Lightning Impulse withstand test is a destructive test carried out on high voltage switchgear. It is classed as a destructive test as each shot damages the insulation and lays carbon tracks.

The Energy Networks Association Technical Specification (ENA-TS) 41-36 states the BIL (basic Impulse level) Required for the Voltage rating of the piece of switchgear rated up to 36kV.

For example an 11kV switchgear will have a BIL of 95kV.

Switchgear which include a Vacuum circuit breaker must have a second means of isolation, ie a disconnector. This disconnector can be a two position (mains on, off) or three position (mains on, off, or earth on) disconnector operated off load which is in series with the Circuit breaker.

To pass the test 15 shots at +95kV and 15 shots at -95kV are fired at all positions of the disconnector and only 2 out of the 15 (and not the last 5) shots can flash over to earth.

For example if the disconnector was in the off position one side will be connected to the impulse generator and the other side will be earthed. Positive and Negative shots will be fired and the impulse can not flash through the air gap to the earthed side of the disconnector.

This proves the isolation gap inside the disconnector has a BIL rating of 95kV.

Therefore if the incoming side of a switchboard is live and the outgoing side is isolated for maintenance. There can be a transient impulse on the live side of the circuit and it will not flash across the isolating gap and endanger anyone working on the dead side of the circuit

User Avatar

Wiki User

14y ago

What else can I help you with?

Related Questions

What is impulse current?

lighting impulse current upto 200000 amperes crest are generated by charging the set of capacitor in parallel and discharging them in same way in a test object which is usually a surge diverter or high rupturing capacity-fuse.


Define rated impulse voltage?

Simply, the voltage which is withstand by the test object as an impulse is called as rated impulse voltage.


What is chopped wave in impulse test?

csACaca


If your disconnector is not hitting your sear?

If your disconnector is not making contact with the sear properly, it could be due to improper assembly or wear on the disconnector or sear. Check for any obstructions or debris that may be preventing proper contact between the two parts. If the issue persists, it may be necessary to replace one or both components.


Why negative impulse is applied during Impulse voltage test?

The lightning phenomena is occurred on transmission lines or sub-stations due to which a negative wave is generated hence definitely destroy the power apparatus. So for impulse voltage testing of any power apparatus one must produce a negative impulse.


What test don't you have to do on a lighting circuit?

A continuity test, just turn the lights on and if there is continuity the fixtures will let you know.


What is meaningful sentence of impulse?

impulse is impulse


What are expressions for impulse?

Impulse = mv Impulse = Fmv


Is impulse body spray tested on animals?

Impulse, owned by Unilever, has a policy against testing their products on animals. They are committed to producing cruelty-free products.


What is Disconnector Switch?

to disconnect the circuit when faults occursAnswerA 'disconnector switch' is another term for an 'isolating switch' or 'isolator'. It is a manually-operated switch used to provide a visible break between a de-energised part of a circuit and the energised part of a circuit so that work can be carried out safely on the de-energised part. A disconnector switch is not intended to break a load current, and most certainly not designed to break a fault current -that is the function of a circuit breaker.


How do you make a sentence with impulse?

I bought the hat on impulse. It was just an impulse.


How to disconnect ac lines from compressor on a Honda Odyssey after the system is purged?

You need to use a fuel line disconnector.