Yes, this is done on star (wye) systems where one neutral is used for three phase wires. e.g. 120/208 voltage system.

User Avatar

Wiki User

15y ago

What else can I help you with?

Continue Learning about Natural Sciences

What is an electric shared neutral?

An electric shared neutral is the white or negative wire that is shared between two electrical circuits on a basic single phase system. Most electrical devices use 120 volts and require a "hot" wire and a neutral wire to operate. Some larger devices use 240 volts and require two "hot" wires to operate. Two circuit breakers in an electrical panel can share one neutral wire as long as the breakers are not on the same "leg" of power. When looking at an electrical panel there are usually two "legs" of power feeding all the breakers, each leg has 120 Volts to ground, if the "legs" are combined you will have 240 Volts. A neutral wire can be shared by two circuits as long as the breakers are on separate "legs". If someone needed to add two circuits in their home, the could run what is called a 3-wire romex, It has a black wire, a red wire, a white wire and a ground wire. The white wire is the neutral for both the black and red 120 volt circuits, and the breakers for the new circuits would need to be on separate "legs" in the panel.


How many electrons are in one neutral h?

One neutral hydrogen atom contains one electron.


Do you have to pin breakers together when sharing the neutral on branch circuits?

Pinning breakers is becoming a thing of the past. This is due to the manufacturing of two pole breakers with one common trip reset handle. The electrical code states that on a 240 volt breaker if one leg trips the other leg must be disconnected from the supply also. This is a safety factor so that if they weren't tied together and one leg tripped the other half of the breaker would remain "hot". Any one working on that circuit in the tripped position could get a nasty shock from the un-tripped leg. Pinning the breakers on 240 volts was done because it was convenient to use single pole breakers in the distribution panel. To abide by the code the two single pole breakers were common tied together. When the branch circuits share a neutral to a common box they have to be common tied for the same reason above. This type of circuit is found on kitchen counter receptacles. Two separate circuits that share a neutral and go to separate junction boxes do not need the breakers tied.


Ground wire share?

That's not much of a question but I think you mean "how or why do you share a neutral?" A neutral is sometimes called a "grounded conductor" because it is connected to the main ground at the point of entry of a home or building. But it is not the "ground". You typically have 4 main conductors at the point of entry of your home or other building. 2 are "hot" wires, 1 is the neutral(these three come from the utility provider) the last one is the ground wire(s) usually coming from ground rods pounded into the earth outside (sometimes there is also a conductor connected to the copper water pipe where it comes into the home or to a rebar encased in the concrete foundation of the building)(these are all considered the "grounding electrode conductor" or ground) the neutral and ground are connected at one point only usually in your panel but sometimes in the meter-base. there is approx. 240 volts potential between the two "hot" wires. Both wires are approx. 120 volts each to the neutral. each "hot" wire is also known as a "phase". If you could see the electrical panel with no breakers in it you would notice that one "hot" wire (or phase) feeds half of the breaker spaces and the other "hot" wire feeds the other half but the panel is not split up as it might look (left and right halves). Each phase feeds every other space vertically. So the top two breakers would be fed from "A phase" then the second two by "B phase" and so on down the panel. (this allows a double wide or 2-pole breaker to span both phases and feed 240 volts to your electric range or dryer). Now to your question: Due to the way Alternating Current (AC) is generated, the two phases are polar opposites of each other. When "a-phase" is at it's peak, "b-phase" is at it's lowest point. The neutral corresponding to it's phase conductor follows this pattern. As long as the two circuits are on opposite phases, those two circuits can share one neutral conductor with no overloading problems. If you share one neutral with two circuits from the same phase, you will over-load that neutral and it could create enough heat to potentially cause a fire. There is no over-load protection connected directly to the neutral. Electricians share neutrals for a few reasons. It eliminates wiring costs and also reduces the number of conductors in conduits. You will have problems if you try to share a neutral on circuits requiring GFCI or Arc Fault protection. It causes nuisance tripping and major headaches for all. Sharing neutrals has been a common practice for years. In three-phase systems(common in commercail and industrial buildings), three circuits can share one neutral as they are 120 degrees from each other.(picture a round generator of 360 degrees total).


Can you put 2 circuits on one neutral in a single phase house panel?

you can, but i would not recommend it, I've seen it done many times in older homes, if for some reason you do make sure both circuit power"hot" wires are connected to the same bus of electrical panel or a backfeed could cause a high voltage and be even more hazardous

Related Questions

Can one neutral share two phases?

Yes, they can share a neutral


How many neutrals for three-phase multi circiuts?

For a three phase distribution system there is one neutral. In North America the electrical code allows three individual branch circuits to connect with one neutral as long as the three circuits each use an individual phase leg. This differs from 120/240 volt single phase wiring where only two legs can be used with one neutral.


Can you use a GFCI on an unswitched circuit line red that uses the same neutral white for a switched circuit coming from the other phase line black in a 240v breaker panel?

Yes. You are allowed to use a neutral for one circuit from each phase of your service. For example, in a residential service, you can use the same neutral for circuits 1 and 3. In a commercial (3 phase) service, you can use a neutral for circuits 1, 3, and 5. You will experience problems if you use a neutral for two 'black' circuits or two 'red' circuits, if the circuits originate from the same phase bus bar. Also, AFCI's are sensitive to sharing neutrals, but GFCI's are not.


What is an electric shared neutral?

An electric shared neutral is the white or negative wire that is shared between two electrical circuits on a basic single phase system. Most electrical devices use 120 volts and require a "hot" wire and a neutral wire to operate. Some larger devices use 240 volts and require two "hot" wires to operate. Two circuit breakers in an electrical panel can share one neutral wire as long as the breakers are not on the same "leg" of power. When looking at an electrical panel there are usually two "legs" of power feeding all the breakers, each leg has 120 Volts to ground, if the "legs" are combined you will have 240 Volts. A neutral wire can be shared by two circuits as long as the breakers are on separate "legs". If someone needed to add two circuits in their home, the could run what is called a 3-wire romex, It has a black wire, a red wire, a white wire and a ground wire. The white wire is the neutral for both the black and red 120 volt circuits, and the breakers for the new circuits would need to be on separate "legs" in the panel.


What is meaning for TPN isolator and SPN isolator?

TPN (Triple Pole and Neutral) isolator is an electrical switch used to disconnect three-phase electrical circuits, ensuring that all three phases and the neutral are isolated for safety during maintenance or servicing. SPN (Single Pole and Neutral) isolator, on the other hand, is used for single-phase circuits, allowing isolation of the live wire and the neutral wire. Both types of isolators are crucial for ensuring safety by preventing accidental energization of circuits during work.


How is it wired or terminated to a phase if all circuits are on the same phase or hot legit would be limited to one neutral?

The question makes no sense.


How many electrons are in one neutral h?

One neutral hydrogen atom contains one electron.


Do you have to pin breakers together when sharing the neutral on branch circuits?

Pinning breakers is becoming a thing of the past. This is due to the manufacturing of two pole breakers with one common trip reset handle. The electrical code states that on a 240 volt breaker if one leg trips the other leg must be disconnected from the supply also. This is a safety factor so that if they weren't tied together and one leg tripped the other half of the breaker would remain "hot". Any one working on that circuit in the tripped position could get a nasty shock from the un-tripped leg. Pinning the breakers on 240 volts was done because it was convenient to use single pole breakers in the distribution panel. To abide by the code the two single pole breakers were common tied together. When the branch circuits share a neutral to a common box they have to be common tied for the same reason above. This type of circuit is found on kitchen counter receptacles. Two separate circuits that share a neutral and go to separate junction boxes do not need the breakers tied.


Where can one purchase flexible printed circuits?

Flexible printed circuits are used for assembling electronic circuits. You can purchase these from many companies such as Flexible Circuit, All Flex Inc and Strataflex.


Can 2 220 circuits share one ground?

Yes they should, since there is only one earth, no seriously all earths in a ac system should be joined together.


Is a 3 phase cable one circuit?

If it is powering a single 3 phase device and is protected by a single throw 3 pole breaker or disconnect, yes. If all three hots share one neutral, and supply different devices or circuits, breakers should be able to trip independently but would still have to disconnect all three phases together.


Ground wire share?

That's not much of a question but I think you mean "how or why do you share a neutral?" A neutral is sometimes called a "grounded conductor" because it is connected to the main ground at the point of entry of a home or building. But it is not the "ground". You typically have 4 main conductors at the point of entry of your home or other building. 2 are "hot" wires, 1 is the neutral(these three come from the utility provider) the last one is the ground wire(s) usually coming from ground rods pounded into the earth outside (sometimes there is also a conductor connected to the copper water pipe where it comes into the home or to a rebar encased in the concrete foundation of the building)(these are all considered the "grounding electrode conductor" or ground) the neutral and ground are connected at one point only usually in your panel but sometimes in the meter-base. there is approx. 240 volts potential between the two "hot" wires. Both wires are approx. 120 volts each to the neutral. each "hot" wire is also known as a "phase". If you could see the electrical panel with no breakers in it you would notice that one "hot" wire (or phase) feeds half of the breaker spaces and the other "hot" wire feeds the other half but the panel is not split up as it might look (left and right halves). Each phase feeds every other space vertically. So the top two breakers would be fed from "A phase" then the second two by "B phase" and so on down the panel. (this allows a double wide or 2-pole breaker to span both phases and feed 240 volts to your electric range or dryer). Now to your question: Due to the way Alternating Current (AC) is generated, the two phases are polar opposites of each other. When "a-phase" is at it's peak, "b-phase" is at it's lowest point. The neutral corresponding to it's phase conductor follows this pattern. As long as the two circuits are on opposite phases, those two circuits can share one neutral conductor with no overloading problems. If you share one neutral with two circuits from the same phase, you will over-load that neutral and it could create enough heat to potentially cause a fire. There is no over-load protection connected directly to the neutral. Electricians share neutrals for a few reasons. It eliminates wiring costs and also reduces the number of conductors in conduits. You will have problems if you try to share a neutral on circuits requiring GFCI or Arc Fault protection. It causes nuisance tripping and major headaches for all. Sharing neutrals has been a common practice for years. In three-phase systems(common in commercail and industrial buildings), three circuits can share one neutral as they are 120 degrees from each other.(picture a round generator of 360 degrees total).