rule.


Can you have only one current carrying conductor in a conduit?

You can have only one current carrying conductor in a conduit, but that conduit must have a slot to relieve the eddy currents that will be created by the transformer effect created by the conductor. It is better to run the neutral or opposite conductor along with the hot conductor together in the same conduit, or through the same penetration, so as to minimize this effect.


What is a conduit?

A conduit is a set of closed canalization circular or not that assures the free passage of conductors and ensures their continuous protection.