The most typical industrial three phase voltage in the United States is 480volts. In Canada it is 600 volts.
The car's alternator is a three phase generating system. Inside the alternator is a three phase full wave diode bridge that changes the AC generated voltage to a DC voltage.
No. A 277 volt ballast needs the correct voltage to operate. The 277 voltage is derived from the star point voltage of a 480 volt three phase system (277/480). The 208 voltage is a three phase line voltage whose star-point voltage is 120 volts (120/208).
If secondary side of the 3 phase transformer has any issue, it would result unbalanced voltage between phases. Other reason could be if the load on one phase is highly different than other phase, it also would result in unbalanced voltage.
To calculate the three-phase voltage in New Zealand, you typically use the formula for line-to-line voltage (V_L) in a three-phase system, which is V_L = √3 × V_Ph, where V_Ph is the line-to-neutral voltage. In New Zealand, the standard line-to-neutral voltage is 230V, so the line-to-line voltage would be approximately 400V (230V × √3). Ensure that the system's configuration (such as star or delta) is taken into account when performing calculations.
The single phase voltage in India is 230v when we check with the phase and the nutral single line
If the phase voltage is 230 V, then (providing you are describing a three-phase, four-wire, system), then the line voltage will be 1.732 larger -i.e. 400 V.
The single phase voltage in India is 230v when we check with the phase and the nutral single line
Three-phase voltage in Germany is 400V, single-phase voltage is 230V.
There is no 'total voltage' in a three-phase system. There are three line voltages and three phase voltages.
The three phase voltage is 380 the hertz is 50
In India its 415V, 50Hz.
Phase to Phase voltageCorrection to the above answer:There is no such thing as a 'phase-to-phase' or 'phase-to-ground' voltage. The correct terms are 'line-to-line' (or 'line voltage') and 'line-to-ground' (or 'phase voltage'). Transmission-line voltages are line-to-line (or 'line') voltages.
The current is the same in the three live wires. The voltage can be described as the line voltage (phase to neutral) or the phase voltage (phase to phase) which is larger by a factor of sqrt(3). So a line voltage of 230 v corresponds to a phase voltage of 400 v.
The formula you are looking for is - phase voltage/1.73 = phase to neutral voltage.
Let's get the terminology correct. A 'phase voltage' is measured across a phase, whereas a line voltage is measured between two lines. So there is no such thing as a 'phase to phase' voltage -it's a line to line voltage (hence the term 'line voltage').
The voltage in a three phase delta system is stated by the phase to phase voltage. If it is a wye connection the phase to neutral is represented by the two voltages. e.g. 120/208, 240/415, 277/480, 347/600, 7225/12500, etc.