277 V is dangerous, but not much more so than 120 V or 240 V that you see in the familiar split phase household electrical system.
Any voltage potential that is high enough to cause a lethal current to pass through your body is hazardous. This is usually anything above 50 V (assuming the line to line or line to earth connection points on the body are at areas where skin is intact and dry).
Higher voltages do have inherently more power because power = voltage x current. Even if the current was the same you'd get worse burns at higher voltages, but usually the current increases too because the skin's resistant would be constant (V = IR).
Remember, it's electrical current that actually hurts you, but voltage is needed to cause current to flow. Voltage ITSELF isn't inherently hazardous. If you wear insulated boots and touch a live wire your body will rise to the voltage potential of the wire but nothing will happen until you touch something else, like an earthing point or another live conductor that is out of phase with the first one (DON'T try this... you could be touching something and not realize it, or if the voltage is high enough it could ARC to earth to complete the circuit)... then there's a potential DIFFERENCE across your body and potentially lethal current can flow if that difference is big enough.
In a 277-volt circuit, if you measure the voltage from Phase 1 to ground, you should read approximately 277 volts. This is because 277 volts is typically the line-to-ground voltage in a three-phase system where the phase voltage is 480 volts. Therefore, when measuring from the phase conductor to ground, the voltage remains the same at 277 volts.
No, 277 volts is the line to neutral of a 480 volt wye three phase system. L1- N, L2 - N and L3 - N will give you 277 volts. L1 to L2. L2 to L3 and L3 to L1 will give you 480 volts.
In WYE 480 VAC each leg to neutral is equal to 277 volts. 480 / 1.73 (sq root of 3) = 277.
To read 277 volts on a meter, simply ensure the meter is set to the appropriate voltage scale (typically AC). Then, connect the meter leads to the circuit or outlet you are measuring. The display should show the voltage reading, which in this case would be 277 volts. Be sure to take appropriate safety precautions when working with electricity.
Most transformers designed to step down from 480 volts to 277 volts typically can be configured to also provide a 240-volt output. However, this depends on the transformer's design and tap settings. It's essential to consult the transformer's specifications or a qualified electrician to confirm its capabilities for specific voltage outputs.
From a three phase four wire distribution system the voltages would be as follows. From L1 to N - 277 volts. From L2 to N - 277 volts. From L3 to N - 277 volts. From L1 to L2 - 480 volts. From L2 to L3 - 480 volts. From L3 to L1 -480 volts.
In a 277-volt circuit, if you measure the voltage from Phase 1 to ground, you should read approximately 277 volts. This is because 277 volts is typically the line-to-ground voltage in a three-phase system where the phase voltage is 480 volts. Therefore, when measuring from the phase conductor to ground, the voltage remains the same at 277 volts.
No, 277 volts is the line to neutral of a 480 volt wye three phase system. L1- N, L2 - N and L3 - N will give you 277 volts. L1 to L2. L2 to L3 and L3 to L1 will give you 480 volts.
Commercial lighting. In a facility where 3 phase 480 volts is needed for machinery, 277 is also readily available because each leg of 480 to ground is 277 volts. This way numerous supply transformers are not needed in a commercial building.
Not unless it is rated for that voltage. You can likely find a step down transformer from 277 volt sto 120 volts.
In WYE 480 VAC each leg to neutral is equal to 277 volts. 480 / 1.73 (sq root of 3) = 277.
The voltage of 277 is the wye connection of a 480 volt three phase supply. The only way to reduce 277 to 120 volts is with a step down transformer.
The star point or wye voltage of a 480 volt three phase four wire system is 277 volts. The 480 voltage is divided by the sq root of 3 (for 3 phases). The sq root of 3 is 1.73. 480 volts/1.73 = 277 volts. The same formula is used on all three phase four wire systems. 208 volts /1.73 = 120 volts, 416 volts /1.73 = 240 volts, 600 volts / 1.73 = 347 volts.
Slightly dimmly
A 277 volt lighting fixture is one that is usually used in an industrial application. The reason for this is the voltage rating. A voltage potential of 277 volts is the voltage to neutral (ground) of a three phase four wire 480 volt distribution system. 480 volts / 1.73 = 277 volts. Rather than having to add a transformer to the system to provide 120 volts for lighting, manufactures produced a ballast for fluorescent fixtures that operates on the 227 volt potential.
To read 277 volts on a meter, simply ensure the meter is set to the appropriate voltage scale (typically AC). Then, connect the meter leads to the circuit or outlet you are measuring. The display should show the voltage reading, which in this case would be 277 volts. Be sure to take appropriate safety precautions when working with electricity.
No, you will not obtain 230 volts. From a wye connected three phase 480 volt supply, 277 volts can be obtained from one phase leg and the neutral on the wye connection. 480 volts/1.73 (sq. root of 3) = 277 volts.