For questions of this type, it seems the main issue may be one of definitions and industry terms. See if this makes sense:
Line voltage is a very ambiguous term. For instance, say you are wiring a doorbell transformer. You feed 120V into the primary, and 18V comes out the secondary. The electrician would say the output is "low voltage" and the input is "line voltage". He simply means the building wiring, or "lines". Now, if you go out to the breaker panel, you will measure 120V from each "leg" to neutral, but you can also measure 240V from leg to leg. It's all line voltage. Line voltage simply means the voltage present in that particular power distribution system.
Now the power in your house is "single phase" (well, in almost all homes, anyway). Single phase is fine for most anything, but motors are a special case. Motors need something to create a rotating magnetic field to get them turning. Single phase power doesn't have anything to do that, so they need some sort of a gimmick, like a capacitor, to create a "phase shift" to get the rotation.
Single phase AC (alternating current) simply means the voltage goes positive then back down to zero, then negative then back up to zero. That's one complete cycle. The cycle is divided into 360 degrees, like a circle. The positive voltage goes from 0 to 180 degrees, and the negative half 180 back to 0.
Now 3-phase power has, you guessed it, 3 hot wires. Each hot wire, when paired with a neutral, is a single-phase source. Heres the big difference: Phase A starts its positive cycle. When it is 120 degrees into the cycle, phase B starts going positive. When Phase B is 120 degrees finished with its cycle, phase C starts going positive. When phase C is 120 degrees into its cycle, that's a total of 360 degrees, and phase A is done with one cycle, and the whole process starts over. Picture 3 people doing "the wave" at a football game. Same principle.
This time difference, or "phase shift" is what makes 3-phase power unique. 3-phase motors use the phase shift directly to produce the rotating magnetic field they need to turn. Think of 3 people in a circle, tossing a ball around. see the "circular" motion? Now picture two people tossing the ball back and forth. No circular motion there. That's the difference between single-phase and 3 phase.
So, electricians use the term "phase" to refer to one of the three hot wires in a 3-phase (also correctly called multiphase or polyphase) power system. The term "phase" voltage is just as ambiguous as "line" voltage. To be accurate, you must specify whether you mean phase-to-phase voltage, or phase-to-neutral voltage.
Confused? if you go into a large commercial building with 3-phase power, many times the incoming panel will have voltmeters on the front. In one building, the first meter will be labeled "phase-to-phase voltage", and the second meter will be labeled "phase-to-neutral voltage". Go into the building NEXT DOOR, and the same meters will be labeled "line-to-line voltage" and "line-to-neutral voltage". See? the terms are used pretty interchangably.
In a 3-phase system, each phase, leg, or line has the same potential, or voltage (except for a very few wierd and pretty outdated systems). If you measure from phase A to Phase B you will get the same reading as B to C, also the same as C to A. So, measuring any two phases will tell you what the line voltage is, but that motor still needs all 3 phases to get the rotation.
To understand the different voltages you find in a 3-phase system, see the related questions for another answer that relates to that subject.
To convert line to line voltages to line to neutral voltages:
VA = [VAB - VCA] / 3
VB = [VBC - VAB] / 3
VC = [VCA - VBC] / 3
Assuming ABC rotation. Depending on how you define "unbalanced", your calculation can change from here. You could define it as 3I2 (symetrical components); this is how I would define based on my experience. If you look in power quality standards, and power quality equipment manuals, you will find several other definitions.
It depends on the system.
For a delta-connected, three-wire, system, the line voltage is exactly the same as the phase voltage.
For a wye-connected, four-wire, system, the line voltage is 1.732 (the square-root of 3) times the phase voltage.
If, by 'fix', you mean 'establish' or 'standardise', then for a three-phase, four-wire, system, the 'line-to-line' (not'phase-to-phase'!) voltage will be 1.732 times the 'line-to-neutral' (not 'phase-to-neutral'!) voltage.
Phase to Phase voltageCorrection to the above answer:There is no such thing as a 'phase-to-phase' or 'phase-to-ground' voltage. The correct terms are 'line-to-line' (or 'line voltage') and 'line-to-ground' (or 'phase voltage'). Transmission-line voltages are line-to-line (or 'line') voltages.
Nominal transmission and distribution voltages are line voltages. So '66 kV' is a line-to-line voltage. Note that there is no such thing as a 'phase-to-phase' voltage -the correct term is 'line-to-line'. Using the term, 'phase-to-phase', indicates a lack of understanding of a.c., which is not uncommon! Incidentally, the symbol is 'kV', not 'KV'.
The conductors that connect a three-phase supply to its load are called 'line conductors' or, more simply, 'lines'. The individual generator stator windings, transformer winding, or loads are called 'phases'. Lines and line terminals are identified by colours, letters, numbers, or combinations of letters and numbers. For example, A-B-C. Phases are identified by using the letters assigned to the line terminals between which the phases are connected, e.g A-B, B-C, and C-A. Voltages measured between lines ('line-to-line') are termed 'line voltages', and currents that pass through the lines are called 'line currents'. Voltages measured across a generator's windings, transformer windings, or individual loads, are called 'phase voltages', and the currents that pass through these are called 'phase currents'. For a three-phase, three-wire, system, the phase- and line-voltages are numerically-equal to each other. For a three-phase, four-wire, system, the line voltage is 1.732 times larger than the phase voltage.
It depends on the type of three-phase system. If it's a three-wire system, then the phase voltage is numerically equal to the line voltage. If it's a four-wire system, then the phase voltage is numerically equal to the line voltage divided by 1.732 -in your example, this works out to be 5.77 V.
Line to line voltage is not the same as line to neutral voltage because line voltages are 120 degrees apart. They are related by: Line to neutral voltage * tan (120 degrees) = Line to neutral voltage * 1.73.Additional CommentFor delta-connected systems, the line voltage is the same as the phase voltage.For wye-connected systems, the line voltage is larger than the phase voltage by a factor of 1.732. The reason for this is as follows:Because any two phase voltages are displaced from each other by 120o, they must be added vectorially, not algebraically, to find the line voltage. As the above answer points out, this means that the relationship between the two is the square-root of 3, or 1.732.
First of all, there is no such thing as a 'phase-to-phase' voltage. The correct term is 'line-to-line' voltage. Secondly, without knowing what you mean by 'overall voltage', there is no way of answering your question.
380V ÷ √3 = 219.4
Phase to Phase voltageCorrection to the above answer:There is no such thing as a 'phase-to-phase' or 'phase-to-ground' voltage. The correct terms are 'line-to-line' (or 'line voltage') and 'line-to-ground' (or 'phase voltage'). Transmission-line voltages are line-to-line (or 'line') voltages.
There is phase to phase voltage in 3 phase system.AnswerYou don't get voltage 'phase-to-phase'; it's 'line-to-line'!
The formula to use is, phase voltage /1.73 = phase to neutral (ground) voltage.CommentThere is no such thing as a 'phase to phase', or 'phase to neutral' voltage. The correct terms are 'line to line' and 'line to neutral'. So the above answer should read: line voltage/1.73= line to neutral voltage = phase voltage.
Phase, if you are referring to line, as power line from pole.
The term, 'unbalanced system' refers to an unbalanced load. Under normal circumstances, an unbalanced load leads to unbalanced line currents. The line voltages are determined by the supply and remain symmetrical, even when the load is unbalanced. As your question refers to a 'line to neutral' voltage (i.e. a phase voltage), you must be referring to a star (wye) connected load, in which case the phase voltage (line to neutral voltage) is 0.577 (the reciprocal of the square-root of 3) times the line voltage (line to line voltage).
Phase to phase voltage is 1.732 (the square root of 3) times the phase to star point (neutral) line voltage.e.g. if the line voltage is 220Vphase voltage = 1.732x220 = 380V (approx)Additional AnswerYou might also like to know that the line voltage leads the phase voltage by 30 electrical degrees. And, incidentally, the correct expressions are 'line-to-line' not 'phase-to-phase', and 'line-to-neutral' not 'phase-to-neutral' (think about it, a line voltage is measured from the junctions between adjacent phases, so they cannot be 'phase to phase'!)
To match 2 phase line voltage it has to be the same voltage.
Let's get the terminology correct. A 'phase voltage' is measured across a phase, whereas a line voltage is measured between two lines. So there is no such thing as a 'phase to phase' voltage -it's a line to line voltage (hence the term 'line voltage').
The current is the same in the three live wires. The voltage can be described as the line voltage (phase to neutral) or the phase voltage (phase to phase) which is larger by a factor of sqrt(3). So a line voltage of 230 v corresponds to a phase voltage of 400 v.
In a 3 phase system, the voltage measured between any two phase is called line to line voltage.And the voltage measured between line to neutral is called phase to neutral (line to neutral) voltage.AnswerThere is no such thing as a 'phase-to-phase' or a 'phase-to-neutral' voltage. The correct terms are 'line-to-line' and 'line-to-neutral'.The voltage between any two line conductors is called a line voltage.In a three-phase, three-wire, system, the line voltage is numerically equal to the phase voltage.In a three-phase, four-wire, system, the voltage between any line conductor and the neutral conductor is called a phase voltage. The line voltage is 1.732 times larger than the phase voltage.