First, the amps drawn will be different depending on the supply voltage. You do not say which yours is - 208? 460? 4,160? Second, manufacturers normally give two different current figures, one for the motor running with full load, and one for 'locked rotor'. Locked rotor current is the very high current drawn when power has been applied, but the motor has not had time to start spinning. No one that I know of publishes 'current at no load' for their motors. Since a motor with no load is not doing anything useful, no one really cares how much current is being drawn. It's kind of like putting your car up on a jack so the wheels are off the ground and asking how much fuel will the car burn sitting still with the wheels turning at 50 miles an hour! Also, since a three phase motor does not have a neutral connection, it is, in effect, always delta connected. Delta and wye connections have the same voltage and phase characteristics IF you do not have a neutral. The motor cannot tell the difference.

User Avatar

Wiki User

15y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: At how many amps should a 30kw motor run at with no load in delta?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

How do you measre the running amps a star delta motor?

Measure the current on the incoming side of the starter.


Why does my star delta motor run at very high amps in delta and eventually trips on overload after changing the overload protection device.It should normally run at 25amp in delta but runs at 170 amps?

THE FIRST THING IS TAKE THE READING OFF LOAD AND SEE IF THEY ARE BALANCED. HAS THE MOTOR BEEN RECENTLY REWOUND? GET A MOTOR REPAIR COMPANY TO LOOK AT THE MOTOR AND SEE IF IT HAS BEEN WOUND CORRECTLY. IF THE STAR-DELTA WORKS CORRECTLY IT SHOULD START IN STAR FOR ABOUT FIVE TO TEN SECONDS AND GO INTO DELTA THIS IS DEPENDANT ON THE STARTING CURRENT THE MANUFACTURE OF THE SWITCH AND THE APPLICATION. CHECK ALL THREE PHASES ARE BALANCED AND IF THEY ARE THE MOTOR WINDINGS MAY NOT BE CORRECTLY WOUND. SOME HAVE STAR CONNECTIONS BUILT IN.LOOKING AT THE AMPERAGE THE LOAD REQUIREMENT IS ONLY A FRACTION OF WHAT YOU ARE GETTING SO IT LEAVES ONLY TWO THINGS I......MOTOR FAULT 2.....WHAT EVER THE MOTOR IS DRIVING IS PUTTING A MASSIVE PRESSURE ON THE MOTOR CAUSING IT TO OVERLOAD.


What is cable size for 3 110kw 3 phase induction motor 100 meter run for cable 400v?

first calculate the full load amps of the motor by using formula, line amps = KW * 1000 / (line volts*1.732*P.F) Of the mentioned motor the amps will be 96 amps at the P.F 0.8. The motor will have star delta starter so the cable size would be 2 runs of 3c x 70 sq mm AL if laid in air.


Why one phase shows 0 Amps while a delta connected 3 phase induction motor runs?

Cause 2 phase is applied to the motor and another phase is disconnected ... in this condition ur motor cannot run longer ,it will trip on over current or burn ur motor winding .


How many amps does a 2 hp 210 volt single phase motor draw?

Then you are trying to get more HP out of the motor that it can supply. Back off on the load that the motor is driving or put a bigger motor onto the load.

Related questions

How do you measre the running amps a star delta motor?

Measure the current on the incoming side of the starter.


Why does my star delta motor run at very high amps in delta and eventually trips on overload after changing the overload protection device.It should normally run at 25amp in delta but runs at 170 amps?

THE FIRST THING IS TAKE THE READING OFF LOAD AND SEE IF THEY ARE BALANCED. HAS THE MOTOR BEEN RECENTLY REWOUND? GET A MOTOR REPAIR COMPANY TO LOOK AT THE MOTOR AND SEE IF IT HAS BEEN WOUND CORRECTLY. IF THE STAR-DELTA WORKS CORRECTLY IT SHOULD START IN STAR FOR ABOUT FIVE TO TEN SECONDS AND GO INTO DELTA THIS IS DEPENDANT ON THE STARTING CURRENT THE MANUFACTURE OF THE SWITCH AND THE APPLICATION. CHECK ALL THREE PHASES ARE BALANCED AND IF THEY ARE THE MOTOR WINDINGS MAY NOT BE CORRECTLY WOUND. SOME HAVE STAR CONNECTIONS BUILT IN.LOOKING AT THE AMPERAGE THE LOAD REQUIREMENT IS ONLY A FRACTION OF WHAT YOU ARE GETTING SO IT LEAVES ONLY TWO THINGS I......MOTOR FAULT 2.....WHAT EVER THE MOTOR IS DRIVING IS PUTTING A MASSIVE PRESSURE ON THE MOTOR CAUSING IT TO OVERLOAD.


What is the difference between full load amps and running load amps?

Full load amps is the maximum rated amps that the motor should draw according to its nameplate rating. Running load amps is the actual amperage the motor is drawing at that point in time when the test is taken. Some motor loads vary depending on if the load is cyclic. The reading on this type of motor would be from no load amps to full load amps.


Why is the automatic star to delta starter tripping?

The only thing that will trip the starter, is the load of the motor. Check the motor leads to make sure you have not crossed them over coming from the motor junction box. If the motor current is normal nameplate full load amps when run across the line then reduce the timing of the timer on the switch over from star to delta.


What is cable size for 3 110kw 3 phase induction motor 100 meter run for cable 400v?

first calculate the full load amps of the motor by using formula, line amps = KW * 1000 / (line volts*1.732*P.F) Of the mentioned motor the amps will be 96 amps at the P.F 0.8. The motor will have star delta starter so the cable size would be 2 runs of 3c x 70 sq mm AL if laid in air.


How many amps are needed for a 220V well?

It depends on the motor. The motor determines the amperage. Should be written on the well pump itself.


How many amps should a starter draw?

It depends on the size and type of the motor being started.


Why one phase shows 0 Amps while a delta connected 3 phase induction motor runs?

Cause 2 phase is applied to the motor and another phase is disconnected ... in this condition ur motor cannot run longer ,it will trip on over current or burn ur motor winding .


How many amps does a 2 hp 210 volt single phase motor draw?

Then you are trying to get more HP out of the motor that it can supply. Back off on the load that the motor is driving or put a bigger motor onto the load.


What is the difference between Full load Amps and Service Factor Amps on an electric motor?

Full load amps is the amperage at which the motor was designed to work at to achieve its rated horsepower. Service factor amps is the amount of a periodic overload at which a motor can operate without overload or damage. Continuous operation within the service factor amps will shorten the insulation and motor bearing life of the motor as the motor will be operating at a higher temperature than it was designed to.


How many amps should a 220 volt well pump pull?

The horsepower of the motor is needed to complete this answer.


What is the phase current of a three phase 2.2kw 415v motor connected in star?

The line current would be the same if the motor were connected in delta. The current can be based on the rule of thumb which says 7 amps must be allowed for a 1-HP single-phase motor on 240 v. A 2.2 kW motor is three times as powerful, and on a three-phase supply of the same voltage (240/415) it would draw 7 amps.