answersLogoWhite

0

This is per the NEC Handbook, 2005 edition. Your municipality may use different rules. I am not an electrician.

Per Table 5, chapter 9:

Approximate area of 14 ga. THWN is 0.0097 sq. in.

Approximate area of 6 ga. THWN is 0.0507 sq. in.

0.0097 * 3 = 0.0291

0.0507 * 4 = 0.2028

...total area 0.2319 sq. in.

Per table 1 chapter 9, you are allowed 40% fill for more than two wires in EMT. So, 0.2319 / 0.4 = 5.7975 sq. in. minimum conduit area, which means you'd have to use 2-1/2 inch trade size EMT, which is 5.858 sq. in.

Hope this helps.

User Avatar

Wiki User

18y ago

What else can I help you with?

Related Questions

What is the smallest size emt conduit that can be used with nineteen 10 gauge thwn wires?

1 1/2 inch


What size conduit is correct for 10-3 gauge wire?

You can pull 10 #3 gauge wires in a 2 1/2" conduit.


How many12 gauge wires can you use in a 1 inch conduit?

The NEC allows 26.


What information can be found in the wires in conduit chart?

The wires in conduit chart provides information on the types and sizes of wires that can be safely installed in different types of conduit. It includes details on wire gauge, insulation type, and maximum current-carrying capacity for each wire size.


How many 12/2 wires can fit in a 3/4 conduit?

In a 3/4 conduit, you can fit up to three 12/2 wires.


How many number 12 wire is can you fit in a three-quarter inch conduit?

The number of 12-gauge wires that can fit in a three-quarter inch conduit depends on the type of conduit and the specific application. Generally, for a three-quarter inch EMT conduit, you can fit about 9 to 10 number 12 wires, following the National Electrical Code (NEC) guidelines for conduit fill. It's essential to consider derating factors and any additional requirements based on the installation conditions. Always consult the NEC or a qualified electrician for precise calculations.


How many wires are typically accommodated in a PVC conduit according to the "How Many Wires in PVC Conduit" chart?

The "How Many Wires in PVC Conduit" chart typically accommodates up to 9 wires in a PVC conduit.


How many number 12 wires can fit in a three quarter inch conduit?

10


What information can I find in the conduit size chart for wire?

A conduit size chart for wire provides information on the recommended conduit size based on the wire gauge and the number of wires being used. It helps in determining the appropriate conduit size for safe and efficient wire installation.


What size of conduit do you need for 3-6 gage thwn wires?

To determine the appropriate conduit size for 3 to 6 gauge THWN wires, you can refer to the National Electrical Code (NEC) conduit fill tables. Generally, for one to three conductors of these sizes, a 1-inch conduit is often sufficient. However, if you plan to run multiple conductors or if the installation has specific conditions, it's best to consult the NEC tables or a local electrician for precise calculations. Always ensure to account for any bends and fittings that can affect conduit fill.


What information can be found in the conduit wire chart?

A conduit wire chart provides information on the types and sizes of wires that can be used in different conduit systems. It includes details such as wire gauge, insulation type, and maximum current capacity for each wire size.


What is the maximum number of six gauge wires that can be installed in one inch flex conduit?

The maximum number of six gauge wires that can be installed in one inch flexible conduit is typically determined by the National Electrical Code (NEC) fill tables. For six gauge wire, the NEC allows for a maximum of 3 conductors in a one-inch conduit, assuming they are all the same type and insulation. However, this number can vary based on factors such as the type of insulation and the presence of additional conductors. Always consult local codes and regulations for specific requirements.