answersLogoWhite

0

In case of a fault (short) the device could still be energized even with the fuse blown. this means, a fuse in the neutral would never blow in a fault to ground, resulting in a very dangerous situation.

User Avatar

Wiki User

15y ago

What else can I help you with?

Continue Learning about Natural Sciences

How do you put on a four prong outlet on a roper electric dryer?

Black & Red are hot, and White is neutral. If it has no place to connect neutral connect neutral to ground.


What should you never do with a chemical?

You should never inhale, ingest, or touch a chemical without proper protection and training. It is also important to never mix chemicals unless you are certain of the reaction and have the appropriate safety measures in place.


Can a live and earth wire be joined together in a light switch?

Physically yes, but to no avail. The breaker will trip instantaneously as a short circuit will have been introduced into the circuit with this action. In all wiring the live must never be connected directly to earth. The only place where the neutral and earth are connected together is at the distribution panel where the utility's supply neutral joins the system earth on the distribution panel's neutral bus bar.


In a home circuit are the neutral and ground bare wires always connected?

They are always connected, but at one and only one place, the service entrance. For instance, if you are adding a subpanel to an existing house, the subpanel will probably come with the ground bus and the neutral bus tied together with a special bonding screw. To be legal, you must remove this screw, isolating the neutral from ground. The house's main panel still has the bonding screw or jumper in place, and remains the only place the connection is made.


Why fuse inserted in phase wire only?

The fuse is place in the live wire so that under fault conditions the supply is cut off but the equipment is still connected to the neutral wire. If both wires were fused, there would be a 50-50 chance of the one in the neutral going first, which could leave the equipment still connected to the live wire and thus a further potential danger.

Related Questions

What is use of neutral link?

In a MEN (Multiple Earth Neutral) system, the neutral wire is connected to the earth wire at the switchboard. This is the neutral link. From an electrical point of view the neutral pin and the earth pin in a power socket are at the same potential but from a safety point of view they are different. A residual current device (RCD) (or earth leakage core-balance-relay(ELCBR)) sits in series with both the active and the neutral feed and a leakage from either wire to ground (via a human or water leak in a washing machine etc) will trip the circuit breaker that is in the RCD.Another AnswerFuses or circuit breakers must be inserted into the line conductor, never into the neutral conductor. However, if we need to isolate the circuit, we must place a break in both the line and the neutral conductors. We can achieve this for the line conductor by, for example, removing the fuse. To achieve the same with the neutral conductor, we can open the neutral link, which is simply a short length of conductor inserted between a pair of terminals in the neutral.


Why am I getting 120 volts from bare wire ground in electrical panel box?

Answer for Canada, USA and countries running a 60 Hz, 120/240 volt, split supply service.If the ground wire is connected it is impossible to have a 120 volt potential to ground on it.I think that maybe you are taking the reading using a 120 volt supply from a breaker on one lead of the tester and touching the other lead to the ground wire. If this is the scenario you will get a 120 volt reading. The same reading you would get by leaving the one lead on the 120 volt supply and touching the other lead to the neutral wire.The reason is because the ground and neutral wire have the same impedance or resistance between each other and it should be equal to zero. This continuity is obtained because of the ground bonding screw in the main distribution panelboard. The neutral bus is bonded to the panelboard enclosure. The ground bus is also bonded to the enclosure giving continuity between the two conductors.Electricians use this to an advantage when looking for open neutrals in a circuit. If at a receptacle that does not work he will test for a voltage from the "hot" conductor to the ground wire and read 120 volts. Then another reading from the "hot" conductor to the neutral conductor. If there is no voltage between the "hot" conductor and neutral then, the neutral is open back to the distribution source.Knowing this, never ever use a ground conductor in place of a insulated conductor if you are ever short a wire in a two cable system. Always pull in a new three wire cable. Running current on a bare conductor can be very dangerous and could electrocute someone under certain circumstances.


Whether it is possible to transmit electrcity from one place to another place with out any conductor?

Yes, it is possible to transmit electricity from one place to another place with out any conductor , just like wireless.


Why should you never place food on the floor of an oven?

Heat rises


What is the role of a neutral wire?

The real purpose of neutral is grounding. In order for electricity to flow you need a direct continuous link from the supply to a ground. Without the neutral electricity wouldn't be able to flow because it wouldn't have a ground (a place to go). The real name for neutral is the grounded conductor, and what is commonly referred to as ground is really the grounding conductor. The grounding conductor exists for the sole purpose of being a back up neutral in case something happens, this way you don't BECOME the ground if you touch it. But don't think that means you can go touching wires if you don't know what your doing cause you can still get hurt even with both grounded and grounding hooked up.


Why dont you use earth wire place of neutral?

Earth is neutral, but only at the distribution panel and upstream from it. Downstream of the distribution panel, earth and neutral shall not interchange or cross connect their connections or their roles - earth is protective ground - and neutral the current carrying return conductor.


Can you crimp copper grounding electrode to aluminum neutral of service entrance?

You should not have to crimp the copper grounding electrical wire to the aluminium service neutral. There is only one place where these two wires should meet. In the service distribution panel there is a neutral block where the two wires are connected. There are individual terminal points in the block. Tighten the ground rod wire under one of these points and place the incoming service neutral under another point in the same block. In this same block there will be a machine screw that bonds the neutral block to the distribution panel's enclosure.


How can I test a neutral wire to ensure it is functioning properly?

To test a neutral wire, use a multimeter set to measure voltage. Place one probe on the neutral wire and the other on a ground wire or metal box. A properly functioning neutral wire should show a voltage reading close to zero. If the reading is significantly higher, there may be an issue with the neutral wire.


What will be happen if you use earthing in place of neutral in any circuit?

* * * DANGER * * * DANGER * * * DANGER * * *Do not, under any circumstances, use earth ground instead of neutral in a circuit. Besides being a violation of the US National Electrical Code, and probably the applicable electrical code for any country that has an existing neutral system in place, it constitutes a hazard because the earth ground conductor is not rated to carry operational current. It is only there to carry momentary fault current so as to trip the protective device (fuse or circuit breaker) in the distribution panel. Also, placing operational current on protective earth ground can raise the voltage on that conductor, creating the potential for an electrocution hazard.


What does neutral mean its from social studies?

Place


What if you write to a public place and never hear from them?

If you never hear from them, then you should try to contact that place another way. Phone, address, ect. If you don't want to do this, then try writing again.


I am adding a 30 amp sub panel - the problem I have is the neutral bus is full what are my options?

Best answer - If panel can accept, add an additional bus on the other side and bond the two together. Least desirable answer - split bolt the neutral to one of the existing. Under no circumstances should you place multiple wires under one terminal. <<>> The neutral wire for the sub panel will only be a #10 conductor. Neutral wires can be doubled up under a single screw in the neutral bus. Turn the main breaker off to do this installation. Double up two #14 neutrals to make room for the #10 neutral wire. There is no code rule as to how many wires can be installed under a terminal on the neutral bus. There is a code rule though about not doubling up circuit feeders under one breaker terminal.