For 600V insulation Megger NETA & IEEE recommends:

Test voltage = 1000V

Test Duration = 1 minute

Test Value = 100 Megohm minimum (corrected to 20 degrees C)

Typically you megger conductor to conductor and conductor to ground. Most will not megger for the full minute and it is up to your discretion. Just watch that the resistance continually increases during the test period. If it is decreasing then you should hold the full minute and investigate the reason.

For multiple conductor cables then twist all of the conductors together and pull out one at a time and megger it to the bundle. This will expedite thetesting into as few as tests possible while still thoroughly checking the cable.

Note that test voltage and values are based strictly on the insulation rating and the conductor size is pretty much irrelevent.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Do you have Megger testing procedures and measurement limits for power cables at 600V rating 250mm plus 50mm THHN?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

What value of tester is to be used for measuring insulation resistance of three phase 600V cables?

The typical test equipment for this is a megger. The megger is connected to two conductors at a time to test the insulation between the two.


In instrument cables with a rating of 600 volts can you use a megger tester with a 250 voltage range?

Yes, you could, but why would you? Maintenance or fault testing on a cable rated at 600 volts involves applying the rated voltage (600 volts) and measuring the leakage current. Doing this test at 250 volts doesn't really test the cable. High potential (hipot) testing involves the application of even higher voltages for test purposes.


How do you use megger tester?

Megger testOn the whole megger testing is non destructive. What happens is a DC voltage is applied to the device or winding under test. It is an insulation test to see is the insulation has been injured in any way to cause a short circuit when normal power is applied to it. On my megger there are 3 ranges 300V, 750V, and 1000 volts. Applying the proper voltage is essential to not damaging the device you are testing. Working voltages up to 240 volts should use the 300 range. Working voltages up to 600 volts use the 750 volt range and working voltages above 600 use the 1000 volt range. As you can see if you used the 1000 volt range on a device that had a working voltage of say 24 volts you could damage the insulation just by testing it. So meggering a device is non destructive if you use the tester as its instructions tell you to.


What are the roles and responsibilities of testing and commissioning engineer in substation?

There are a great many. but to keep it simple: (a) pressure-testing the cables/switchgear/transformers/etc. (i.e. testing the insulation using high-voltage test sets); (b) testing the operation of the switchgear; (c) testing the operation of the protective relays. ...but lots more.


When are megger testers used?

On the whole megger testing is a non destructive test. What happens is a DC voltage is applied to the device or winding under test. It is an insulation test to see is the insulation has been injured in any way to cause a short circuit when normal power is applied to it. On my megger there are 3 ranges 300V, 750V, and 1000 volts. Applying the proper voltage is essential to not damaging the device you are testing. Working voltages up to 240 volts should use the 300 range. Working voltages up to 600 volts use the 750 volt range and working voltages above 600 use the 1000 volt range. As you can see if you used the 1000 volt range on a device that had a working voltage of say 24 volts you could damage the insulation just by testing it. So meggering a device is non destructive if you use the tester as its instructions tell you to.

Related questions

What has the author Chriss A Grosvenor written?

Chriss A Grosvenor has written: 'Design and testing of NFRad--a new noise measurement system' -- subject- s -: Radiometers, Equipment and supplies, Noise, Measurement, Evaluation, Coaxial cables


What value of tester is to be used for measuring insulation resistance of three phase 600V cables?

The typical test equipment for this is a megger. The megger is connected to two conductors at a time to test the insulation between the two.


How do you use a meggar?

A megger is used to test the resistance of high voltage cables, insulation and motor windings. The test employs a megohm meter.


What is standard units of measurement of raceway used to carry cables?

it is in metre


In instrument cables with a rating of 600 volts can you use a megger tester with a 250 voltage range?

Yes, you could, but why would you? Maintenance or fault testing on a cable rated at 600 volts involves applying the rated voltage (600 volts) and measuring the leakage current. Doing this test at 250 volts doesn't really test the cable. High potential (hipot) testing involves the application of even higher voltages for test purposes.


What is meggers?

A megger is an electrical instrument that is used to measure the resistance of insulation by applying a DC voltage to the conductor. One lead is connected to the conductor and the other lead is connected to ground. Safe insulation reading to ground should be above 2,000,000 ohms or 2 megs.


What is the best test for testing battery cables?

Look at it. If the wire is corroded and/or the insulation is bulging, replace the cable.


How do you use megger tester?

Megger testOn the whole megger testing is non destructive. What happens is a DC voltage is applied to the device or winding under test. It is an insulation test to see is the insulation has been injured in any way to cause a short circuit when normal power is applied to it. On my megger there are 3 ranges 300V, 750V, and 1000 volts. Applying the proper voltage is essential to not damaging the device you are testing. Working voltages up to 240 volts should use the 300 range. Working voltages up to 600 volts use the 750 volt range and working voltages above 600 use the 1000 volt range. As you can see if you used the 1000 volt range on a device that had a working voltage of say 24 volts you could damage the insulation just by testing it. So meggering a device is non destructive if you use the tester as its instructions tell you to.


Electrical equipment PAT?

Portable appliance testing (PAT) is basically a method of testing (using a device and by sight) that any electrical equipment, cables, devices, machinery is safe to use.


What are the roles and responsibilities of testing and commissioning engineer in substation?

There are a great many. but to keep it simple: (a) pressure-testing the cables/switchgear/transformers/etc. (i.e. testing the insulation using high-voltage test sets); (b) testing the operation of the switchgear; (c) testing the operation of the protective relays. ...but lots more.


What has the author Patricio A A Laura written?

Patricio A A Laura is known for writing the book "The Chaos of Longing," which explores themes of love, loss, and longing through poetry and prose. It has received critical acclaim for its raw and emotional storytelling.


What are the five basic troubleshooting procedures?

check power check cables isolate problem take note of errors remember what you've tried