Let's get the terminology correct. A 'phase voltage' is measured across a phase, whereas a line voltage is measured between two lines. So there is no such thing as a 'phase to phase' voltage -it's a line to line voltage (hence the term 'line voltage').
Volts divided by 1.73. The three phase system has to be a three phase four wire wye (star) system. The three phase voltage of 440 that is supplied in the question will not give you 220 volts single phase. 440/1.73 = 254 volts. To obtain 220 volts single phase, a three phase four wire system voltage of 220 x 1.73 = 380 is needed.
440 volts could be single phase or three phase.
Phase voltage is equal to the line to line voltage divided by root 3 or 1.732. So 440 L-L/1.732 = 254V. Your phase voltage is 254V.
For the same power - Watts - you need to run twice as many amps at 220V than at 440V. For the same load, it'll pull half the amps at 220V than it did on 440V
Well that is probably a very complicated circuit. You should just look for a Inverter with 220V single phase input and 415V three phase output. It should be that hard to find.
29
because all over the world there is an standard rate of voltage
The three generated waves in three phase are spaced 120 degrees apart.
yes it can
Phase voltage is equal to the line to line voltage divided by root 3 or 1.732. So 440 L-L/1.732 = 254V. Your phase voltage is 254V.
Just calculate from motorplate: Watts/(Square3*V*cosP)=> example motorplate says: 4.7Kw 440V cosP: 0.82 4700W/(square3*440V*0.82) here you get minimum setting for motor, this case 7.5A JT
50amp but if considering the breaker cannot withstand starting current you need to size the breaker up.
It is 230V single phase and 440V in 3 phase system at 50 Hz.AnswerIf the single-phase voltage is 230 V, then the three-phase voltage must be 400 V, not 440 V. The line voltage is 1.732 times the phase voltage.
Use a transformer. A 208-240v single phase line has 2 power leads. Consult your local electrician for help! 440v systems are not for toying with when questions like this are asked.
For the same power - Watts - you need to run twice as many amps at 220V than at 440V. For the same load, it'll pull half the amps at 220V than it did on 440V
in 3 phase motor u1,v1,w1 give to the short terminal and remaining v2,u2,w2 give t0 the in coming power supply of 440v
Well that is probably a very complicated circuit. You should just look for a Inverter with 220V single phase input and 415V three phase output. It should be that hard to find.