Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
A 220V hot water heater typically requires a double-pole breaker rated at 20-30 amps, depending on the specific power requirements of the water heater. Make sure to consult the manufacturer's specifications or a qualified electrician to determine the appropriate breaker size for your specific unit.
The formula you are looking for is I = W/E, Amps = Watts/Volts. Amps = 5000/230 =21.7 amps. The wire size to run this heater would be a #10 copper conductor. The supply breaker would be a two pole 30 amp breaker.
The breaker size for a 10 KVA electric heater would depend on the voltage it operates at. For example, for a 240V heater, you would need a 41.67 Amp breaker (10,000 VA / 240V = 41.67 A). It is important to consult with a licensed electrician to ensure the correct breaker size and electrical setup for your specific heater.
A 400 watt heater can safely be used on a 15 amp circuit. The size breaker needed for a circuit is determined by the size of the wiring in that circuit. AWG #14 wire requires a 15 amp breaker. AWG # 12 wire requires a 20 amp breaker.
To answer this question the voltage of the immersion heater is needed. I = W/E.
Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
A 220V hot water heater typically requires a double-pole breaker rated at 20-30 amps, depending on the specific power requirements of the water heater. Make sure to consult the manufacturer's specifications or a qualified electrician to determine the appropriate breaker size for your specific unit.
The formula you are looking for is I = W/E, Amps = Watts/Volts. Amps = 5000/230 =21.7 amps. The wire size to run this heater would be a #10 copper conductor. The supply breaker would be a two pole 30 amp breaker.
The maximum current rating for the circuit breaker needed for a device that operates at 20 amps is 25 amps.
The breaker size for a 10 KVA electric heater would depend on the voltage it operates at. For example, for a 240V heater, you would need a 41.67 Amp breaker (10,000 VA / 240V = 41.67 A). It is important to consult with a licensed electrician to ensure the correct breaker size and electrical setup for your specific heater.
A 400 watt heater can safely be used on a 15 amp circuit. The size breaker needed for a circuit is determined by the size of the wiring in that circuit. AWG #14 wire requires a 15 amp breaker. AWG # 12 wire requires a 20 amp breaker.
For a 240-volt circuit that requires a 50 amp breaker, the appropriate size of the breaker needed is 50 amps.
Yes, a 30 amp double pole breaker would be suitable for a 4800 watt wall heater. Since watts equals volts multiplied by amps, this wall heater on a 240-volt circuit would draw 20 amps (4800 watts/240 volts), which is less than the 30 amp capacity of the breaker.
A 15000 watt 240 volt heater would require a 62.5 amp circuit breaker. To accommodate this exact load, you would typically use the next standard breaker size above 62.5 amps, which is a 70 amp breaker to ensure safety and proper operation of the heater.
Each baseboard heater will draw a little over 4 amps at 120 volts or 2 Amps at 240 volts. The total number of baseboards on a circuit will draw the sum of these amps. Keep the load under 80% of the amperage rating of the breaker.
A double breaker is a breaker that has 2 switches on it. One of the switches is 20 amps and the other is 30 amps.