No, each segment of a tandem breaker is what the breaker rating on the handle states. Tandem breakers are used when there is no space left in the distribution panelboard. You get an extra circuit by removing the full size breaker and installing a tandem breaker,

User Avatar

Wiki User

7y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Does a 15 amp tandem breaker equal 30 amps total?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What is the continuous current draw on a 20 amp circuit breaker?

Depends on what you have connected to the circuit. It is less than 10 amps or the breaker would trip. A rule of thumb is you design for about 80% load related to the breaker. For 20 amps that would equal 16 amps.


What's a double breaker 20 amps and 30 amps?

A double breaker is a breaker that has 2 switches on it. One of the switches is 20 amps and the other is 30 amps.


What is KA in Circuit Breaker?

KA stands for kilo-amps, or thousands of amps. Thus a 2KA breaker means it will trip when the load exceeds 2,000 amps.


How many volts can you draw off of a 15amp breaker?

It's the amps that are controlled by the breaker not the volts. You can have a 600 volt 15 amp breaker, you can have a 347 volt 15 amp breaker. The breaker will trip when you exceed 15 AMPS.


What size wire and breaker do you need for a 5000 watt garage heater?

Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker


Is it necessary to balance a house fuse panel to save electricity and if so why and how is it done?

A balanced house panel should be the ultimate goal. It will not save you electricity as the watt meter on the house monitors the use of power from both legs of the incoming power. To balance a panel you want the current from L1 to Neutral to equal L2 to Neutral. The neutral carries the unbalanced current between L1 and L2. A perfectly balanced panel will have no current on the neutral. It is done by knowing what the current draw is on every breaker. Then they are physically positioned so that they equal each other on the opposite leg. e.g. breaker 1 on leg L1 = 5 amps, breaker 2 on leg L2 = 10 amps, breaker 3 on leg L1 = 10 amps, breaker 4 on leg L2 = 5 amps. Total up all amperages on L1 and then on L2 , if they are equal then the panel is balanced with no current on the neutral.


Why does a 15 amp breaker trip while a small appliance is on?

The total amps on the circuit exceeds 15 amps. It is possible your appliance is drawing more than 15 amps, but more likely that there are other things on the circuit causing the total current to be exceeded.


If a breaker is rated for 30 amps and is 2 poles is it ok to put an appliance that draws 50 amps?

The number that is on a breaker is the amount of amperage that the breaker can deliver before it trips. This is the same regardless of how many poles the breaker is.


How do you calculate the number of breakers and their amp ratings when some are 120V and some are 240V for a given main service of 100A?

add the amps from each breaker reguardless of voltage. If the total exceeds 80 amps, it means you cannot use all breakers at full amp. For example: If the total equals 90, then you will have to make sure ten amps are not being used at that time. Yes, you do have 100 amps, however it is safest to run eighty percent of your total amps., at one time. The number of breakers has noting to do with the amps. You can use one breaker rated at 80 amps, or you can use four twenty amp breakers.


What size breaker should be used for a 3.6 kW oven?

3000 / 240 = Amps. You de-rate a breaker by 20 % for continuous load like an oven. You could get by with a 20 Amp breaker and 12 AWG wire. However, I would recommend 30 Amps and 10 AWG for an oven for the long run.


Is a 15 amp double tandem the same as a double pole 30 amp?

No the outlet holes are in parallel so the total ampacity of the receptacle is still 15 amps.


What is 6InA in circuit breaker?

61 nano-amps is 0.061 milliamps or 0.000061 amps