A ton of A/C is 844.2 watts, so 5 tons is 4222.5 watts. Design extra 10 percent for constant load for total of 4650 W. Using 240 volts at 20 amps (W = Amps x volts), on 12 AWG wire, you would get 155 feet before having a 5% voltage drop. If inrush current is 30 amps at startup, you would have 7.5 percent drop in the cable during startup. To be safe, perhaps bump up a size (10 AWG) and have 4.7 percent drop during inrush (at 155 ft), or be able to run up to 170 feet at 30A load with 5 percent drop. In any case, because normal operating current is 20 A, you should use a 30 A breaker and thus 10 AWG wire, to be on safe side. If the unit is 120 V, the distances are halved for the same amount of drop.
The size of any unit is, by definition, 1.
An electric home heater unit does not have an outdoor part like a central heating system. It functions as a standalone device and does not require an external unit to operate. The heating element inside the unit is what generates heat to warm up the surrounding space.
You can use #10 or #12 THHN stranded wire with a 20 amp breaker for the outdoor unit. A disconnect is required within sight of the outdoor unit. The wire between the outdoor and indoor unit should be 14/3 with ground or 14/4 stranded. Do not use solid or aluminum wire for either application.
No, it is not advisable to mix a heat pump condenser unit with a non-heat pump indoor unit. The two systems are designed differently and operate at different efficiencies. Mixing the components could result in poor performance and potentially damage to the system. It's best to use matching components for optimal performance.
The appropriate metric unit of capacity for a lunch in the size of a juice box is milliliters (mL).
CondenSER is correct. CondenSOR is not a real word. Regards!
The indoor unit is bigger than the outdoor unit
The thermostat(s) in your house cause (control) the unit you are referring to. It is actually called the condensor and is the part that expels the heat from inside your house to the outside.
4tons
It depends on several factors. Outside tempature, unit size,cooled space, insulation values etc. In my area during peak outdoor tempatures of 100-102F, 72-75F is optimal but expensive.
Most all large chillers are water cooled. due to the increased efficiency, ease of maintenance and outdoor space savings.
It is a 4 ton Condensing Unit
why is it important to have drainage for the outdoor unit
why is it important to have drainage for the outdoor unit
Refrigerant is pumped by a compressor located in the out door section called the condensor to a evaporator coil as a liquid through a metering device.Your air handler or furnace blows air from your home across the evaporator where the liquid refrigerant expands into a gas and picks up the heat from the air across the coil.Then the gas is pumped to the condensor and is again condensed into a liquid through the means of cooling the gas usually by a fan pulling air across the coils of the outdoor unit.
This is a 10 SEER 3 ton 230v a/c condensor unit.
Only 1 radiator Unit in front is most likely the condensor for the a/c