Do you have a dual capacitor that starts both the compressor and the fan motor? You need 230V to power the compressor. You should have one wire from the capacitor going from the start terminal on the compressor and one going from the common terminal to common on the capacitor.
The compressor needs 230V to start so 120 will not work.
Your contactor in the outdoor unit is stuck closed.
There are three main parts to an air conditioning unit. You could have a bad capacitor. AC units have fairly large capacitors that are required for the motor to start. That is the most likely point of failure. Otherwise, your compressor could have gone bad. Lastly, your fan motor could have gone bad.
First make sure power is off...there is three leads that supply power to compressor...they should be Yellow Black and Red....make a diagram where these leads connect on your unit and then disconnect them...You will need a multi meter to check ohms of resistance...Yellow is usually the common lead...attach one meter lead to it...now touch other meter lead to black lead...should read somewhere between 1 to 4 ohms...now touch the meter lead to the red wire...should read somewhere between 3 to 7 ohms...next read from yellow lead to side of compressor...if you get any reading then compressor is grounded and needs to be replaced...if you get no reading there, reconnect lead and see if compressor will run...if it will not then if could be possible capacitor is bad...on some units they have start assist capacitors this could be bad also..replace these and see if compressor runs...if it will not run it will need to be replaced..if it does run use an amp meter and check load amps of compressor...
It is possible that the power surge/outage damaged the capacitor of the air conditioning unit. If when the A/C is turned on, and the fan on the outdoor unit (usually located at the top of the case) is not turning, or is turning very slowly and/or sporadically, it's the capacitor.
The outdoor lamp manufacturer would be able to tell you that... all outdoor lamps are different.
Check to see if the capacitor is good. It is usually located inside the outdoor unit. It could be that the capacitor is bad and needs replacing. The outdoor fan will still run if you have a dual capacitor. One sure sign of a blown capacitor is that the top of the capacitor is bowed outward. If you have a multimeter you could also check the amp draw on the condensing unit. I would look at the capacitor first though
Check your outside unit. Is the fan blowing? If not replace outdoor fan motor or the fan capacitor. If the fan is running then the compressor may not be. Usually a quick fix by replacing the capacitor. In most units a dual capacitor that is bad may shut down the fan or compressor. Call a HVAC technician to replace it. This can be very dangerous.
CondenSER is correct. CondenSOR is not a real word. Regards!
Does the outdoor fan come on? If it does not, then the fan motor or the capacitor is bad. Does the outdoor coil get hot? How loud is the hum? If the Condenser fan(outside Fan) is running and the condensor is not obstructed by debris or some other object, I would suspect rotor lock. This can be caused by high head pressure. A common cause of high head pressure would be a bad equalizer/unloader valve. This valve is responsible for bleeding the high pressure down during the compressor rest period between cooling cycles. Of course the worst scenario of all would be a siezed compressor. One way to test for a failed unloader or equalizer valve would be to shut the unit off for at least an hour and then restart. If it does restart odds are the valve is bad and not the compressor.
It could be off on a low pressure switch. You need to check if you have 24 volts to the outdoor unit at the contactor coil. If the contactor is not working the outdoor unit will get no high voltage to the compressor or fan. It could also be that the capacitor for the fan and compressor is blown.
Yes a compressor will run the entire heating and cooling cycle, unless its in emergency heat in which case you will not have compressor operation. Defrost cycle is the AC mode except the outdoor fan is de energized to assist in the defrosting of the outdoor coil.
Absolutely NOT ! you will end up with more problems,and spend more redoing it because it doesn't work together.And besides a 4 ton compressor needs a 4 ton condensor.3 ton condensor will not have the surface area to cool the freon from a hot vapor to a cool liquid,that is needed for optimal performance in air handler,which is also rated for a 4 ton ,due to the coil size and the expansion valve size.
It could be that the outdoor fan is not turning causing the compressor to overheat and shut down on overload or your outdoor unit may need to be hosed off. You could have a faulty run capacitor. If you do need a new compressor you have to consider the age of your unit, the need to replace the indoor unit, and your financial situation. The cost of a compressor is over 500.00 in my area, then you have the labor, refrigerant recovery, and misc charges. It could bring the total of the job to 1000.00. Complete change out could run between 5000 and 8000 depending on size of equipment and geographical locale.
Either mounted to the fan or in the electrical compartment on the outdoor unit.
Probably not a bad run capacitor since the compressor gets real hot. It also may have a bad run capacitor. Same thing happened to me. It eventually would not come on at all. Shot, unfortunately, so I replaced the whole outside unit. ==Answer 4 == One of 3 problems, you are low on refrigerant, the condenser coil is dirty, or the outdoor fan is not working. The reason it shuts down is the compressor has an overload sensor that is opening and shutting the compressor down. You need to figure out which one of these is happening. No one has mentioned the possibility of a "locked rotor" within the compressor.j3h.
Refrigerant is pumped by a compressor located in the out door section called the condensor to a evaporator coil as a liquid through a metering device.Your air handler or furnace blows air from your home across the evaporator where the liquid refrigerant expands into a gas and picks up the heat from the air across the coil.Then the gas is pumped to the condensor and is again condensed into a liquid through the means of cooling the gas usually by a fan pulling air across the coils of the outdoor unit.
Check the filter first -Improvement- The filter would only equate to less air flow through the vents. Here are some suggestions. -When you turn your thermostat to cooling, does the fan on the outdoor compressor kick on? If not, you need to check the capacitor in your unit. Also, check the fuses to the disconnect. If yes; -Check the refrigerant charge to your compressor. If you don't know how to do this, call a licensed HVAC technician.