answersLogoWhite

0

Yes, ground fault protection for equipment is requiredeven if the neutral will not be used.

However, the question implies that it might not be required if there is a neutral. That is not true. With two exceptions, ground fault protection is always required in the US, and it is probably required in other countries as well.

The exceptions are the use of an electric cooking range, and an electric clothes dryer. In those cases, the US NEC allows the neutral conductor to also be the ground fault conductor, except for the case where the range or dryer is in a mobile home. In the case of the mobile home, the ground fault conductor and the neutral conductor must be maintained separate and distinct all the way back to the distribution panel.

In every other case, including where local code overrides the US NEC's exceptions, it must be understood that ground fault protection (protective earth ground) is not the same as neutral, even though the neutral conductor is grounded.

User Avatar

Wiki User

15y ago

What else can I help you with?

Continue Learning about Engineering

What is neutral to ground fault?

Neutral, by definition, is grounded at the distribution panel, and also at the distribution pole. That is how the hot to ground voltages are prevented from exceeding their normal voltage and encroaching on truly lethal voltages, such as 7.6kV in a typical US 13.2kV system, in a wye configuration.Note: and this is critical, do not depend on the fact that neutral is grounded and consider that it is the same as protective earth ground. It is not. Protective earth ground is a different wire.


What is grounding - grounded - neutral?

A) If low resistance configuration is chosen, then, ground fault current is greater than 25% of 3-phase value. B) If high resistance configuration is chosen, then, ground fault current is between 1 to 5% of 3-phase value. C) Ground fault protection scheme is important because affects resistor thermal rating, hence size. D) For B) above, ground fault current must not be less than system charging current produced by phase to ground capacitance in 11 kV system. E) For D) above, total capacitance calculation must include line to ground capacitance of cables, motors, transformers, and (often forgotten) surge protection capacitors, as well as lightning arrestors. shirish prajapati


Why neutral ground voltage is 120v sometime 0v?

There should be no voltage on the neutral wire to ground. This is a serious situation. Call a qualified electrician to check this out.


Can you glow led by using neutral and earth?

If you connected neutral and earth (ground) to each lead in an LED and it glowed then this would be evidence of a ground fault.


When you test the outlet you get no current between power and neutral but you get it between power and ground?

There is an open circuit on neutral. You should have power between hot and neutral, as well as between hot and ground. Note well, however, that you should not pull any power between hot and ground, because ground is not intended to be a current carrying conductor - it is only there as a protective earth ground in the case of fault. You can not easily tell, at the outlet, if neutral and ground is reversed - you need to pull a load and then double check with a clamp on ammeter at the distribution panel.

Related Questions

What is neutral grounding resistor panel?

A neutral grounding resistor panel is used to resist fault current to the ground. It is used for alternator protection protection purposes. When a fault occurs in the alternator, the panel helps force the current to the ground.


Is equipment ground required in EMT conduit?

Yes it should be grounded


What happens if you connect neutral to ground in an electrical circuit?

Connecting neutral to ground in an electrical circuit can create a dangerous situation called a ground fault. This can lead to electrical shock, fires, and damage to appliances or equipment. It is important to keep neutral and ground separate to ensure the safety and proper functioning of the electrical system.


How a 240 V GFCI breaker works without a neutral ran to the equipment?

A 240V GFCI breaker monitors the difference in current between the hot wires, providing ground-fault protection without needing a neutral wire. It compares the current on both hot wires and trips if an imbalance is detected, indicating a ground fault. This system does not rely on a neutral wire to detect faults and protect against electrical shocks.


What is meant by neutral grounding reactor?

Neutral-earthing reactors or Neutral grounding reactors are connected between the neutral of a power system and earth to limit the line-to-earth current to a desired value under system earth fault conditions.


What all is considered to fall into the category of lighting protection equipment?

Lighting protection equipment includes; rod clamps, plates,surge suppressors, fasteners, conductors, air terminals, and ground straps.


Define earth voltage and neutral voltage?

As the neutral point of an electrical supply system is often connected to earth ground, ground and neutral are closely related. Under certain conditions, a conductor used to connect to a system neutral is also used for grounding (earthing) of equipment and structures. Current carried on a grounding conductor can result in objectionable or dangerous voltages appearing on equipment enclosures, so the installation of grounding conductors and neutral conductors is carefully defined in electrical regulations. Where a neutral conductor is used also to connect equipment enclosures to earth, care must be taken that the neutral conductor never rises to a high voltage with respect to local ground.


May you use earth wire as neutral wire?

1. SafetyWhen there are separate wires for neutral and ground it is much less likely that a problem in electrical wiring causes a dangerous situation which will cause electrical shock or fire.If the ground and neutral were the same conductor, the cutting only the neutral wire (for example by accident) would cause the grounded metal case of the equipment to be on mains potential just because there is only live connected to equipment and that voltage can go through the equipment to the cut neutral cable and from there to equipment case.When ground and neutral are separate, then cut neutral causes only the equipment to stop working and no dangerous situation. If ground gets cut by accident, there is no danger caused before some equipment gets damaged. So when there is separate wires for neutral and ground, a singe wire fault (cut or short circuit to other wire) on any wire going to outlet does not cause immediate danger to the user of the equipment:2. Minimizing the ground potential differences between outlet groundsIn an ideal separate grounding wire system there is no current flowing in ground wire network, so there is no voltage difference between grounds on different outlets. Unfortunately in real life systems there is always some current leaking to ground, but that current is very small (only probably milli amperes) compared to the current flowing on line and neutral wires (usually amperes).If the neutral and ground were shared on same wire, the current flowing on neutral wire would easily cause a large voltage difference (up to many volts) on different outlets grounds. The ground potential on any outlet will then depend on the load current, neutral wire resistance and the mains phase it is connected to.


Is it OK illegal or dangerous to connect the neutral to ground to make the circuit work?

If you have to connect the neutral to ground to make the circuit work then you have an open neutral in your circuit. Be careful in handling the neutral as there can be voltage potential on the neutral if a load is connected. In a properly wired home that has been inspected by the local electrical inspector the neutral should be bonded to the ground at the main service distribution point. There will be a green screw that projects through the neutral bus and is threaded into the back of the electrical panel. This should be the one and only place in the whole electrical system where this neutral to ground connection takes place. Dangerous!!!!! The ground is the safety to prevent you from getting shocked due to a malfunctioning piece of equipment. By using the ground for a neutral you will be energizing the entire ground system of you house or business. Thus anything with metal on it and a ground wire going to it will be electrified if the ground fails at the breaker box or building ground rod. Do you want to take this risk? Not I..........


Which is not a protection against electrical accidents?

Do not attempt to climb off of the equipment, you would become the path to ground for the electricity.


Can the bare grounded neutral conductor of a service be buried directly in the ground?

A bare grounded neutral should never get close to the ground if it is wired properly. When the neutral leaves the meter base it is in conduit and should enter into the distribution panel where it connects to the neutral buss. It is at this junction that the copper ground wire is connected after coming from the outside ground rod or ground plate which ever grounding system was used.


Is the neutral bus bonded to the equipment ground in a subpanel?

Definitely not. The neutral wires must be put on the neutral buss and that is the only place that they are to be terminated in a distribution panel. In a distribution panel there is no ground buss, it is just the metal enclosure that is used. The ground wire is only used to return a system fault back to the distribution panel to trip that circuits breaker.Distribution panels typically have two "busses"-- one for ground and one for neutral. These are terminal strips where the ground and neutral wires are connected. In some panels, these busses are electrically connected or "bonded." In other panels they are isolated. Most panels come with an optional "bonding screw" that can be installed or removed depending on whether the busses need to be connected. NEC is very specific on when these busses are to be connected. Ground and neutral busses should only be bonded at the main panel where the service enters the building. Other distribution panels will have separate ground and neutral busses and they should be isolated electrically--connecting these is a commonly seen mistake.I believe the question refers to the case where the two busses are properly bonded together, so are electrically equivalent. Then is it acceptable to have some ground wires on the neutral bus and vice-versa. Electrically it will work, but code or electrical inspectors may deem it to be confusing or sloppy practice and reject the installation.As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energized.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.