Best Answer

Yes, a 230 volt electric motor can run on 208 volts. The horsepower will be lowered by .9 or to 90% of the nameplate rating. e.g. A 230 volt 10 HP motor will only produce 9 HP at 208 volts.

Note: If motor sees a load equal to its' rated HP it will over amp and shorten the live of the motor and/or trip out on internal overload.

User Avatar

Wiki User

11y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

12y ago

Previous answers have not included the following; 208V is normally (but not always) 3 phase. 230 V is normally (but not always) Single phase. Hooking up a single phase 230V motor to 2 legs of a 208V 3 phase service will likely cause the motor to overheat.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

You need to install an individual buck booster (transformer) on each hot feed coming out of your 208V panel to elevate your voltage output as close to 230V as you can. Price range per is about $150.00, but $450.00 is cheaper than an upgrade, especially if you have other 208v applicances in the business.

This answer is:
User Avatar

User Avatar

Wiki User

11y ago

Most motors that I see are rated for 208/230 volt. The usual tollerance is plus or minus 10%. 10% of 208 is 20.8, plus the 208 volts you say it is rated, would be 228.8 volts maximum. So you should be ok.

This answer is:
User Avatar

User Avatar

Wiki User

14y ago

Yes, IF IT IS RATED FOR 208V. Check the motor's nameplate first!!

This answer is:
User Avatar

User Avatar

Wiki User

14y ago

Yes, but you will not get the full nameplate horsepower rating from the motor at the lower voltage.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

Yes, you can run a 208 volt motor on 230 volts with no problems.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

no

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Can you hook up 208 volts on a 230 volt motor?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

What is the maximum volts that can be used on a 208 230 volt motor?

You should not go above 240 volts for that type of motor.


How many Amps for 3 horsepower at 208 volts?

For a single phase 3 HP motor at 208 volts the amperage is 18.7 amps. For a three phase 3 HP motor at 208 volts the amperage is 10.5 amps. This figure is derived at by taking the full load amps at 230 volts and adding 10%. As the voltage goes down the amperage goes up. For 200 volt motors 15% is added to the FLA of a 230 volt motor.


What is the difference between 208 volt and 220 volt power?

The main difference between the two voltages is that the 208 volts is a three phase voltage and 220 volts in North America is a single phase voltage. If you operate a 220 volt motor on 208 volts the current will be 5% higher that the motor's nameplate rating. If the load is resistive and you operate a 220 volt baseboard heater on 208 volts the true heater wattage will not be reached because of Ohm's law. Current is directly proportional to the applied voltage and inversely proportional to the resistance in the circuit. The following statement is not true as many motors will have the two voltages on the motor's nameplate. You can operate a 208 volt motor or appliance on 240 volt, but that will decrease life expectancy by 50%.


What size breaker for a 208 volt single phase motor that pulls 1.4 amps?

208 volts is not a common single phase voltage but you could just size your breaker to the capabilities of the conductor. 208 is normally a phase to phase voltage <<>> Many 230 volt motors can be connected to lower voltage supplies. These motors can be connected to supplies of 208 and 200 volts. The code requirement is that the 230 volt full load amperage of the motor be increased by 10% and 15% respectively for wire sizing and breaker selection. To answer the question you will need a two pole 15 amp breaker.


Is it possible to hook up a unit that is 208 volt single phase to a 240 volts 3 phase?

Any two legs of a three phase system are classed as single phase. If a 208 volt device is connected across two legs of a 240 volt system its current draw will be higher. It is not recommended to connect a 208 volt device to a 240 volt supply. Using a constant resistive load of 6000 watts for an example, the resistance of the unit at 208 volts has to be found. R = E (squared)/W = 7.21 ohms. Now using the formula to find amperage at this resistance I = E/R, 208/7.21 = 28.84 amp at 208 volts. If the 208 volt device is connected to a 240 volt supply the following condition happens. I = E/R, 240/7.21 = 33.29 amps. The device in now definitely overloaded and instead of its rated 6000 watts it is outputting W = A x V, 33.29 x 240 = 7989 watts almost 2000 watts more than the unit is rated at.Using a 240 volt rated device on 208 volts is more forgiving and is done quite often. Using the same 6000 watts on 240 volts the resistance is calculated to be R = E (squared)/W = 9.6 ohms. If the 240 volt device is connected to a 208 volt supply the following condition happens. I = E/R, 208/9.6 = 21.67 amps. To check this connection's wattage W = A x V, 21.67 x 208 = 4507 watts or about 1500 watts below its rated output at 240 volts.If the connected load is a constant wattage like a motor, the amperage and voltage will change to maintain the constant wattage. I = W/E. A motor rated at 6000 watts at 240 volts will draw 25 amps. A motor rated at 6000 watts at 208 volts will draw 28.8 amps.The CEC states that if a 208 volt rated motor is connected to a 240 volt supply its full load current has to be increased by 10 % for its overload protection.If the three phase source is delta connected, and the neutral/ground is at the center tap of one of the phase windings, then there is 208 volts available from neutral to the third phase leg. In this case, there would be no mismatch of voltage, and the 208 volt load will operate as designed.This particular configuration is not so common. It is sometimes used in a light industrial setting where a fourth transformer for the 120/240 split phase portion is not used - it provides 240 three phase delta only, 120/240 split single phase, residential style, and 208 single phase.See related links below (High Leg Delta)Note that 240 three phase loads are also not so common. In the case where 480 three phase is required in this configuration, then there is a step up transformer trio provided, ususally by the customer.

Related questions

What is the maximum volts that can be used on a 208 230 volt motor?

You should not go above 240 volts for that type of motor.


How many Amps for 3 horsepower at 208 volts?

For a single phase 3 HP motor at 208 volts the amperage is 18.7 amps. For a three phase 3 HP motor at 208 volts the amperage is 10.5 amps. This figure is derived at by taking the full load amps at 230 volts and adding 10%. As the voltage goes down the amperage goes up. For 200 volt motors 15% is added to the FLA of a 230 volt motor.


Will 220 volt work in a high volt 3 phase motor?

Yes a 208 voltage motor will operate on 220 volts. You have to increase the motor overload protection by 10% of the motor's full load amperage to protect the motor.


Does a 208 volt outlet need a neutral?

No a 208 volt outlet does not need a neutral. 208 volts is the line voltage between any two legs of a three phase 208 volt system.


Can you operate a 208 volt on 110 volt?

The United States is one of the only places in the world that uses 110 volts instead 220 volts. In order to operate 208 volts on a 110 volt electrical current, you will need a voltage converter.


What is the difference between 208 volt and 220 volt power?

The main difference between the two voltages is that the 208 volts is a three phase voltage and 220 volts in North America is a single phase voltage. If you operate a 220 volt motor on 208 volts the current will be 5% higher that the motor's nameplate rating. If the load is resistive and you operate a 220 volt baseboard heater on 208 volts the true heater wattage will not be reached because of Ohm's law. Current is directly proportional to the applied voltage and inversely proportional to the resistance in the circuit. The following statement is not true as many motors will have the two voltages on the motor's nameplate. You can operate a 208 volt motor or appliance on 240 volt, but that will decrease life expectancy by 50%.


What size breaker for a 208 volt single phase motor that pulls 1.4 amps?

208 volts is not a common single phase voltage but you could just size your breaker to the capabilities of the conductor. 208 is normally a phase to phase voltage <<>> Many 230 volt motors can be connected to lower voltage supplies. These motors can be connected to supplies of 208 and 200 volts. The code requirement is that the 230 volt full load amperage of the motor be increased by 10% and 15% respectively for wire sizing and breaker selection. To answer the question you will need a two pole 15 amp breaker.


What is a 208 circuit?

The 208 volt configuration is one phase of a three phase source at 240 volts, where the 208 volt circuit is connected between the center tap of one 240 volt phase (usually a grounded neutral, in the style of a standard 120/240 split phase system) and the high delta connection on either of the other two phases. 208 circuit would consist of two phases of a 208 volt wye system or could be all three phases. The voltage between conductors would be 208 volts. The voltage to ground from any phase would be 120 volts. A 240 volt delta system would give you a high leg to ground, somewhere around 190 volts and the other two would be 120 volts to ground.


Why won't a 230-460 volt motor work on a 120-208 volt circuit?

Because its designed to operate at 230-460, not 120-208.


Can you use 600VOLT motor in 220VOLT supply through a transformer?

Usually with a voltage of 600 volts the motor will be three phase. To use a transformer with that motor you will need a three phase 240 volt service. These days utility companies are moving away from three phase 240 and substituting it with 120/208. The 208 three phase service has the added bonus that 120 volts can be obtained from the star point (grounded neutral).


How is it possible that a chicken rotisserie that uses 208v 3 phase can have a motor that uses 208v?

Two scenarios are that the motor could be a three phase motor. These three phase motors are manufactured in smaller sizes. The other scenario is that the motor is a 208/220 volt single phase motor. It will operate on 208 volts by taking two legs of the three phase supply for its operation.


How will a 3 phase panel give you 110 volts and 220 volts?

A three phase panel will not give you 110 and 220 volts. A three phase four wire panel will, but not at these voltages. The nearest voltages will be 120 and 208 volts. The 120 volt is the wye voltage of 208 volts. 208/1.73 = 120 volts. A single phase three wire panel will give you 110 and 220 volts.