answersLogoWhite

0

Infinity is the reading when the meter is pegged at the opposite end of the scale from '0'. The symbol for infinity looks like the number 8 laying on its side.

User Avatar

Wiki User

15y ago

What else can I help you with?

Related Questions

How do you megger test a 240 1ph under ground service?

If the service is connected you can not megger the service ahead of the main breaker. If the service is waiting for connection all you can do is megger between the wires. As the underground service is installed in PVC conduit, no ground circuit will be available between the underground conductors and the PVC conduit. Connect the black lead to the neutral bar in the meter base. Connect the other lead to the L1 lead and ring it. Do the same to the L2 lead. Then disconnect the lead from the neutral bar in the meter base and connect it to L1. Connect the other lead to L2 if it is not still connected from the last operation. Ring the line between L1 and L2. If you get a reading of infinity on all three tests then the service is good for connection.


How does 1 mega ohm looks on a megger device?

On a megger device, 1 megaohm will typically be indicated on the display or dial as "1 MΩ" or "1.0 MΩ." Depending on the specific model, it may be shown as part of a range or scale that includes other resistance values. The reading will be steady if the insulation is good, and a higher reading indicates better insulation quality. If the reading fluctuates or shows a value significantly lower than 1 MΩ, it may indicate insulation problems.


How do you test an electric bell with a megger?

To better understand how to perform this test, it is important to understand what a megger test does. A megger traditionally utilizes a relatively high voltage {500vdc} to detect minute leakage current in an insulator or conductor. These "pinhole" leaks lead to current arcing and eventually an electrical short to the frame of the device. In the case of a bell, you would connect one lead to the metal frame of the bell and the other to either of the bell wires. The result of the test should be infinity or an open circuit.


What is the accepted value for megger of 500 kv Ct tested by 5 KV DC Megger?

The value of insulation resistance varies according to the type of CT and manufacturer. It is best to check with the manufacturer for acceptable values. The word 'Megger' is a registered trademark of Megger Limited. Megger Limited's product range includes insulation testers, relay testers, battery testers and many other electrical test and measurement products. Tony Wills, Applications Engineer, Megger Ltd.


How do you check a motor for a bad winding?

You need a Megger tester. With one lead attached to the winding and the other attached to the motor housing, the Megger sends a high voltage through the winding. The Megger reads the resistance, letting you know if there is a short to ground.


What is meggers?

A megger is an electrical instrument that is used to measure the resistance of insulation by applying a DC voltage to the conductor. One lead is connected to the conductor and the other lead is connected to ground. Safe insulation reading to ground should be above 2,000,000 ohms or 2 megs.


How do you connect a megger on a three phase wye - wye transformer for testing?

First you would disconnect the HO bushing connection from ground. Then you would megger low-side phase to ground.. Next you would megger high-side phase to ground.. Lastly megger high-side to low-side phase to phase. You would not megger phase to phase on each side because this is a direct connection.


How do you use megger tester?

Megger testOn the whole megger testing is non destructive. What happens is a DC voltage is applied to the device or winding under test. It is an insulation test to see is the insulation has been injured in any way to cause a short circuit when normal power is applied to it. On my megger there are 3 ranges 300V, 750V, and 1000 volts. Applying the proper voltage is essential to not damaging the device you are testing. Working voltages up to 240 volts should use the 300 range. Working voltages up to 600 volts use the 750 volt range and working voltages above 600 use the 1000 volt range. As you can see if you used the 1000 volt range on a device that had a working voltage of say 24 volts you could damage the insulation just by testing it. So meggering a device is non destructive if you use the tester as its instructions tell you to.


Distance to the moon or infinity is greater?

The distance to the moon is greater compared to an infinite distance because infinity is a theoretical concept representing an endless distance. The moon, on the other hand, is a physical celestial body with a measurable distance from Earth.


How do you megger test continuity on a basic lighting circuit city and guilds level 2?

You don't megger test continuity. You test for that with a continuity meter or ohmmeter. "Meggers", as they're often called, produce high voltages to test the integrity of a conductor's insulation.


How do you mega ohm a motor 3 phase?

The megger leads are connected in the following manner. Black lead to motor ground terminal or motor frame. The other lead to one of the phase wires. Meg that coil to ground and note the reading. Do the same with the other two motor leads and note the readings. Look at all of the three reading that you have taken. Engineers like the reading to be above 5 meg. Preferred readings about 2 meg. Motor needs looking after below 1 meg.


How do you mega a motor 3 phase?

The megger leads are connected in the following manner. Black lead to motor ground terminal or motor frame. The other lead to one of the phase wires. Meg that coil to ground and note the reading. Do the same with the other two motor leads and note the readings. Look at all of the three reading that you have taken. Engineers like the reading to be above 5 meg. Preferred readings about 2 meg. Motor needs looking after below 1 meg.