The primarys are marked with the letter H and the secondary terminals are marked with the letter X. The rest depends on how many phases, single transformer, bank transformes, secondary outputs desired, delta or wye or both, etc.....
A: most of the time there are not marked with anything. for a power transformer the primary will offer a resistance of 15 ohms the secondary can be more or less depends on applications
The secondary current of a transformer is determined by the load and the secondary voltage applied to that load, and this, in turn, will determine the primary current by the inverse of the turns ratio. However, if you are asking about a transformer's rated secondary and primary currents, then you need to divide the transformer's apparent power rating (expressed in volt amperes) by the rated secondary and primary voltages respectively.
First of all, transformers are rated in volt amperes, not watts. Secondly, in order to determine a transformer's turns-ration, you need to know its primary and secondary voltage ratings.
Turns Ratio = (Primary turns / Secondary turns) To calculate the turns ratio you have to actually know the number of turns or wraps on the primary and secondary coils. Nobody knows that usually the manufacture of the transformer doesn't even know. So what you can use as and equivalent is to calculate the voltage ratio. So what you typically need to look for is the Input voltage and divid it by the output volatge. Usually that would be as follows; (Primary Voltage/Secondary Voltage) = Voltage Ratio
the most basic transformers have at least two coils, a primary and a secondary. A transformers nameplate will provide you with the max allowed voltage and current, as well as a voltage per turn ratio. for example a step down transformer could have a primary of 120 volts and a secondary of 24 volts this would give you a ratio of 5:1.
The secondary load current will change. This, in turn, will cause the primary current to change (the primary current being the phasor sum of the [IS (Np/Ns)] and the primary current (Io).
The primary current of a transformer depends upon the secondary current which, in turn, depends upon the load supplied by the transformer. There is not enough information in the question to determine the rated primary and secondary currents of the transformer.
3
The secondary voltage of a transformer with a turns ratio of 5 to 1, and primary voltage of 200 is 40. (5 to 1)
The secondary current of a transformer is determined by the load and the secondary voltage applied to that load, and this, in turn, will determine the primary current by the inverse of the turns ratio. However, if you are asking about a transformer's rated secondary and primary currents, then you need to divide the transformer's apparent power rating (expressed in volt amperes) by the rated secondary and primary voltages respectively.
As far as a transformer is concerned, the secondary voltage Vs value cannot be determined by the primary voltage Vp alone. For the simplest of calculations the transformer primary-secondary turn ratio must be known. For an ideal transformer ( and practicaly ideal transformers don't exist as there will be various losses in the transformer cores and windings), the simple equation relating secondary voltage to primary voltage would be : Vs/Vp=Ns/Np=Ip/Is where Ns is the number of winding turns in the secondary of the transformer, and Np the primary. Ip is the primary current and Is the secondary.
Transformer turn ratio is the ratio between the turns on the primary side and the number of turns on the secondary side. For instance if you have a turn ration of 100:200 the primary side has 100 turns and the secondary side has 200 turns. This will be a step up transformer. 10 volts AC into the primary side will result in 20 volts on the secondary side. There will be a decrease in current but the voltage will increase. The total power into and out of the transformer will be the same minus some losses for resistance in the windings.
First of all, transformers are rated in volt amperes, not watts. Secondly, in order to determine a transformer's turns-ration, you need to know its primary and secondary voltage ratings.
K is the ratio of the number of secondary winding turns of wire around the transformer core verses the number of turns on the primary.
Output from secondary is about 6.8V rms, on no load. On the primary side, you have 140 / 120 = .86 volts per turn. Therefore, on the secondary side you will have 8*.86 = 6.8 volts.
Output from secondary is about 6.8V rms, on no load. On the primary side, you have 140 / 120 = .86 volts per turn. Therefore, on the secondary side you will have 8*.86 = 6.8 volts.
Turns Ratio = (Primary turns / Secondary turns) To calculate the turns ratio you have to actually know the number of turns or wraps on the primary and secondary coils. Nobody knows that usually the manufacture of the transformer doesn't even know. So what you can use as and equivalent is to calculate the voltage ratio. So what you typically need to look for is the Input voltage and divid it by the output volatge. Usually that would be as follows; (Primary Voltage/Secondary Voltage) = Voltage Ratio
To test a transformer on a furnace, you can use a multimeter to check the voltage output. First, turn off the power to the furnace. Then, locate the transformer and measure the voltage across the primary and secondary terminals. If the voltage matches the specifications provided by the manufacturer, the transformer is functioning properly. If not, the transformer may need to be replaced.