answersLogoWhite

0


Best Answer

In mains power generation terminology power is commonly generated at the power station in three separate "phases". The "Hots" ("Live" wires in European parlance) of each of the phases are timed to "lag" each other in wave/cycle terms as follows: the Hot of the first phase is generated at 0o (Zero degrees, which is equivalent to 360o), the Hot of the 2nd phase is timed to lag the Hot of the the first phase by 120o and the Hot of the third phase is timed to lag the Hot of the first phase by 240o.

[In Europe, where power is generated at 50Hz, the "Hots" (labelled as lines L1, L2 and L3) making up each of the three phases commonly have the colors Brown for L1, Black for L2 and Grey for L3; the Neutral wire is Blue. (These are equivalent to the UK's old wiring regulations for 3-phase supply cable of Red, Yellow and Blue where the Neutral wire was Black.) In the US or other countries which use 3-phase power generated at 60Hz the colors for the hots are generally black, red and yellow and neutral is white but other colors such as orange and blue may also be used to differentiate between separate circuits.]

In electrical wiring terminology each "Phase" of a single phase circuit really comprises a pair of wires. The pair is made up of a "Hot" and a "Neutral". (A "Live" and a "Neutral" in European parlance.)

The number of phases delivered from the street to a building depend on its power usage requirements: an industrial building or site which uses 3-phase power for powerful motors, ovens, etc. must have its electricity delivered as 3-phase power; commercial offices or domestic homes typically only use single-phase lights and appliances, so such homes and offices usually only require single-phase power to be delivered from the street.

Homes in the US typically have a single phase service which is "split" into two "hots" with a common "neutral" wire - that comes from the center tap point of the secondary winding on the nearby service voltage-step-down transformer - in order to support high-power 240 volt appliances, such as electric dryers, ranges and ovens. The voltage across the two "hots" is 240 volts while the voltage from any hot to neutral is 120 volts.

So, to answer the main question asked:

All the Hot wires for each circuit within a phaseare kept common to each other within a given building.

and

All the Neutral wires for each circuit within a phase are kept common to each other within a given building.

Under current wiring regulations and codes the hot and neutral wires for each circuit within a phase that is installed within certain designated areas of a building must be protected by a Ground Fault Current Interruptor (GFCI), also known as a Residual Current Device (RCD). That is a sensitive current-breaking device (also known simply as a "circuit breaker" or a "trip") which continuously monitors for significant current imbalances between the Hot and Neutral wires and/or a significant fault current flowing in the protective Ground wire. If any current imbalance or any fault current is detected the protective device must break the supply of power to the circuit within a maximum allowed time. To protect human life a typical design would be engineered to trip within 200 mS (mS = milliSeconds = thousandths of a Second) on detecting an Earth leakage current of 30 mA ( mA = milliAmps = thousandths of an Amp) and to trip in less than 40 mSec at a higher Earth current of 150 mA.

All Ground wires for the various circuits within a building are bonded together only on the supply side of any protective devices. They are connected to a reliable Ground point (Earth in European parlance) at the location where the mains supply enters the building.

[Older buildings, which were wired up under older wiring regulations and codes where no GFCI or RCD was specified, merely have all white neutral/ground wires bonded together and connected to a reliable Ground point (Earth in European parlance) at the location where the supply enters the building.]

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

User Avatar

Wiki User

13y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: In wiring of a building which is kept common neutral or phase?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Wiring 240 volt electric motor?

Phase to Phase, Neutral to Neutral, Earth to Earth. If its a new motor it should have the wiring for a capacitor and centrifugal switch done internally. Otherwise run a wire from the phase, through the centrifugal switch, into capacitor, into start winding, and back to neutral. So many different kind of single phase 240v motors though, cap start, cap start cap run etc all involving different wiring


Why is residential wiring called single phase if there are 2 phases coming in?

residential wiring are called single phase because the 2 phases coming in are one is neutral and the other is line.the neutral has a potential zero with ground and it is to provide a closed path for the current to flow through..the line is having a potential of 230V with the ground and a line together with a neutral is called a phase


How do you tap off of a 480 volt disconnect?

You don't. You hire a qualified electrician who doesn't need to read this page for the answer. That said, if you are merely curious as to the methods: "480" Volt will be 3-phase with either Delta wiring (480 phase-to-phase, NO neutral), or Wye wiring (480 phase-to-phase, and 277 phase-to-neutral). You can use this directly, to run three phase equipment from all three phases, to run equipment at 480 from just two phases (being careful to keep loads balanced), or to run lighting circuits from the 277-to-neutral (being careful to size the neutral conductor carefully). You can also step it down to "208", which will be 208 phase to phase and 120 phase to neutral -- "standard" line voltage. But seriously, if you need to ask the question, you SHOULD NOT be touching 480 switchgear and wiring, for the safety of both yourself and others.


What are the color codes of old residential wire wiring?

red = phase, black = neutral, green = earth


In 3 phase wiring why neutral is thinner than that of phase?

As normally load distribution is done equally in all three phases, almost balanced current is drawn by load and current flow though neutral is very small when compared to the phase and hence difference in cable size is observed


Where do you place the leads to measure the single phase voltage of a three phase power source?

In delta wiring measure between any two phases.In wye wiring measure between any phase and neutral.Do you know whether you have delta or wye wiring?CommentThe above answer should read 'between any two lines' and 'between any line and neutral'. There is no such thing as a 'phase' conductor!


How many neutrals for three-phase multi circiuts?

For a three phase distribution system there is one neutral. In North America the electrical code allows three individual branch circuits to connect with one neutral as long as the three circuits each use an individual phase leg. This differs from 120/240 volt single phase wiring where only two legs can be used with one neutral.


Can an electrical short be caused a phase to a phase?

It could be a phase to phase, ph to neutral or earth fault. In single ph wiring ph to ph exhibits no short ckt faultAnswerYes, but you have got the terminology wrong. There is no such thing as 'phase-to-phase', the correct term being 'line-to-line'. So you can have a short circuit as a result of a line-to-line fault, a line-to-neutral fault, or a line-to-earth fault.


Why neutral is not requied in 3 phase?

As far as I understand, you don't need neutral line for connecting appliances that is 3-phase compilant. You only need the neutral line to connect a single phase appliance, which you connect along with one of the three lines.


If in the three phase connection phase to phase voltage is 400v what will be the phase neutral voltage?

The formula to use is, phase voltage /1.73 = phase to neutral (ground) voltage.CommentThere is no such thing as a 'phase to phase', or 'phase to neutral' voltage. The correct terms are 'line to line' and 'line to neutral'. So the above answer should read: line voltage/1.73= line to neutral voltage = phase voltage.


What is substitute of neutral wire?

None.In standard single phase wiring there are 3 wires: hot (black), neutral (white), and ground (green). Each has a different purpose and none can be used for any other purpose.


Why the diameter of earth leads always more than phase and neutral?

For easy and quick identification of the leads, so that the user does not make mistake while connecting the leads.AnswerFor residential wiring, the earth wire rarely has a cross-sectional area that is larger than the line (not 'phase') or neutral conductors.