This is because of two reasons:
1. Primarily because SC test is performed at rated Current(as we calculate series parameters-leakage impedance-in SC test). As the rated current on hv side is much less than lv side(VI = constant), so the rated hv side current is easily achieved(compared to lv side). Vice-versa is true for Open circuit test.
2. Also because we cannot short-circuit hv side, as, if we short-circuit hv side, V of hv side essentially falls to zero and since VI(KVA power)=constant, so the hv current will be very high(compared to low rated current on hv side), and will burn the winding.
When short-circuiting lv side, the current also increases but this increase does not burn winding due to low rated V and high rated I (You can consider the example of 220/11V)on lv side. So,SC test is performed on hv side while shorting the lv side.
Also SC test can be performed on either sides for small transformer rating. The above care must be taken for big transformer(High KVA rating)..
A high current flows through a short circuit even if there is no voltage change because the resistance across the short circuit is zero.
In Short circuit test High Voltage side is feeded with 2-5% of the High Voltage rating to circulate approximately full load current in low voltage winding by short circuiting it. Low voltage is generally short circuited to facilitate measurements because it is more difficult to measure the quantities at high voltages.
1)Short circuit test is performed at rated current. As the rated current on high voltage side is much less than low voltage side, so the rated high voltage side current is easily achieved compared to low voltage side. 2)Also because we cannot short circuit high voltage side, as, if we short circuit high voltage side, voltage of high voltage side essentially falls to zero and since VI=constant, so the high voltage side current will be very high and will burn the winding.
Since a short circuit is, essentially, a zero impedance connection between nodes, the current in a short circuit is limited only by the ability of the source. In the case of an ideal voltage source connected to an ideal short circuit, you would have infinite amperes.
in the open circuit test, the high voltage winding is open circuited and the measurements are made on the low winding side i.e, the open circuit test is performed on the L.V side. This is because if the measurements are made on HV side then voltage applied must be large and the current would be unsuitably small, for which the high voltage sources may not be readily available and at the same time the instrument ranges required should be very high, Also the result obtained may not be accurate. NOTE: iron loss will be same, if measured from either of the winding. in short circuit test. the low voltage winding is short circuited and the measurements are made on the high voltage winding side i,e,. the sort circuit test is performed on H.V side. This is because if the test is performed on the L.V side, the current will be suitably large for which the instruments used should be of very high ranges. moreover instruments of such high ranges and the auto-transformer capable of handling such high currents may not be readily available.
A high current flows through a short circuit even if there is no voltage change because the resistance across the short circuit is zero.
Most likely a short circuit will cause no voltage. Due to the high current on a short circuit fault the over current protection of the circuit will trip. This will cut the voltage supply off completely.
In Short circuit test High Voltage side is feeded with 2-5% of the High Voltage rating to circulate approximately full load current in low voltage winding by short circuiting it. Low voltage is generally short circuited to facilitate measurements because it is more difficult to measure the quantities at high voltages.
I assume "tension" in this question should be replaced with "voltage". Short circuit tests are often performed from the lower voltage side of the transformer, since a lower voltage source is then required to perform the test. Often times the test lab may not have a source that can output a high enough voltage to perform from the high voltage winding.
generally open circuit test is performed on the low voltage side.....not on high voltage side.... becuase on low voltage side, we can apply that low voltage very easily ( i.e with a less amount of source is required)... whereas on high voltage side, we need a large power source in order to apply full voltage... in short circuit test, we will test on high voltage side by keeping Low voltage side being short circuit.because high voltage side needs less current source than low voltage side....
in the short circuit test we applied supply voltage on L.V side and short circuit the H.V side and connect the ammeter in H.V circuit to measure the short circuit current. with the help of s.c test we measure the copper losses in the transformers.
1)Short circuit test is performed at rated current. As the rated current on high voltage side is much less than low voltage side, so the rated high voltage side current is easily achieved compared to low voltage side. 2)Also because we cannot short circuit high voltage side, as, if we short circuit high voltage side, voltage of high voltage side essentially falls to zero and since VI=constant, so the high voltage side current will be very high and will burn the winding.
Since a short circuit is, essentially, a zero impedance connection between nodes, the current in a short circuit is limited only by the ability of the source. In the case of an ideal voltage source connected to an ideal short circuit, you would have infinite amperes.
This is describes the condition at the location a short-circuit fault.
The circuit voltage is too high. Could be a failed sensor, wiring short, or PCM problem.
Map sensor circuit voltage highMap sensor circuit voltage high
When a voltage is present between two points in a circuit (electrical outlet, battery, etc.) it normally flows through a load of some resistance to do some work. If instead a pure conductor (usually metal) connects the two points separated by a voltage, a short circuit results. Current through the short circuit is very high and usually results in fire or failure unless protected by a circuit breaker. In low-voltage, low-power electronics a short circuit might not be dangerous but is usually undesirable.