You can run a 6AWG cable from a 2 pole 60A breaker in the main box to your garage, into a small sub-box with 4 15A circuit breakers, and hang a outlet from each circuit breaker. That would do 4 normal power tools fairly safely.

Your better off bringing a 100A sub service to your garage if your going to spend the time and money on the project.

------------------

60 amps will work just fine but 40 or 50 amps will probably do you just as well. Odds are you won't be running more than one tool at a time and you can install multiple 15 or 20 amp circuits. Your individual circuits can add up to more than the size of service you actually supply.

A compressor may need a 240v 2-pole circuit. Lights are not much of a consideration unless you are doing something unusual. Install enough receptacles that one is always convenient.

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Can you pull 60amp from main box to garage and run a lot of power tools?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Electrical Engineering

Can you tap meter and feed panel in detached garage?

No. Any connections to the detached garage have to be after the main disconnect of your house panel. You have two options here. You can replace meter with a meter disconnect combo and have the main feed your house and add a breaker to feed the garage or You could install a 400 ap service and place two disconnects at the meter. one for the house and one for the garage. unless you are going to have a serious electrial load in the garage you sould just feed off the panel in the house for cost effectiveness.


Can you put a 60amp breaker and a 50amp breaker on a 60amp subpanel just as long as they are not being used at the same time?

You can. Using these size breakers in a 60 amp sub panel might be pushing the limit for breaking the sub panels feeder breaker. The breaker feeding the sub panel will have to be no bigger than 60 amps because of the main bus bar capacity of the sub panel. It would be better to install a 100 amp sub panel and then there would be a bit of a buffer and you will have the ability to add additional small load circuits.


Do you need a main disconnect on the feeder wires running to a detached garage running from the box in the house?

Yes you do. The detached garage will either be fed with a single circuit or a sub panel. The wire feeding the garage will need to be protected and that is the purpose of the breaker (disconnect). The breaker size will be determined by the size of the wire that is used on this circuit.


What gauge wire to use for direct burial for a garage that is 400 feet from your house?

Depends on the size of the sub-panel in that garage. If you are installing a 60 amp sub-panel 400 feet away from the main service panel then use AWG # 4.


Will turning off the main breaker turn off all the power to the circuit breaker box?

No. Power to all the circuit breakers will be cut off except for the Main power breaker. The Main power breaker (which supplies power to all other breakers and will say 100, or whatever your max breaker box power is, on it )will have power going to it all the time, unless power is turned off outside the house.

Related questions

How do you power a 50 amp kiln in your garage?

By supplying it with a 50 amp feed from your main distribution panel.


Where to find discount hand power tools online?

There are numerous online resources which provide hand power tools at discounted prices. The main resources to visit are www.toolking.com and www.mydiscounttools.com.


What are the purposes of Clarke tools?

Clarke tools are a brand name that are used for multiple purposes. Clarke offers a variety of power tools, screwdrivers, wrenches and such other small tools. It's main competitor is Dewalt tools.


Why would your power go out to your garage but not to your house and no fuses be blown?

Does the garage have a separate breaker box or fuse box inside? Is there a separate power feed for the garage? In the 70's and 80's some cities were allowing aluminum wiring INSIDE residences. If the wire from the main fuse/breaker panel is aluminum there is a real possibility that you might have a bad connection between the fuse box or breaker panel and the outlets in the garage.


Where is the best place to find slims power tools?

I looked online for slims power tools, and I found the companies main website. www.slimspowertools.com. You can order the products here, or you could try www.ebay.com, or www.amazon.com for a better deal.


What stores in Orange County, California sell Bosch Power Tools?

Bosch power tools main office is located in california. Their website www.boschtools.com will tell you all of the locations that are near you, you can also purchase online and have them sent to your home.


I have 100 amp breaker box I want to put a 60amp double pole breaker in and run 60 amp wire to me garage. Do the y make a 60 amp breaker box with more then 4 breaker slots. or can you run 60 amp wire?

Rated for exactly 60amps you will find limited breaker spaces due to the rating of the hardware used in it's construction and air circulation restrictions from the equivalent limited enclosure area. When rated at a determined amperage level it is required to construct the device based on the worse case possible scenario which includes a continuous running load. This will determine it's minimum standards according to local and national codes for hardware, room, spacing, and, layout. This does not limit you to only this size panel though. As long as you install the 60amp breaker first in your house panel anything installed down stream {from the load side of the 60amp breaker will be protected up to 60 amps. Therefore you are permitted to exceed those ratings and still remain within code because regardless of what your load is, it can not exceed 60 amps without tripping the breaker. You can install a 12/24 {12-full size or 24-half size [mini's]} 100amp panel for additional breaker spaces and the cost difference is negligible. One code issue to consider is if the sub panel in the garage is not in line of sight of that 60amp breaker then you might want to install another 60amp breaker in the garage panel to interrupt the incoming power giving you the ability to work on/in the garage panel without the possibility of someone re-energizing it mistakenly. I would suggest before this to consult with an electrician for a load calculation to determine if there is 60amps of available power in the 100amp panel in the home. This panel may not have an over-current 100amp main breaker which means it is possible to exceed the panel rating of this unprotected panel. Installing a 100amp over-current device {breaker, fused safety switch, fuse block etc...} like your 60 amp breaker to the garage it will limit the total load to only 100amps. Good Luck and obtain all permits and full understanding of the project and safety protocols in it's regards.


What are some tools of geography?

=maps and globes are the main tools.=


60amp service going to garage I am installing hot-tub that requires a 220-50amp breaker how do you mesure the Amp-Volt reading at garage Garage power is mainly for lights and occasional tools?

I would personally run a new line from the main service from your house to your hot tub.. This might seem like a pain in the butt considering your situation it would save ALOT of headaches in the future.. With the recent advancements in plug in cars, lawn mowers, etc. and the fact that the more circuitry you have for future expansion in your garage the better off you will be.. You can read both the voltage and the current with a Fluke brand multimeter. the current (amperage) is read with the "clamp on" feature that is built on the instrument.. Make sure to purchase the meter with this feature.. (They are beautiful!) There are a few things that hot tubs require before installation.. Make sure your are at LEAST 22 feet 6 inches from ANY overhead power.. If there are ANY non GFCI receptacles (outlets) within 10 feet from your tub make sure to change them to the GFCI type.. If you have lighting within 10 feet from the tubs basin that lighting also has to be GFCI protected .. If your power is being run underground the tub must be at least 6 feet away from the underground pipe.. One thing that is missed above is that the hot tub circuit itself has to be on a GFI breaker.


How do you get to the garage in need for speed undercover?

hit the first option on the main screen and the screen after that


Can a garage lift lift a car with ease?

These lifts are designed to lift a car with ease - they are machines and require a power supply and that varies by manufacturer. the main selling point of a car lift is that it can "double your space) in your garage by lifting you car up on something that looks like a bunk bed.


Where can one purchase a Bosch radion online?

Bosch radion are tools that provide power and radio service when the main power is down. Amazon, Lowes, Best Buy, Home Depot and overstock carry them.