answersLogoWhite

0

What else can I help you with?

Continue Learning about Engineering

Motor has full load current of 39.5 Amps the actual current measured on each phase is 25 Amps in delta you need to know if the motor is below its full capacity Any calculations to help you compare?

First, check the nameplate on the motor. The FLA or full load amperage is the required start up current and is typically 125-150 % higher than the running load amperage (RLA). So a current draw of 39.5 while starting would be normal for a motor drawing 25 A in run mode.You don't need any calculations. If the stated RLA is close to 25 A and you're drawing 25 A then the motor is fine. As long as you're supplying the correct full voltage required by the motor, it will operate at "full capacity". There are numerous formulas for motors. I would need to know the motor's horsepower, voltage, whether it's single or three phase and its stated efficiency (EFF on the nameplate), the FLA and RLA to tell you if the motor is running properly or if it's going bad.


How do you measure RLA on a 230-1 phase motor do you add each the amps measured on each leg?

You can't measure an RLA. It is determined by the factory that manufactured the compressor. To answer your other question, a 230 volt load is actually using both legs as part of the circuit, so you can measure either leg with a current meter but there is no need to add them up.


How do you run a motor 208 volts ac in a 230 volts suply?

If your motor is rated for only 208 volts you may not be able to use 230 volts for it. It will run, but may shorten the life of the motor. Motors are rated with a 10% tolerance for voltage. This means that a 208 volt motor has a maximum voltage rating of 228.8 volts. So measure you voltage supply and see if it is below 228.8 with a good RMS voltmeter. If it is, you are good to go. If it is not there are two ways to make it work. 1. Put a high wattage ballast resister in series with the supply voltage to drop the voltage to the motor within range of 187.2 to 228.8 volts. To determine the value of the resistor take the Horse Power of the motor and multiply it by 746. This will give the wattage of the resistor, use one at least 20% larger. Next take the Rated Load Amps (RLA) or Full Load Amps (FLA) of the motor and divide it into the difference between 230 (voltage supply) and the 208 (rated motor voltage), this will get you close to the resistance value of the Ballast resistor you need to use. So a 1/2 HP motor with a 1.2 RLA will require about a 18 ohm, 500 watt ballast resistor. This is not the recommended method, but will work. 2. Install a Buck & Boost transformer rate for the HP of the motor that will Buck the supply voltage for the motor down to 208 volts. This is the recommended way and the only way it should be done. Any good commercial electrical supply house can help you properly size the transformer that you will need.


How do you find the no load amp rating of a motor?

Full load amps is found on the motor's nameplate, and is unique to that particular brand and model number. A Magnetec 2hp motor will draw different amps than a Baldor 2hp, etc. There are high efficiency motors, and not so high as well. Consult the nameplate. If you want a "rule of thumb" to estimate the RLA (Running Load Amps - this is the term most often found on the nameplate - same as full load amps), then use this: Figure about 1400 watts per horsepower. Divide Watts by volts to get Amps, for example: * 3hp motor, 120V * 3hp X 1400 W = 4200 W * 4200 W / 120 V = 35 A This formula is only for single-phase motors! I looked up a typical 3hp 120 V Baldor motor in the Grainger's catalog, and the RLA for it was 32.0, so this will get you in the ballpark. I have seen 3hp 120 V motors as low as 25 A and as high as 40, so DO NOT use the rule of thumb to size branch circuit conductors or overcurrent protection! For 3-phase motors: Figure about 1100 watts per horsepower (3-phase is a little more efficient). Divide Watts by Volts, then divide the answer by 1.73 to get Amps, for example: * 3hp motor, 208V 3Ph * 3hp X 1100 W = 3300 W * 3300 W / 208 V = 15.86 * 15.86 / 1.73 = 9.16 A This formula is only for 3-phase motors! My Grainger's catalog motor with the same Voltage and HP had a nameplate rating of 8.34 A.


Is surge current the same as short circuit current?

Not usually, but it may depend on the context. For instance, surge current might be used for a generator that is going to start a motor. Motors draw high current as they start, then the current drops to a normal level, called RLA, or running load amps. Generators have a watt rating for continuous operation called running watts, but they also have a 'surge' rating. You might see a generator listed as a '6000/5200 watt. The 6000 watts is the 'surge' rating. This means the generator can supply 6000 watts for a few seconds, such as might be needed to start a motor, but cannot supply more than 5200 watts continuously. Short circuit current on the other hand simply means how many amps will flow instantaneously if you drop a wrench across the two wires! For a normal utility power service, the short circuit current, also called fault current, can be several tens of thousands of amps, even though the main breaker is only a couple hundred amps.

Related Questions

What is rla and lra on compressors?

rla run load amps lra locked rotor amps.


What does rla mean on an air compressor?

Rated load amps = rla


What is RLA in Electrical Terms?

RLA in eletrical terms is Reading Language Arts.


How do you figure out Run Load Amps if it is not given?

To calculate the Run Load Amps (RLA) if it is not given, you can use the formula: RLA = Horsepower x 746 / Efficiency x Voltage x Power Factor x √3 x FLA, where FLA is the Full Load Amps. You need to know the motor's horsepower, efficiency, voltage, and power factor to determine the RLA. If these values are not known, you may need to contact the manufacturer or consult the motor's specifications.


What is 15 RLA to Fla?

15 RLA (Right of Line Abreast) to Fla (Florida) does not have a direct conversion as they are different units of measurement and do not represent the same thing. RLA is a military term for a tactical formation, while Fla is the abbreviation for the state of Florida.


What is the average wattage a freezer uses?

Voltage X amps = wats 120 volt freezer drawing 2 amps is 240 watts running note it can take up to 3 to 4 times that to start. you have rla run load amps then you have LRA Lock rotor amps (what it takes to start)


WHAT IS RLA?

run load ampers


What does RLA stand for?

Republican Literation Association


Motor has full load current of 39.5 Amps the actual current measured on each phase is 25 Amps in delta you need to know if the motor is below its full capacity Any calculations to help you compare?

First, check the nameplate on the motor. The FLA or full load amperage is the required start up current and is typically 125-150 % higher than the running load amperage (RLA). So a current draw of 39.5 while starting would be normal for a motor drawing 25 A in run mode.You don't need any calculations. If the stated RLA is close to 25 A and you're drawing 25 A then the motor is fine. As long as you're supplying the correct full voltage required by the motor, it will operate at "full capacity". There are numerous formulas for motors. I would need to know the motor's horsepower, voltage, whether it's single or three phase and its stated efficiency (EFF on the nameplate), the FLA and RLA to tell you if the motor is running properly or if it's going bad.


How do you measure RLA on a 230-1 phase motor do you add each the amps measured on each leg?

You can't measure an RLA. It is determined by the factory that manufactured the compressor. To answer your other question, a 230 volt load is actually using both legs as part of the circuit, so you can measure either leg with a current meter but there is no need to add them up.


What is locked rotor current?

"Locked Rotor Current" also called LRA which stands for Locked Rotor Amps, is commonly found on electric motor nameplates. Locked Rotor essentially means the motor is not turning. The current or amps in this case have to do with the amount of electrical energy required to start the motor. At the instant the motor is switched on, it is not turning, and draws the maximum current. As the motor starts to turn, the current goes down. This required energy is much greater than the Full Load Amps or Running Amps, which is the current drawn when the motor is running at normal speed under full load. The current required to start the motor will depend on the type of motor as well as the specified design voltage required for the motor, typically the higher the voltage, the lower the required amperage or current. The term also applies to equipment such as Air Conditioners which have an enclosed motor inside the compressor, as well as the condenser fan(s) etc. Depending on the type of motor, LR current can be anywhere from 3 to 8 times the normal running current, also called RLA, or running load amps.


What is the difference between full load amps and running load amps?

Full load amps is the maximum rated amps that the motor should draw according to its nameplate rating. Running load amps is the actual amperage the motor is drawing at that point in time when the test is taken. Some motor loads vary depending on if the load is cyclic. The reading on this type of motor would be from no load amps to full load amps.