answersLogoWhite

0

Blowdown Valves

In case of Transformer oil the meaning of BDV is break down voltage. It refers to the one of the tests of the oil.

User Avatar

Wiki User

12y ago

What else can I help you with?

Related Questions

How much min BDV of oil in transformer is required when charged it first time in 11kv 66kv and 132 kv of transformer?

The minimum Breakdown Voltage (BDV) of transformer oil required typically varies based on the voltage level of the transformer. For 11 kV transformers, a minimum BDV of around 30 kV is usually acceptable. For 66 kV transformers, a BDV of approximately 50 kV is often required, while for 132 kV transformers, it should be at least 60 kV or higher. Ensuring adequate BDV is crucial for the insulation performance and reliability of the transformer.


What is the expriy date of 11 KV Transformer oil?

It is better to check the BDV (Break down voltage) of the oil to decide whether the said oil is usable for 11KV application, instead of depending upon its "expiry" date.


What are the conditions for operate the three phase transformer?

The BDV value of the transformer oil should be above 50kv winding resistance value should me minimum depends upon the KVA Of trans earthing should be provide for the trans air should be release inside of the tranformer insulation level should be check to operate the transformer these are all the initial condition to operate the trans


What is bdv value of engine oil?

The BDV (Breakdown Voltage) value of engine oil measures its dielectric strength, indicating how well the oil can insulate and resist electrical breakdown. A higher BDV value signifies better quality and performance, as it can help prevent the formation of sludge and ensure effective lubrication under high temperatures and pressures. Typically, BDV values for engine oils should be above 30 kV to ensure proper functionality and longevity. Regular testing can help monitor the oil's condition and its ability to protect engine components.


What is oil transformer?

Transformer oil is pure insulating oil.


How much kv require for trasformer oil BDV?

above thirty (30) KV (rms)


What is the present excise duty of transformer oil?

to cool a winding of transformer and it is a insulating material and transformer oil is a purifing oil


What type of oil transformer is nytro Libra oil?

Nytro libra is an uninhibited transformer oil


Bil of power transformer?

B.I.L. stands for Basic Impulse Level for the transformer. It should be on the faceplate of the transformer.


Name of transformer oil?

An oil transformer is filled with PCB oil to better transfer heat from the windings to the outside case (and into the air).


What is means of transformer oil what contents is there in that oil?

transformer consists of polychlorinated biphenyls,...etc


What is BDV test for distribution transformer?

When you say BDV you might mean the dielectric strength of transformer oil. A new transformer oil should have at lest a dielectric strength of 39 KV. from a British standard.Transformer oils used are normally tested using ASTM D877-82 with the KV strength tester using 1" electrodes spaced 0.1" apart and the test voltage increased at 3,000 volts/min until it breaks down. The average Kv obtained after 8 trials is considered the Oil dielectric strength.Using this test method,dielectric strength at 30 kv and above is considered good. Dielectric strength between 23 to 29Kvis considered usable, but requires filtering. Below 23 kv, the transformer oil should be replaced.Another method ASTM D18747-82 uses the small radius electrodes but spaced only .o4 inches. The test voltage is 500volts/min and increased until breakdown. The dielectric strength is still the average Kv obtained in 8 trials. The dielectric strength of 28-29Kv is considered good. Below 28 kv, the transformer oil is usable but requires filtering. The latter method is considered a better test method