answersLogoWhite

0


Best Answer

There should be no voltage on the neutral wire to ground. This is a serious situation. Call a qualified electrician to check this out.

User Avatar

Wiki User

15y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Why neutral ground voltage is 120v sometime 0v?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

If 120V is present on a120V relay coil what will the voltage reading be across the closed set of relay contacts on a 120V circuit?

0v The relay is designed to act as a switch when voltage is applied across the coil. The contacts open or close but only pass through whatever is connected to those terminals. <<>> When a relay coil is energized the relay's contact change status. The closed set of contacts will open. The 120 volt circuit that is connected will turn off. As to the voltage at the contact terminals, it depends on where you are taking the voltage reading from and to. On the source side of the terminal there will be a reading of 120 volts to neutral or ground. On the other side of the contact terminal there will be zero volts to the neutral or ground. This is because that wire is in series with the load to neutral. A meter reading across the relay terminals will read 120 volts.


What should be the primisable voltage between neutral and earth in a three phase system?

It is the line to line voltage divided by 1.73. 600V / 1.73 = 347V 480V / 1.73 = 277V 380V / 1.73 = 220V 208V / 1.73 = 120V


What is the voltage of a series circuit with four voltage drops of 30 volts?

there is 120V across the circuit.


If you need 220v 3-phase power how many wires are required coming in from the transformer or power pole and what are the voltages or potential purposes of each wire load 110v load 220v neutral ground?

In 120/208V 3 phase system you have 5 wires: three hots, one neutral, and one ground. You have 208V between any two hots and 120V between any hot and neutral. The neutral is the same as in a single phase system. Clarification: Only 4 wires maximum come from the pole - 3 phases and a neutral, and then only if the transformers are on the pole. The ground is always locally derived from a ground rod(s) and/or cold water pipe ground. Most of the time, only 3 wires come in from the pole - the 3 phases in a Delta configuration (Delta has no neutral). The neutral is then derived from a local transformer connected in a Delta-Wye setup. The neutral is the center connection in the Wye. So, from the utility feeder to the transformer - 3 wires. From the transformer (wherever it is located) to the building service entrance panel - 4 wires. The ground is connected at the service entrance panel, and from there to the rest of the building you would have all 5 wires. Clear? In the US, 208/120 is a standardized mains voltage, but in some parts of the world, the phase-to-phase voltage is 220. In that case, the phase-to-neutral potential (in a 3-phase system) would be 127 Volts, not 120.


How single phase 208 works without a neutral?

There must be a 'return' connection if the load is to work. So, you cannot simply connect the load to the line conductor and expect it to work. It must also be connected to the neutral. In some circumstances (e.g. with no ground-fault interrupter installed), it will also work if you connect it to earth (ground) instead of the neutral, but this will contravene most electrical regulations and should NEVER be done.

Related questions

How does an electric utility ground electricity delivered to your home?

Electricity is delivered to homes through transformers. The center of the transformer output winding is connected to ground. This center tap is then connected to the home power panel as the neutral lead. The voltage between the grounded neutral and either of the "hot" legs is half the voltage between the legs. In the US and Canada, the full voltage between the legs is 240V and between either leg and neutral is 120V.


How do you test residential electricity with a DVOM?

For most tests you want the AC Volts setting. On US residential service you should see 240V between one hot and the other, 120V between a hot and neutral, 120V between a hot and ground, and 0V between neutral and ground. Variations of 10% or less from these numbers are OK. You should see very little to no voltage when testing neutral to ground. Don't use the current setting unless you know what you are doing. You can tost your meter.


Single phase 4 pole Gen alt w 240V 60hz output no neutral. you check from each lead to ground and get 50-70V How do you get a neutral for connecting Gen to a standard breaker box having 240V and 120V?

Neutral is at the jumper that changes it from 120v to 240v. Two stator windings are used in series to make 240v; at that junction is (when wired in Series)your neutral/common/ground. Ground this terminal and use it for your neutral/common. When wired in parallel you have 110v and the jumper is removed and there is no common/neutral and ground is from the frame of the generator.


If 120V is present on a120V relay coil what will the voltage reading be across the closed set of relay contacts on a 120V circuit?

0v The relay is designed to act as a switch when voltage is applied across the coil. The contacts open or close but only pass through whatever is connected to those terminals. <<>> When a relay coil is energized the relay's contact change status. The closed set of contacts will open. The 120 volt circuit that is connected will turn off. As to the voltage at the contact terminals, it depends on where you are taking the voltage reading from and to. On the source side of the terminal there will be a reading of 120 volts to neutral or ground. On the other side of the contact terminal there will be zero volts to the neutral or ground. This is because that wire is in series with the load to neutral. A meter reading across the relay terminals will read 120 volts.


Can you use a 120v cord that will fit a 240v socket the appliance is 240 and the cord is thick?

120v and 240v cords usually have different end configurations and will not plug into the different recepticles. However, if you changed the plug end, and the cord has the proper size rating, then yes, you could use the same cord. But, it also depends on the cord too. Most 120v cords only have three wires in them. One "hot one "neutral" and one "ground" wire. A 240v cord would have FOUR wires, two "hot" wires, one neutral wire, and one ground wire. Therefore, if you changed the voltage from 120v to 240 using a 3 wire cord, you'd not have a ground wire and that could be VERY dangerous. Note that occasionally a 240v device (e.g. some motors) will only need three wires (red,black,green, no neutral) and can be wired with a 120v cord if the cord is rated for 240v.


Why your new light fixtures dont come on when you have 120V at the socket?

My first suspicion is you have a loose or disconnected neutral. TURN THE BREAKER OFF WHEN CHECKING THE CONNECTION. To include all points, even the obvious, make sure you have changed the lamps to known working lamps from another fixture. How do you know it has 120 volts at the socket? If you tested it with a voltage tester or a multimeter, which wires were you connected to? In order to troubleshoot you need to make three measurements, at the BOXif wall or ceiling mounted or RECEPTACLE if plugged in with a cord, not the fixture socket the lamp screws into. Hot to ground (volts AC) Should be 120 volts nominal. This can vary from about 110-130v. Hot to neutral (volts AC) Should be 120 volts nominal. Neutral to Ground (volts AC) Should be 0 volts. These wires are electrically joined at your main panel. If you have 120v hot to neutral, your circuit is working properly. Any problem will lie in the fixture or the connections to the fixture. If you do not have 120v to neutral but you do have 120v hot to ground, your neutral is not connected. TURN THE BREAKER OFF and check the connection. If you do not have 120v to neutral or120v to ground, your hot is not connected. TURN THE BREAKER OFF and check the connection. If you have anything other than 0 volts neutral to ground, your fixture connection may be okay, but your neutral is not connected properly going back to the main panel. This is a dangerous situation, and it can result in fire over time. In this case have an electrician inspect the situation immediately!


A system has 220v ac L and neutral can be possible two hot leg 120v ac be used?

yes, but the two 120v legs would have to come from breakers that are on the two different bus bars in the panel box, otherwise, you will get zero voltage between the two hot wires and 120 volts to neutral.


On a 220 volt circuit where the white wire is common how many volts would the red wire be?

3 OR 4 . you only need 2 wires for 220, 1 phase is 120v between 2 of them its 220v . you also should have a ground for the third wire ,and the newer stuff requires a neutral or white wire for the 4th wire. hope i helped , D


What is voltage in Mexico city?

It is 120V/60Hz


What is the role of a transformer in a neighbourhood?

High voltage(23000vac) is delivered to your community then stepped down(240vac 2 phase 120v to neutral) to allow use of common household appliances.


Could anybody help the reading between earth and neutral in the incomer supplying power to the house is 120V while live and neutral reads normal 220V and live-earth reads up to 298V.?

It sounds like either you have a bad ground connection or that ground and neutral are NOT bonded at the main panel only. There is either a strap or screw in main panel that connects ground and neutral. Also check the connection to a ground rod and that the ground rod is intact.


Can 120V appliance work with 220V?

120V appliance will not work on 220V. Use an instrument transformer or voltage regulator to adjust the high voltage to the desired level.