# 15 LED STATUS PROBLEM SOLUTION

The self diagnostic test has

detected the presence of

flammable vapors.

The Intelli-Vent control is

programed to lock-out and

display this error code if the

resistance value it senses from

the FV sensor is above 70,000

ohms but remains below

1,700,000 ohms.

The Intelli-Vent control is in a

hard lock-out condition that

cannot be reset by cycling power

to the water heater. See the

instructions below for the reset

procedure.

1 Turn off power to the water heater. Carefully check

the surrounding area for any substances such as

gasoline, paint, paint thinners, or cleaners that could

emit flammable vapors. Remove anything that can

potentially emit flammable vapors from the area and

store it properly in a different location.

2 Ensure power to the water heater is turned off.

Remove the FV sensor from it's bracket on the base

ring of the water heater and disconnect both wires to

the sensor. Take a resistance reading between the

two wiring terminals of the FV sensor and note the

resistance values.

Perform this test once in the area by the water heater

and a second time outdoors after allowing the sensor

to acclimate to the outdoor atmosphere for 5

minutes.

Service Note: These resistance readings should be

taken using an ohm scale above70,000 ohms.

3 If the resistance of the FV sensor is above 70,000

ohms during the indoor test only and the resistance

reading taken in the outdoor atmosphere dropped

below 70,000 ohms. Re-check the area surrounding

the water heater for substances that could be

emitting flammable vapors. Remove any such

substances from the area and store them properly in

a different location. Repeat step 2.

4 If the resistance of the FV sensor is above 70,000

ohms during the indoor and outdoor tests - replace

the flammable vapor sensor.

5 If the resistance of the FV sensor was below 70,000

ohms during the indoor and outdoor tests and all the

steps above have been performed - replace the

Intelli-Vent™ control.

Flammable Vapors Sensed (FVS) Reset Procedure

After a flammable vapor lockout has been initiated, a manual reset must be performed to restore

operation. The following should be done by a qualified service person after the hazard has been

removed:

1 Manual reset is accomplished by first, turning off power to the water heater for 10

seconds.

2 Restore the power to the water heater.

3 Within 10 seconds of restoring power, press the two temperature adjust buttons

simultaneously until the left (green) "Vacation" LED begins to blink (approx. 5 second

delay). Once the Vacation LED begins to blink, release both buttons.

4 Again, within 10 seconds, press both temperature adjust buttons simultaneously until the

Vacation LED is on steady (approx. 5 second delay).

5 Release the two buttons, the microcomputer will clear the FVS lock-out and normal

operation will then be restored.

- edit

This reset procedure didn't work for me but I found another that did. Follow steps 1-3 above and then for step 4 push the left (cooler) and right (hotter) buttons in this order: Left Right Left Left Right Left Right Right.

User Avatar

Wiki User

8y ago

What else can I help you with?

Related Questions

How do I reset a White Rodgers thermostat?

To reset a White Rodgers thermostat, locate the reset button on the device and press it. This will restore the thermostat to its default settings.


How do I reset the electric water heater reset button?

To reset the electric water heater reset button, locate the button on the heater's control panel and press it firmly. This will reset the heater and restore its functionality.


How do you do a hard reset for Motorola a810?

To Perform a Master Reset or Master Clear:Tap (Menu)Tap SetupTap either Master Reset or Master Clear


How do you reset a RAZR?

LOOK IN SETTING FOR MASTER RESET AND MASTER CLEAR


How can I reset a White Rodgers thermostat?

To reset a White Rodgers thermostat, locate the reset button on the device and press it for a few seconds until the screen goes blank. Then release the button and wait for the thermostat to restart. You may need to reprogram your settings after the reset.


How do I perform a reset on a White-Rodgers thermostat?

To perform a reset on a White-Rodgers thermostat, locate the reset button on the device and press it for a few seconds until the screen goes blank. Release the button and wait for the thermostat to restart. This should reset the device to its default settings.


Master reset codes k850i?

reset


How do I perform a water heater reset?

To perform a water heater reset, locate the reset button on the water heater and press it. Wait for a few minutes before turning the water heater back on. If you're unsure, consult the manufacturer's manual for specific instructions.


How do I reset a White Rodgers thermostat to its default settings?

To reset a White Rodgers thermostat to its default settings, locate the reset button on the device. Press and hold the reset button for about 5 seconds until the display resets to its factory settings. This will erase any custom settings and return the thermostat to its original configuration.


Master reset code C905?

Plz asked me heard reset master code c905 mobile


How do you reset Master Code on PC1555rkz?

click the reset button


How do you reset the master pin on a foxtel box?

you cant reset it