The recommended gauge size for a 20 amp wire in a residential electrical circuit is typically 12 AWG (American Wire Gauge).
Not directly, you would need to transform 480v circuit to 120v with a transformer first.
Sounds like a 240 volt sub panel feeding a well pump.
At 80% load factor you can support 60 fixtures.
A gas stove needs no high current. A basic 15amp circuit will suffice. Code will probably require a 20amp circuit since its in the kitchen.
It is not advisable to run a 20 amp circuit 150 feet without understanding the specific electrical load requirements and potential voltage drop over distance. It's important to consult with a licensed electrician to ensure the safe and efficient operation of the circuit over that distance.
You either have a short in the electric motor, wiring or another electrical device drawing more amps than the fuse can handle. Make sure the fuse is right amps as recommended by the manufacturer.
No, it is not safe to use two 20 amp circuit breakers to protect a 40 amp circuit. Circuit breakers are designed to protect the wiring in a circuit from overheating, and using a higher amperage circuit breaker than the wiring is rated for can lead to overheating and potential fire hazards. It is important to use the correct size circuit breaker for the amperage rating of the circuit.
No. Receptacle is rated at 15 amps and the wire that feeds it will also rated at 15 amps. Since it will take 20 amps to trip the breaker the wire will be become overloaded. The above is true only if it is a single dedicated outlet. You can use 15A duplex outlets on a 20A circuit, ie: kitchen and dining room outlets per the National Electrical Code.
ITS SHOULN'T BE JUST A FUSE IT SHOULD HAVE A CIRCUIT BREAKER TOO. THE CIRCUIT BREAKER OPENS IF YOU HOLD THE SWITCH TOO LONG. ITS 20AMP ON MOST CARS THAT I WORKED ON. ITS IN THE FUSEPANEL ON MUSTANGS. GOOD LUCK PAUL G
I don't understand the question, but if you want to make the line into a 20amp instead of 15amp, you just install a 20amp breaker, but remember,the wire must be 12ga wire to be connected to a 20amp breaker.
Have an electrician wire you a proper line for the appliance. You were just kidding about the 100A, right? 10, or 20amp, not 100.
The main fuse panel is at the left end of the dash and there's a fuse/relay box under the hood above the left front wheel well. Check both panel covers. The outlets are on a 20amp circuit, so if you don't find any labels, check all the 20amp fuses for a blown one.