Wiki User
∙ 2009-08-16 19:16:45== == The washing machine outlet should be ground fault protected on 12-2 wire. The 30 amp dryer circuit should be on 10-3 wire with a ground. <><><> Laundry receptacle outlet for washer, 12/2 with ground yes! GFCI required if receptacle is within 6 feet of sink or duplex receptacle rather than single receptacle [but a GFCI isn't a bad idea anyway...
Dryer, 10/3 with ground and 4-wire outlet and cord set connection at dryer location! NO NEUTRAL BONDING LINK!
1) NEC requires a disconnecting means [plug and receptacle works] if equipment [dryer] is not within sight of the power source [in this case, if the panel is in the garage]
2) You were never allowed to use the ground wire to carry neutral current, so you need an insulated white or grey neutral [this means three wire]
3] You are not longer allowed to use the neutral jumper at the terminal in the dryer for a chassis ground [with certain limited exceptions - existing ungrounded three wire cable and new dryer] Ground wire goes to chassis. <><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
Wiki User
∙ 2009-08-16 19:16:45Should be fine as long as you use a GFIC receptacle and mount at the proper height. You need to contact your local code enforcement people. Normally each locality has their own requirements to be followed.
The is no height stated in the CEC as to height of receptacles. If the basement walls are studded out, then install the receptacles at the normal 300 mm above the floor.
Epithelial tissue are closely connected and have a basal membrane, even though not all epithelial cells are necessarily connected to the basal membrane. The so called simple epithelial tissue subgroup does.
maybe you have the hot and the neutral switched...
To meet the requirements of the electrical code you have to know the total wattage of the lights that you are going to connect to the 15 amp circuit.
Yes, there is no reason why this can not be done. In fact a benefit of this is that every receptacle downstream from this new receptacle will also be protected by the GFCI receptacle.
In older constructed fire places, the trap door led to a receptacle under the floor, accessible from the basement, into which you could sweep the ashes. Then you emptied the receptacle in the basement after the ashes had sufficient time to cool. Before you attempt to sweep ashes into the trap door, be sure there is a proper receptacle in place to catch them.
Should be fine as long as you use a GFIC receptacle and mount at the proper height. You need to contact your local code enforcement people. Normally each locality has their own requirements to be followed.
As long as you have a cable in the basement to plug the modem into (phone line or cable line (coaxial) usually) and a power receptacle a modem will work anywhere.
A bAsement membrane
The is no height stated in the CEC as to height of receptacles. If the basement walls are studded out, then install the receptacles at the normal 300 mm above the floor.
Parallel connect the new receptacle to a receptacle in the existing circuit. Black (hot) existing to black (new), white existing to white (new), ground existing to ground (new). Make the ground wire coming into the new receptacle box longer so that it can be looped around the ground screw located in the receptacle box first and then connect to the receptacle without having a break in the wire.
Installing a steam shower in the basement is not a good idea. The steam shower should be installed in the nbathroom of your home.
Not if it is all connected properly - have it fitted professionally.
pseudostratified.
If it has never worked properly, you probably have somehow connected it improperly. Contact a local electrician or qualified handyman to help wire the heater properly.
No, if the gutters were not installed correctly.