Parallel Operation of DC Generators: In a dc power plant, power is
usually supplied from several generators of small ratings connected in
parallel instead of from one large generator. This is due to the following
reasons:
(i) Continuity of service: If a single large generator is used in the power
plant, then in case of its breakdown, the whole plant will be shut down.
However, if power is supplied from a number of small units operating in
parallel, then in case of failure of one unit, the continuity of supply can be
maintained by other healthy units.
(ii) Efficiency: Generators run most efficiently when loaded to their rated
capacity. Therefore, when load demand on power plant decreases, one or
more generators can be shut down and the remaining units can be
efficiently loaded.
(iii) Maintenance and repair: Generators generally require routinemaintenance
and repair. Therefore, if generators are operated in parallel,
the routine or emergency operations can be performed by isolating the
affected generator while load is being supplied by other units. This leads
to both safety and economy.
(iv) Increasing plant capacity: In the modern world of increasing
population, the use of electricity is continuously increasing. When added
capacity is required, the new unit can be simply paralleled with the old
units.
(v) Non-availability of single large unit: In many situations, a single unit
of desired large capacity may not be available. In that case a number of
smaller units can be operated in parallel to meet the load requirement.
Generally a single large unit is more expensive.
Connecting Shunt Generators in Parallel: The generators in a power
plant are connected in parallel through bus-bars. The bus-bars are heavy
thick copper bars and they act as +ve and -ve terminals. The positive
terminals of the generators are .connected to the +ve side of bus-bars and
negative terminals to the negative side of bus-bars. Fig. (1) shows shunt
generator 1 connected to the bus-bars and supplying load. When the load
on the power plant increases beyond the capacity of this generator, the
second shunt generator 2 is connected in parallel with the first to meet the
increased load demand. The procedure for paralleling generator 2 with
generator 1 is as under:
(i) The prime mover of generator 2 is brought up to the rated speed. Now
switch S4 in the field circuit of the generator 2 is closed.
(ii) Next circuit breaker CB-2 is closed and the excitation of generator 2
is adjusted till it generates voltage equal to the bus-bars voltage. This is
indicated by voltmeter V2.
(iii) Now the generator 2 is ready to be paralleled with generator 1. The
main switch S3 is closed, thus putting generator 2 in parallel with
51
generator 1. Note that generator 2 is not supplying any load because its
generated emf is equal to bus-bars voltage. The generator is said to be
"floating" (i.e. not supplying any load) on the bus-bars.
Figure(1)
(iv) If generator 2 is to deliver any current, then its generated voltage E
should be greater than the bus-bars voltage V. In that case, current
supplied by it is I = (E - V)/Ra where Ra is the resistance of the armature
circuit. By increasing the field current (and hence induced emf E), the
generator 2 can be made to supply proper amount of load.
(v) The load may be shifted from one shunt generator to another merely
by adjusting the field excitation. Thus if generator 1 is to be shut down,
the whole load can be shifted onto generator 2 provided it has the
capacity to supply that load. In that case, reduce the current supplied by
generator 1 to zero (This will be indicated by ammeter A1) open C.B.-1
and then open the main switch S1.
Load Sharing: The load sharing between shunt generators in parallel can
be easily regulated because of their drooping characteristics. The load
may be shifted from one generator to another merely by adjusting the
field excitation. Let us discuss the load sharing of two generators which
have unequal no-load voltages. Let E1, E2 = no-load voltages of the two
generators R1, R2 = their armature resistances
V = common terminal voltage (Bus-bars voltage). Then
1
1
1 R
I E V
and
2
2
2 R
I E V
Thus current output of the generators depends upon the values of E1 and
E2. These values may be changed by field rheostats. The common
terminal voltage (or bus-bars voltage) will depend upon (i) the emfs of
individual generators and (ii) the total load current supplied. It is
generally desired to keep the busbars voltage constant. This can be
52
achieved by adjusting the field excitations of the generators operating in
parallel.
Compound Generators in Parallel: Under-compounded generators also
operate satisfactorily in parallel but over compounded generators will not
operate satisfactorily unless their series fields are paralleled. This is
achieved by connecting two negative brushes together as shown in Fig.
(2) (i). The conductor used to connect these brushes is generally called
equalizer bar. Suppose that an attempt is made to operate the two
generators in parallel without an equalizer bar. If, for any reason, the
current supplied by generator 1 increases slightly, the current in its series
field will increase and raise the generated voltage. This will cause
generator 1 to take more load. Since total load supplied to the system is
constant, the current in generator 2 must decrease and as a result its series
field is weakened. Since this effect is cumulative, the generator 1 will
take the entire load and drive generator 2 as a motor. After machine 2
changes from a generator to a motor, the current in the shunt field will
remain in the same direction, but the current in the armature and series
field will reverse. Thus the magnetizing action, of the series field opposes
that of the shunt field. As the current taken by the machine 2 increases,
the demagnetizing action of series field becomes greater and the resultant
field becomes weaker. The resultant field will finally become zero and at
that time machine 2 will be short circuited machine 1, opening the
breaker of either or both machines.
Figure (2)
When the equalizer bar is used, a stabilizing action exists and neither
machine tends to take all the load. To consider this, suppose that current
delivered by generator 1 increases. The increased current will not only
pass through the series field of generator 1 but also through the equalizer
bar and series field of generator 2. Therefore, the voltage of both the
machines increases and the generator 2 will take a part of the load.
If the phase angles of generators operating in parallel are different, it can lead to circulating currents between the generators, potentially causing overheating and damage. The generators may also operate inefficiently, resulting in instability in the power output. To ensure safe parallel operation, generators must be synchronized, meaning their phase angles, voltages, and frequencies must match. Proper synchronization prevents these issues and ensures a stable and reliable power system.
To avoid possible current loop through multiple neutral points
CONDITIONS REQUIRED FOR TRANSFORMER PARALLEL operation are.. 1. Voltage turn ratio. 2. phase sequence 3. Impedence should be same 4. polarity Hitesh
To parallel ship alternators or generators, first, ensure that both units are synchronized in terms of voltage, frequency, and phase sequence. Use synchronization equipment to adjust the output of each generator until they match. Once synchronized, connect the generators to a common bus, ensuring that circuit breakers are in the open position before making connections. After confirming that all parameters are aligned, close the circuit breakers to engage the generators in parallel operation.
A parallel generator is a generator system that operates alongside one or more other generators to provide a combined power output or to share the load demand. This configuration allows for increased reliability, flexibility, and efficiency in power generation, as it can adapt to varying energy needs. In parallel operation, synchronization is essential to ensure that voltage, frequency, and phase are matched across all generators. This setup is commonly used in industrial applications, backup power systems, and renewable energy installations.
If the phase angles of generators operating in parallel are different, it can lead to circulating currents between the generators, potentially causing overheating and damage. The generators may also operate inefficiently, resulting in instability in the power output. To ensure safe parallel operation, generators must be synchronized, meaning their phase angles, voltages, and frequencies must match. Proper synchronization prevents these issues and ensures a stable and reliable power system.
there will be circulating current between the generators sufficiently large that might damage the machines.
To avoid possible current loop through multiple neutral points
CONDITIONS REQUIRED FOR TRANSFORMER PARALLEL operation are.. 1. Voltage turn ratio. 2. phase sequence 3. Impedence should be same 4. polarity Hitesh
To parallel ship's generators, first ensure both generators are synchronized in frequency, phase, and voltage. Use the synchronizing panel to monitor these parameters, making necessary adjustments to the speed governor and voltage regulator. Once synchronized, close the circuit breaker to connect the generators in parallel, and monitor load sharing to ensure even distribution. Regularly check for any alarms or irregularities to maintain safe operation.
The generators also have resistance which causes power loss and voltage drops. Connecting them in parallel reduces the total resistance that reducing the voltage drop as well as increasing the total current.
To parallel two synchronous generators, they must have the same voltage, frequency, and phase sequence. Additionally, their terminal voltages must be in phase alignment, their frequencies must be the same, and their voltages must be within an acceptable range of each other. Proper synchronization is crucial to avoid phase differences and ensure smooth parallel operation.
To parallel ship alternators or generators, first, ensure that both units are synchronized in terms of voltage, frequency, and phase sequence. Use synchronization equipment to adjust the output of each generator until they match. Once synchronized, connect the generators to a common bus, ensuring that circuit breakers are in the open position before making connections. After confirming that all parameters are aligned, close the circuit breakers to engage the generators in parallel operation.
To parallel two generators with different kilowatt (kW) ratings, first ensure they have compatible voltage and frequency outputs. Next, adjust the governor settings to synchronize their speeds and match the phase rotation. Connect the generators to a common busbar, ensuring the load is shared proportionally to their capacity, typically using load-sharing controllers. Finally, monitor the system for any imbalances or issues during operation.
List out the conditions to be satisfied for running two or more DC shunt generators in parallel?
Parallel operation is essential for several reasons, including increased reliability, enhanced system capacity, and improved load distribution. By operating multiple generators or power sources in parallel, a system can provide redundancy; if one unit fails, others can continue to supply power. Additionally, parallel operation allows for better management of varying loads, ensuring optimal efficiency and performance across the system. This approach also facilitates maintenance without interrupting service, as individual units can be taken offline while others remain operational.
A parallel generator is a generator system that operates alongside one or more other generators to provide a combined power output or to share the load demand. This configuration allows for increased reliability, flexibility, and efficiency in power generation, as it can adapt to varying energy needs. In parallel operation, synchronization is essential to ensure that voltage, frequency, and phase are matched across all generators. This setup is commonly used in industrial applications, backup power systems, and renewable energy installations.