The difference is the difference in the size of service entrance conductor and maximum ampacity of the service equipment [panel].
The panel will be labeled and the main breaker, if there is one, will say 100 on the operating handle.
It is unlikely you will find a sixty amp service unless it has fuses [probably with pull-outs] and cloth service cable [it will be very old]. Many of these old fuse services may be 100 amps.
<><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
I don't know anything about Minneapolis except that it's cold, but anything under 100 Amps is normally inadequate for an average home. Therefore, the service you mention is the bare minimum required for a home of less than 2,000 sf leaving little room for future consumption and the possibility of costs for upgrading to a larger service.
If a 100 amp breaker keeps tripping there is an overload on the system.
For a 100A subpanel, a minimum of 1.5-inch Schedule 80 PVC conduit or 1.25-inch rigid metal conduit is recommended. As for the aluminum wire, for a 100A feeder, you would typically use 1/0 AWG aluminum wire for a 3-wire setup or 2/0 AWG aluminum wire for a 4-wire setup. Always consult local electrical codes and a licensed electrician for precise specifications for your installation.
No, you should not load a panel beyond its rated capacity. In this case, a 30A load per phase in a 100A panel would exceed its capacity and could cause overheating or other safety hazards. It's important to properly size the panel based on the expected load requirements.
I doubt if the 125 amp breaker will fit into a 100 amp box. This is due to the rating of the box only being rated at 100 amps. If this exchange could be made then the service conductors feeding the box must be upgraded to take the 125 amperage that the breaker will allow on the conductor.
The recommended wire size for a 100A service is typically 2 AWG copper or 1/0 AWG aluminum.
Have an electrician wire you a proper line for the appliance. You were just kidding about the 100A, right? 10, or 20amp, not 100.
this is pipe size dn100 ( Diametre Nominal 100) =100A
In my experience it is best to upgrade to an 200 amp service. The cost difference is minimal and is a selling point for the future. This includes replacing the service cable and Meter Box.
No because 100a-35 is an algebraic expression containing two terms.
As many as you want without exceeding the 100amps. You could have 100 circuits if all you have is a single 100watt light on each circuit.
Mossberg
It is 100A hundredths.
The Electric Company - 1971 100A 5-100 was released on: USA: 5 March 1976
The recommended wire size for a 100A subpanel installation is typically 3 AWG copper or 1 AWG aluminum.
The recommended wire size for a 100A electrical circuit is typically 3 AWG copper or 1 AWG aluminum.
I just removed a ALT 100A fuse in my buddy's Toyota Corolla from 93'. I had to disasemble the hole fusebox in the engineroom, to take the fuses out from beneath it. They are boltet on, (search google: "ALT 100A" first article). Hope this was helpfull. Rasmus DK.